Operating Instructions and Installation Instructions

Edition: 02 / 2015 Page 37 / 56
VARMAX TWIN - Installation, Use and Maintenance
On generator No. 2
Line No. Value
• Inputs/outputs test menu
Check the outputs
Alarm relay
Relay test (7700) Relay output QX1
Isolating valve Q1.2
Relay test (7700) Relay output QX3
Reset the outputs
Relay test (7700) No test
• Con guration menu
Check the hydraulic diagram
Generator 1 inspection No. (6212) 14
Generator 2 inspection No. (6213) 0
DHW information (6215) 0
Information about heating circuits 3, 2 and 1 (6217) 0
F. CONFIGURATION OPTIMISATION
VARMAX TWIN optimisation:
The Varmax Twin may be optimised as necessary using the parameters in the Flow menu. Refer to
the NAVISTEM B3000 boiler's controller manual for more details.
Diagram: VX211
page 6 / 6
Maintenance optimisation
A maintenance message may be generated that does not set the generator to fault. This maintenance
message may be displayed after the following 3 counters have expired:
Time since last maintenance (or commissioning): set parameter 7044 to 12 months
(Maintenance / Special regime menu)
Burner's operating hours (parameter 7040 - menu Maintenance / Special regime menu)
Number of starts (parameter 7042 - menu Maintenance / Special regime menu)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.