Operating Instructions and Installation Instructions
VARINO GRANDE 350 - 600
We reserve the right to make changes to dimensions and construction 24 Edition 10.07.2015
© Copyright YGNIS AG CH-Ruswil
9.4. Information level
Entry by pressing the PROG key twice. The entry is confirmed by the point after the 1
st
figure flashing. The first
figure shows the step number, the last two figures the current value. By pressing the ►> key, the individual steps
can be read one after the other.
Step no. Information (actual values)
1 Boiler temperature in °C
2 Return flow temperature in °C
3 Status display with 4 figures
Figure 1 = Heat requirement 0: no requirement
I: requirement
Figure 2 = Burner switch/external safety 0: start not possible
I: start possible
Figure 3 = Air pressure monitor 0: switch open
I: switch closed
Figure 4 = Gas pressure monitor 0: switch open
I: switch closed
4 External temperature in °C
(only with "fixed value" control; otherwise display -36)
5 Waste gas temperature in °C
6 Speed of the combustion air fan in RPM
7 Desired boiler temperature (only with "fixed value" control, "analog desired value" control
or fitted heating controller)
8 Operating hours counter
9 Burner setting in % (10 – 100%)
10 Start pulse counter
11 Oxygen level in waste gas in % O
2
12 Speed correction for fan (deviation from the stored pre-setting) in RPM. Corresponds to the
correction to maintain the set oxygen level.