Flue gas temperature-diagram of a VARINO GRANDE as function of the load
4.5. Correction values for different operating conditions
4.5.1. Stand-by loss correction values
Average temperature difference *
Dtm
°C
30
40
50
60
70
Stand-by loss correction
DqB
%
-40
-20
± 0
20
40
* Average temperature difference = Average boiler water temperature minus ambient air temperature
Average boiler water temperature = Average of supply and return temperature
4.5.2. Nominal load related to altitude
80
85
90
95
100
105
0 500 1000 1500 2000
H (m)
qF (% nominal)
The actual correction may be smaller than this, since a margin has been allowed for barometer fluctuations.
This also takes into account using the optional intake duct for external air intake (max. pressure loss according to
chap. 4.4).