Owner's manual

3.5 EXAMPLE
A vortex flowmeter has a maximum output of 20.538 litres/min at 20mA. It is
required to display the flowrate in litres/min with 1 decimal point and the total in
litres with no decimals. High and low alarms are required at 18 l/m and 2 l/m
respectively. The instrument is then programmed as follows.
CAL00 0 No Pulse Output
CAL01 00020 Span (Whole Numbers)
CAL02 5380 Span (Decimals)
03 0.05 Cutoff Point as a fraction of Span
04 1 Rate decimal position
05 1 Timebase
06 01 Filter disabled
07 0 Total decimal position
08 0001 Total Conversion (set to 1.0000)
09 0000 Total Conversion (decimals)
10 00002 Low Alarm
11 0000 Low Alarm
12 00018 High Alarm
13 0000 High Alarm
14 0 Linear Input
15 xxxx Accumulated Totals
SOFT 202A1.11 Software Version
Programming 19