Operating Instructions and Installation Instructions

Edition: 02 / 2015 Page 45 / 56
VARMAX TWIN - Installation, Use and Maintenance
VX210 diagram only:
Domestic hot water menu
Con gure an Anti-Legionnaires' Disease
function
Anti-Legionnaires' Disease function
(1640)
- - -
Periodic Anti-Legionnaires' Disease
function (1641)
- - -
Day week Anti-Legionnaires' Disease function (1642) - - -
Anti-Legionnaires' Disease setting temperature (1645) - - -
Anti-Legionnaires' Disease function duration (1646) - - -
VARMAX TWIN optimisation:
The Varmax Twin may be optimised as necessary using the parameters in the Flow menu. Refer to
the NAVISTEM B3000 boiler's controller manual for more details.
Diagrams: VX210 / VX220
page 8 / 8
Maintenance optimisation
A maintenance message may be generated that does not set the generator to fault. This maintenance
message may be displayed after the following 3 counters have expired:
Time since last maintenance (or commissioning): set parameter 7044 to 12 months
(Maintenance / Special regime menu)
Burner's operating hours (parameter 7040 - menu Maintenance / Special regime menu)
Number of starts (parameter 7042 - menu Maintenance / Special regime menu)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.
Adjust the DHW release mode DHW release (1620) Timer program 4/
DHW
Line No. Value
Timer programme 4/DHW menu
Preselection
Preselection (560) - - -
Adjust the timer programming
On / off phases (561...566) - - -
• DHW tank menu
Adjust the over value
Output setting temperature over value (5020) - - -