Operating Instructions and Installation Instructions
Page 42 / 56 00BNO9132-#
VARMAX TWIN - Installation, Use and Maintenance
Line No. Value
• Heating circuit 1 menu
Adjust the comfort setting
Comfort setting temperature (710) - - -
Adjust the curve slope
Heating curve slope (720) - - -
• Switch the heating regime to permanent comfort
VX210 diagram only:
• Domestic hot water menu
Adjust the comfort setting
Comfort setting (1610) - - -
• Activate the DHW mode
VX220 diagram only:
• Consumption circuit 1 menu
Set the output setting to be taken into
account if the consumption circuit is
requested
Cons request output T° (1859) - - -
On generator No. 2
• Confi gure the isolating valve and its end of run: Confi guration menu
Valve command
Relay output QX3 (5892) K37 exhaust fl ap
End of run
Input H5 (5977) Exhaust fl ap info return
• Confi gure as generator No. 2: LPB network menu
Appliance number
Appliance address (6600) 2
Segment number
Segment address (6601) 0
Adjust the bus supply
Bus supply function (6604) Automatic
Adjust the clock rate
Clock operation (6640) Slave without
adjustment
• Make sure that the communication cable is fully connected between the 2 generators (
!
respect
the polarity).
• Switch off and back on again generator 2. If the communication has been correctly established,
Diagrams: VX210 / VX220