Instruction manual
186
Control Circuit
Input
Sequence
S1 Multi-function input 
selection 1
Factory setting closed:FWD run
open: Stop
Photocoupler 
insulation, 24 
VDC, 8 mA
S2 Multi-function input 
selection 2
Factory setting closed:REV run
open: Stop
S3 Multi-function input 
selection 3
Factory setting: External fault 
(NO contact)
S4 Multi-function input 
selection 4
Factory setting: Fault reset
S5 Multi-function input 
selection 5
Factory setting: Multi-step speed 
reference 1
S6 Multi-function input 
selection 6
Factory setting: Multi-step speed 
reference 2
S7 Multi-function input 
selection 7
Factory Setting: JOG command
SC Multi-function input 
selection common
For control signal
Frequency reference
RP Master reference 
pulse train input
33 kHz max.
FS Power for frequency 
setting
+12 V (permissible current 20 mA max.)
FR Master frequency ref-
erence
0 to +10 VDC (20 kΩ) or 4 to 20 mA (250 kΩ) or 0 to 20 
mA (250 Ω) (1/1000 resolution)
FC Frequency reference 
common
0 V
Output
Multi-function contact output
MA NO contact output Factory setting: fault Contact capacity
250 VAC 1 A or less,
*3
30 VDC 1 A or less
MB NC contact output
MC Contact output 
common
P1 Photocoupler output 1 Factory setting: Run Photocoupler 
output +48 VDC, 
50 mA or less
P2 Photocoupler output 2 Factory setting: Frequency agree
PC Photocoupler output 
common
0 V
AM
Analog monitor output
*2
Factory setting:
Output frequency 
0 to +10 V
0 to +10 VDC, 2 mA or less, 
8-bit resolution
AC Analog monitor 
common
0 V
Type Terminal Name Function (Signal Level)