Instruction manual
172
Protective 
Operation
Output is 
turned OFF 
and motor 
coasts to a 
stop.
EF (External fault)
Inverter receives an external 
fault input from control circuit 
terminal.
EF0: External fault reference 
through MEMOBUS 
communications
EF1: External fault input 
command from control 
circuit terminal S1
EF2: External fault input 
command from control 
circuit terminal S2
EF3: External fault input 
command from control 
circuit terminal S3
EF4: External fault input 
command from control 
circuit terminal S4
EF5: External fault input 
command from control 
circuit terminal S5 *
EF6: External fault input 
command from control 
circuit terminal S6 *
EF7: External fault input 
command from control 
circuit terminal S7
Check the following:
•  NO/NC contact selection 
(constant).
•  Wiring is made properly.
•  Signal is not input from 
the PLC.
CPF-00
Inverter cannot communicate 
with the Digital Operator for 5 
s or more when power is 
turned ON.
Cycle power after confirming 
that the Digital Operator is se-
curely mounted. If the fault re-
mains, replace the Digital 
Operator or Inverter.
CPF-01
Transmission fault occurred 
for 5 s or more when trans-
mission starts with the Digital 
Operator.
Cycle power after confirming 
that the Digital Operator is se-
curely mounted. If the fault re-
mains, replace the Digital 
Operator or Inverter.
CPF-04
EEPROM fault of Inverter 
control circuit was detected.
• Record all constant data 
and initialize the con-
stants. (Refer to page 50.)
•  Cycle power. If the fault 
remains, replace the 
Inverter.
CPF-05
AD converter fault was de-
tected.
Cycle power.
If the fault remains, replace 
the Inverter.
Fault Display Inverter 
Status
Description Causes and Corrective 
Actions
Digital 
Operator
RUN (Green) 
ALARM (Red)