Instruction manual
54
 appears on the display for one second and the set data 
returns to its initial values in the following cases.
1. If the set values of Multi-function Input Selections 1 to 7 
(n050 to n056) are the same
2. If the following conditions are not satisfied in the V/f pat-
tern setting:
Max. Output Frequency (n011) ≥ Max. Voltage Output 
Frequency (n013)
> Mid. Output Frequency 
(n014)
≥ Min. Output Frequency 
(n016)
For details, refer to Adjusting Torque According to Appli-
cation (V/f Pattern Setting) on page 55.
3. If the following conditions are not satisfied in the jump 
frequency settings:
Jump Frequency 3 (n085) ≤ Jump Frequency 2 (n084)
≤ Jump Frequency 1 (n083)
4. If the Frequency Reference Lower Limit (n034) ≤ Fre-
quency Reference Upper Limit (n033)
5. If the Motor Rated Current (n036) ≤ 150% of Inverter 
rated current
6. If constant n018 is set to 1 (Acceleration/Deceleration 
Time Unit is 0.01 s) when n018 is set to 0 (Acceleration/
Deceleration Time Unit is 0.1 s) and a value exceeding 
600.0 s is set for an Acceleration/Deceleration Time (n019 
to n022)
NOTE