User’s Manual EJX510B and EJX530B Absolute and Gauge Pressure Transmitters IM 01C27F01-01EN IM 01C27F01-01EN Yokogawa Electric Corporation 8th Edition
i EJX510B and EJX530B Absolute and Gauge Pressure Transmitters IM 01C27F01-01EN 8th Edition Contents 1. 2. Introduction................................................................................................ 1-1 1.1 Safe Use of This Product ................................................................................. 1-2 1.2 Radio Wave......................................................................................................... 1-3 1.3 Warranty................................
ii 5. Installing Impulse Piping.......................................................................... 5-1 5.1 5.2 6. 6.2 8. 5.1.1 Connecting Impulse Piping to a Transmitter....................................... 5-1 5.1.2 Routing the Impulse Piping................................................................. 5-1 Impulse Piping Connection Examples............................................................ 5-2 Wiring..........................................................................
iii 8.4 9. Self-Diagnostics............................................................................................... 8-23 8.4.1 Identify Problems by Using the Device Configuration Tool............... 8-23 8.4.2 Alert Report....................................................................................... 8-24 8.4.3 Checking with Integral Indicator........................................................ 8-26 Maintenance.......................................................................
1. 1-1 <1. Introduction> Introduction Thank you for purchasing the DPharp EJX Pressure transmitter. Your EJX Pressure Transmitter was precisely calibrated at the factory before shipment. To ensure both safety and efficiency, please read this manual carefully before you operate the instrument. NOTE This manual covers the EJX510B absolute pressure transmitter and EJX530B gauge pressure transmitter.
Functional grounding terminal Caution This symbol indicates that the operator must refer to an explanation in the user’s manual in order to avoid the risk of injury or death of personnel or damage to the instrument. 1.1 1-2 <1. Introduction> Safe Use of This Product For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument.
1.2 Radio Wave IMPORTANT - - - 1.3 This instrument is equipped with a wireless module which is designated as a certification of construction type as a wireless facility for 2.4 GHz band low-power data communication system of the Radio Act. Refer to 2.12 “Regulatory Compliance for Radio and Telecommunication” for detail.
1.5 <1. Introduction> 1-4 ATEX Documentation This is only applicable to the countries in European Union.
2. 2-1 <2. Handling Cautions> Handling Cautions This chapter provides important information on how to handle the transmitter. Read this carefully before using the transmitter. EJX Series transmitters are thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment. Also check that all transmitter mounting hardware shown in figure 2.1 is included.
2.4 <2. Handling Cautions> Selecting the Installation Location The transmitter is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location.
2.5 Pressure Connection WARNING • Never loosen the process connector bolts when an instrument is installed in a process. The device is under pressure, and a loss of seal can result in a sudden and uncontrolled release of process fluid. • When draining toxic process fluids that have condensed inside the pressure detector, take appropriate steps to prevent the contact of such fluids with the skin or eyes and the inhalation of vapors from these fluids.
NOTE When storing the instrument with a battery pack, it is recommended to put the instrument in Deep Sleep mode to conserve the batteries. For details on how to switch to Deep Sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode”. • <2. Handling Cautions> 2-4 CAUTION This instrument has been tested and certified as being intrinsically safe. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair.
<2. Handling Cautions> Note 2. Installation • Installation should be in accordance with ANSI/ISA-RP12.06.01 and the National Electric Code (NFPA 70). • Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments. • Note a warning label worded “SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY,” and “INSTALL IN ACCORDANCE WITH DOC. NO. IFM037-A20”.
2-6 <2. Handling Cautions> Note 2. Installation • Installation should be in accordance with local installation requirements.
2.8.4 IECEx Certification (2) Operation Caution for IECEx Intrinsically safe type. WARNING Take care not to generate mechanical sparking when access to the instrument and peripheral devices in a hazardous location. (3) Maintenance and repair WARNING The instrument modification or parts replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certification. (4) Name Plate SUPPLY OUTPUT MWP mA DC V DC Note 2.
2-8 <2. Handling Cautions> Note 4. Battery Pack • Use only YOKOGAWA battery pack F9915MA or F9915NS. 2.10 Pressure Equipment Directive (PED) Note 5. Special conditions for Safe Use • In case the enclosure of the Pressure Transmitter is made of aluminum, if it is mounted in an area where the use of apparatus of equipment protection level Ga is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
(3) Operation CAUTION • The temperature and pressure of fluid should be maintained at levels that are consistent with normal operating conditions. • The ambient temperature should be maintained at a level that is consistent with normal operating conditions. • Please take care to prevent water hammer and the like from inducing excessive pressures in pipes and valves. If phenomena are likely, install a safety valve or take some other appropriate measure to prevent pressure from exceeding PS.
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of he FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,may cause harmful interference to radio communications.
3. 3-1 <3. Component Names> Component Names Antenna (Note 3) Ground terminal Zero-adjustment screw Pressure-detector section CPU assembly Integral indicator RF assembly Slide Mounting switch screw Transmitter section Amplifier Cover Write protection switch D E WR Not in use Hardware write protection switch (WR) Write Protection Switch Position (Note 1) Write Protection Note 1: Note 2: Note 3: D E D E L H L H NO (Write enabled) YES (Note 2) (Write disabled) F0301.
4. 4.1 <4. Installation> 4-1 Installation Precautions Before installing the transmitter, read the cautionary notes in section 2.4, “Selecting the Installation Location.” For additional information on the ambient conditions allowed at the installation location, refer to section11.1 “Standard Specifications.” NOTE To connect this transmitter to the Field Wireless Network, information for connecting to the field wireless devices needs to be set beforehand. Refer to 7.
4-2 <4. Installation> IMPORTANT IMPORTANT Do not rotate the transmitter section more than the above limit. Tighten the hexagonal nut part of the capsule assembly. See Figure 4.3. Transmitter section Capsule assembly Setscrew Pressure-detector section F0403.ai Figure 4.3 4.3 Tightening Transmitter Rotating Transmitter Section WARNING Intrinsic safe type transmitters must be, as a rule, do not rotate transmitter section if it is powered.
4.5 <4. Installation> 4-3 Changing the direction of the antenna Adjust the direction of the antenna to be in the upright position. Figure 4.5 show factory setup antenna position. If the transmitter is installed to horizontal impulse piping, follow the procedure below and change the antenna position. 1) Loosen the two mounting screws at the bottom of the antenna by using a 2.5mm Allen wrench (see Figure 4.5).
5. 5.1 5-1 <5. Installing Impulse Piping> Installing Impulse Piping Impulse Piping Installation Precautions The impulse piping that connects the process outputs to the transmitter must convey the process pressure accurately. If, for example, gas collects in a liquidfilled impulse line, or the drain for a gas-filled impulse line becomes plugged, it will not convey the pressure accurately.
(3) Impulse Piping Slope 5-2 <5. Installing Impulse Piping> Tap valve The impulse piping must be routed with only an upward or downward slope. Even for horizontal routing, the impulse piping should have a slope of at least 1/10 to prevent condensate (or gases) from accumulating in the pipes.
6. 6.1 <6. Wiring> 6-1 Wiring Mounting Antenna and Wiring For Amplifier housing code 8 and 9, an antenna is not attached to the transmitter. The following provides the instructions for mounting the antenna and installing the remote antenna and wiring using antenna extension cable. IMPORTANT The antenna connector is covered with a cap at the time of delivery. Keep the cap attached until the installation of the antenna or antenna cables to protect the inside connection part.
6-2 <6. Wiring> 6.1.2 Mounting External Antenna and Wiring Antenna Extension Cable 6.1.2.1 Mounting of External Antenna Mount the external antenna at the proper location according to the wireless environment described in 2.4 Selecting the Installation Location. The mounting to the pipe such as 50 mm (2-inch) pipe needs to secure the enough strength to endure a strong wind, vibration and so on. The antenna must be mounted vertically.
6-3 <6. Wiring> Antenna Antenna extension cable 2: 10 m Antenna Protect by self-bonding tape Arrester Grounding cable Antenna extension cable 1: 3 m Protect by self-bonding tape Antenna extension cable 1: 3 m Transmitter body Transmitter body F0604.ai Figure 6.4 Wiring the antenna extension cable CAUTION Use the dedicated antenna extension cable provided by Yokogawa as accessories for the transmitters.
<6. Wiring> 6-4 6.1.2.3 Mounting of Arrester and Wiring 6.2 Mount an arrester between the extension cables and connect the grounding cable to the grounding terminal of the arrester as required. When using the antenna extension cable with an arrestor, Class C grounding with the grounding resistance of 10 Ω is required. Always ground the transmitter case in accordance with national and local electrical codes.
7-1 <7. Operation> 7. Operation 7.1 Preparation for Starting Operation using four categories (Check function, Maintenance required, Failure, and Off specification) according to NAMUR NE107* This section describes the operation procedure for the EJX530B as shown in figure 7.1.
Verify and Change Transmitter Parameter Setting and Values The parameters related to the following items are minimum required to be set for operation, and set at factory as specified in order. Confirm or change the parameters if needed. • Measurement range (measurement lower/ upper limit, unit) 7.2 Zero Point Adjustment After completing preparations for operating the transmitter, adjust the zero point. There are two zero point adjusting ways.
7.4 ■ 7-3 <7. Operation> Connecting to the Field Wireless Network ■ Preparation work prior to connecting to a Field Wireless Network This transmitter does not need to be connected with a physical wire. Instead of physical wiring, it is necessary to set the field wireless devices to communicate with before installing the transmitter. This procedure is called a provisioning.
■ <7. Operation> Connecting to a field wireless network 7-4 (a) Deep sleep The action after installing the battery pack varies depending on the silence setting. Mounting the battery pack automatically starts a search for the field wireless network. When the Field Wireless Integrated Gateway is found, the instrument enters the join status.
<7. Operation> 7-5 NOTE If the transmitter searches the Field Wireless Network for long time at low ambient temperature condition, sometimes error “AL.70 LOWBAT” is displayed on the Integral Indicator. Even though using new batteries, it can occur. It occurs because of battery characteristics. After joining to the Field Wireless Network, this error will be cleared within one hour if battery has no failure. 7.5 Shutting Down the Transmitter Shut down the transmitter as follows.
8. Setting Parameters This transmitter can remotely handle range changes, Tag No. setup, monitoring of selfdiagnostic results, and Zero Point Adjustment, etc. according to communication with the field wireless configuration tool or the device configuration tool. 8.1 8-1 <8. Setting Parameters> Environment for parameter setting After installing the battery pack, perform provisioning and have the transmitter join the field wireless network.
Table 8.1 8-2 <8. Setting Parameters> Parameter Usage and Selection Item Tag No Description Output Sets the tag No. as Device Tag (Software Tag). Sixteen characters (alphanumeric characters, including - and •) can be set. The process variable and the diagnostic result can be output.
8-3 <8.
8-4 <8. Setting Parameters> Online Menu (continued) (AI1 DP) • Block Info • Block Mode • Dynamic Variables • Configuration • Calibration • Others (Block Info) • Tag Description (Block Mode ) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Dynamic Variables) • Process Value • Simulation (Process Value) • Process Value.Status • Process Value.
8-5 <8. Setting Parameters> Online Menu (continued) (AI2 SP) • Block Info • Block Mode • Dynamic Variables • Configuration • Others (Block Info) • Tag Description (Block Mode ) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Dynamic Variables) • Process Value • Simulation (Process Value) • Process Value.Status • Process Value.
8-6 <8. Setting Parameters> Online Menu (continued) (AI3 Temp) (Block Info) • Block Info • Block Mode • Dynamic Variables • Configuration • Others • Tag Description (Block Mode ) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Dynamic Variables) • Process Value • Simulation (Process Value) • Process Value.Status • Process Value.
8-7 <8. Setting Parameters> (b) Detachable antenna type (Amplifier housing code: 8 or 9) Online Menu • UAPMO • UDO • CO • TRANSDUCER • AI1 DP • AI2 SP • AI3 Temp (UAPMO) • Configuration • Diagnostics • Alerts • Power Status • Identification (Configuration) • UAP Option • Hardware Write Protect • Static Revision • Reset Energy Left • Radio Silence • Energy Harvest Type (Diagnostics) • Diagnostic Status • Diagnostic Status Detail.1 • Diagnostic Status Detail.
8-8 <8. Setting Parameters> Online Menu (continued) (AI1 DP) • Block Info • Block Mode • Dynamic Variables • Configuration • Calibration • Others (Block Info) • Tag Description (Block Mode ) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Dynamic Variables) • Process Value • Simulation (Process Value) • Process Value.Status • Process Value.
8-9 <8. Setting Parameters> Online Menu (continued) (AI2 SP) • Block Info • Block Mode • Dynamic Variables • Configuration • Others (Block Info) • Tag Description (Block Mode ) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Dynamic Variables) • Process Value • Simulation (Process Value) • Process Value.Status • Process Value.
<8. Setting Parameters> 8-10 Online Menu (continued) (AI3 Temp) (Block Info) • Block Info • Block Mode • Dynamic Variables • Configuration • Others • Tag Description (Block Mode ) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Dynamic Variables) • Process Value • Simulation (Process Value) • Process Value.Status • Process Value.
8-11 <8. Setting Parameters> (2) Menu Tree The menu tree of the device configuration tool of our recommendation is shown below. Refer to Subsection 9.2 “Calibration Instruments Selection” for the device configuration tool of our recommendation.
8-12 <8. Setting Parameters> Online Menu (continued) Device Configuration (continued) (AI2 SP) (Block Info) • Configure/Setup • Tag Description (Block Mode) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Configuration) (Block Mode) • Block Mode • Concentrator OID • Scale * • Process Value Filter Time • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Scale) • Scale.EU at 100% * • Scale.EU at 0% * • Scale.Units Index * • Scale.
<8. Setting Parameters> 8-13 Online Menu (continued) (Diagnostic) (UAPMO) (Diagnostics/Alerts) • UAPMO • Device Diagnostics • Diagnostic Status • Diagnostic Status Detail1, • Diagnostic Status Detail2 • Diagnostic Switch • Diagnostic Configuration (Power Status) • Energy Left • Power Supply Status (Process Variable) • AI1 DP • AI2 SP • AI3 Temp (AI1 DP) • Process Variable (Dynamic Variables) (Process Value) • Process Value • Simulation • Process Value.Status • Process Value.
8-14 <8.
Menu (Online) (continued) 8-15 <8. Setting Parameters> Device Configuration (continued) (AI2 SP) (Block Info) • Configure/Setup • Tag Description (Block Mode) • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Configuration) (Block Mode) • Block Mode • Concentrator OID • Scale * • Process Value Filter Time • Mode.Target • Mode.Actual • Mode.Permitted • Mode.Normal (Scale) • Scale.EU at 100% * • Scale.EU at 0% * • Scale.Units Index * • Scale.
8-16 <8. Setting Parameters> Menu (Online) (continued) (Diagnostic) (UAPMO) (Diagnostics) • UAPMO • Device Diagnostics • Diagnostic Status • Diagnostic Status Detail.1 • Diagnostic Status Detail.2 • Diagnostic Switch • Diagnostic Configuration (Diagnostic Configuration) (Power Status) • Energy Left • Power Supply Status • Power Supply Voltage (Process Variable) • AI1 DP • AI2 SP • AI3 Temp (AI1 DP) • Process Variable • Diagnostic.Other Faults • Diagnostic.Faults Non-Compliance • Diagnostic.
8.3.3 Parameters for Wireless Communication (1) Network Information Concentrator object block: Configuration Allows confirming the network information. (2) Update Time CO block: Data publication period Sets the update time value to 0.5 to 3,600 seconds. When amplifier housing code 7 is specified, note that more than one second is available. The setting affects the battery life. When update time is set 0 seconds, the transmitter is stopped to update process variables by way of the field wireless network.
When the device detects AL01 and AL02, the LCD display stays on regardless of the status in LCD mode. See Table 9.3 and 9.4 Alarm Message for details. 8.3.4 Tag and Device Information If these are specified when ordering, the designated Tag No. and device information are set and shipped. Tag No. and device information can be checked as follows. 8.3.6 Range Change The range values are factory-set as specified by the customer. To change the range, follow the steps below.
The low cut point has hysterisis so that the output around the point is behaved as below figure. Output mode: Linear Low cut mode: Zero Low cut: 20.00% 2% Input Setting range: 0 to 20% Hystrersis fixed at 10% of the cut point F0805.ai 8.3.8 Integral Indicator Scale Setup The following two displays are available for the integral indictor: pressure and temperature. The following two variables can be displayed on the integral indicator: % of pressure range, and % of temperature range.
(1) Zero Point Adjustment a. To set 0% at current input, perform following procedure. • Procedure to call up the calibration adjustment parameter (Cal Cmd). AI1 block: Cal Cmd: CAL_LOW The present output is changed from 13.83kPa to 13.50 kPa in CAL_LOW of the pressure (AI1 block) Cal Cmd parameter. This method is used only when the pressure at bottom of measurement range is zero. • Procedure to call up the lower limit adjustment parameter (Calibration Lowest Point).
(2) Span Adjustment Span Adjustment is function to change the input and output characteristic that assumed the bottom value (zero point) of measurement range a standard. Therefore, perform span adjustment (adjustment of the upper limit value) after zero adjustment (adjustment of bottom limit value). After adding the pressure at point of adjustment and setting pressure value as parameter, the transmitter calculates quantity of adjustment and performs adjustment automatically.
8-22 <8. Setting Parameters> 8.3.12 Switching to Deep Sleep Mode 8.3.13 Switching to Silence Mode When the instrument will not be used for a long time, switch the instrument to deep sleep mode to conserve battery power. To switch to deep sleep mode, follow the procedure below. • Procedure to call up the switch-to-deep-sleep parameter TRANSDUCER block: Special Cmd This is a function to pause the instrument when it cannot join the field wireless network after a specified time has elapsed.
8.4 <8. Setting Parameters> Self-Diagnostics UAPMO block: Diagnostic Status 8.4.1 Identify Problems by Using the Device Configuration Tool First, check Diagnostic Status of the self-diagnostic result. Table 8.
<8. Setting Parameters> 8-24 8.4.2 Alert Report EJX generates alert information related to Diagnostic Status and automatically sends to a field wireless gateway. To use this function, the following alert setting is necessary. When “Out of Service” for Diagnostic Status alert is required, choose “FALSE” for [Out of Service.Alert Disable] in the UAPMO block. Refer to the field wireless gateway User’s Manual for the setting procedure to obtain the alert information from the gateway.
Table 8.4 8-25 <8. Setting Parameters> Diagnostic Results Summary Diagnostic Status Contents Faults in electronics Faults in sensor or actuator element Installation, calibration problem Out of service Outside sensor limits Alert Type 78 77 76 75 74 NAMUR NE107 Category F F C O C Environmental conditions out of device specification. 73 O Power is critical low: maintenance need shortterm.
<8. Setting Parameters> 8-26 8.4.3 Checking with Integral Indicator NOTE If an error is detected by running self-diagnostics, an error number is displayed on the integral indicator. If there is more than one error, the error number changes at three-second intervals. See Table 9.4 regarding the error codes. F0807.ai Figure 8.
9. 9.1 Maintenance Overview WARNING Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body or inhalation of vapors when draining condensate or venting gas from the transmitter pressure-detector section and even after dismounting the instrument from the process line for maintenance. Maintenance of the transmitter is easy due to its modular construction.
Table 9.1 Name Provisioning device tool Field wireless configuration tool Digital manometer Pressure generator Pressure source 9-2 <9. Maintenance> Instruments Required for Calibration Yokogawa-recommended Instrument • FieldMate (R2.02.
Using pressure source with manometer Using pressure generator Reference pressure Reference pressure P Precision digital manometer P Pressure generator Supply pressure Figure 9.1 9.4 9-3 <9. Maintenance> Pressure source F0901.
9-4 <9. Maintenance> 9.4.1 Replacing the Integral Indicator 9.4.2 Replacing the RF Assembly This subsection describes the procedure for replacing an integral indicator. (See figure 9.2) This subsection describes how to replace the RF assembly (see Figure 9.2). ■ ■ Removing the Integral Indicator 1) Remove the cover. 2) While supporting the integral indicator with one hand, loosen its two mounting screws. 3) Dismount the integral indicator from the RF assembly.
4) Use a socket driver (width across flats, 5.5 mm) to loosen the two bosses. 5) Carefully pull the CPU assembly straight forward to remove it. 6) Disconnect the flat cable (cable with white connector at the end) that connects the CPU assembly and the capsule. NOTE Be careful not to apply excessive force to the CPU assembly when removing it. ■ Mounting the CPU assembly 1) Connect the flat cable (with white connector) between the CPU assembly and the capsule.
■ 9-6 <9. Maintenance> Reassembling the Capsule Assembly 1) Reattach the transmitter section to the pressure-detector section. Reattach the stopper with the hexagon-head screw. 2) Tighten the five setscrews.(Tighten the screws to a torque of 1.5 N·m) 3) Install the CPU assembly according to subsection 9.4.3. 4) After completing reassembly, adjust the zero point and recheck the parameters. The battery pack mounting screws cannot be separated from the battery pack so as to prevent drop-off.
■ 9-7 <9. Maintenance> Assembling 1) Insert new batteries into the battery case. Be careful of the orientation of the batteries. 2) Attach the two parts of the battery case to each other. 3) Tighten the two battery case mounting screws to a torque of approximately 0.7 N·m. The battery pack mounting screws cannot be separated from battery pack so as to prevent drop-off. CAUTION Observe the following precautions for the safe disposal of batteries.
■ How to replace and dispose of the batteries: This is an explanation about the new EU Battery Directive (DIRECTIVE 2006/66/EC). This directive is only valid in the EU. Batteries are used for this product. When you remove batteries from this product and dispose them, discard them in accordance with domestic law concerning disposal. Take a right action on waste batteries because the collection system in the EU on waste batteries are regulated.
9-9 <9. Maintenance> 9.5.2 Troubleshooting Flowcharts Output travels beyond 0% or 100%. The following sorts of symptoms indicate that transmitter may not be operating properly. Example : • There is no output signal. • Output signal does not change even though process variable is known to be varying. • Output value is inconsistent with value inferred for process variable. Connect the device configuration tool and check self-diagnostics.
<9. Maintenance> 9-10 Large output error. Connect the device configuration tool and check self-diagnostics. Does the selfdiagnostic indicate problem location? NO Refer to Alarm Message Summary in Subsection 9.5.3. NO Are valves opened or closed correctly? YES Fully open valve. NO Is impulse piping connected correctly? YES Refer to individual model user manuals and connect piping as appropriate for the measurement purpose.
<9. Maintenance> 9-11 9.5.3 Errors and Countermeasures Various diagnostics of the Al2 object and the static pressure is not supported in this instrument. Table 9.3 Integral indicator Error Message Summary (Causes and Actions) Factory NAMUR category Bit Diagnostic Status Diagnostic Status Detail Cause FC_SENSOR_FAIL FR_SENSOR_FAIL AL. 01 CAP.
Integral indicator <9.
Integral indicator <9. Maintenance> Factory NAMUR category Bit Diagnostic Status AL. 63 AI SIM C Bit 17 Simulation is active AL. 64 AI SIM AL. 65 AI SIM *1: *2: *3: *4: C Bit 17 Simulation is active Diagnostic Status Detail Cause SimulationActive (AI1) AI1 block is simulate mode. SimulationActive (AI2) AI2 block is simulate mode. SimulationActive (AI3) AI3 block is simulate mode.
Table 9.4 Error Message Summary (Output Actions) Factory Integral NAMUR Indicator category Bit Diagnostic Status Output actions Diagnostic Status Detail FC_SENSOR_FAIL FR_SENSOR_FAIL FC_UNOSC_FAIL FR_UNOSC_FAIL CAP_T_SENSOR_FAIL AL. 01 CAP. ERR F *2 Faults in sensor or Bit 26 actuator element CAP_EEPROM_FAIL CAP_EEP_IRREGULAR AMP_T_SENSOR_FAIL*3 AMP_EEPROM_FAIL AMP_EEP_IRREGULAR AL. 02 AMP.ERR F *2 9-14 <9.
<9. Maintenance> Factory Integral NAMUR Indicator category Bit Diagnostic Status Output actions Diagnostic Status Detail DP_OUTSIDE_LIMIT AL. 10 PRESS SP_OUTSIDE_LIMIT AL. 11 ST. PRSS O Bit 23 Outside sensor limits CAPT_OUTSIDE_LIMIT AL. 12 CAP. TMP AMPT_OUTSIDE_LIMIT AL. 13 AMP. TMP DP_TRIM_SPAN_ OUTSIDE AL. 53 P. ADJ DP_TRIM_ZERO_ OUTSIDE AL. 53 P. ADJ C AL. 55 SP. ADJ Installation, Bit 25 calibration problem SP_TRIM_SPAN_ OUTSIDE SP_TRIM_ZERO_ OUTSIDE AL. 55 SP.ADJ AL. 79 OV.
<9. Maintenance> Factory Integral NAMUR Indicator category AL. 30 RANGE AL. 31 SP. RNG O AL. 70*6 LOWBAT M AL. 70*6 LOWBAT Bit Diagnostic Status Output actions Diagnostic Status Detail Environmental DP_OUTSIDE_RANGE conditions out Bit 22 of device SP_OUTSIDE_RANGE specification Power is critical low: Bit 20 maintenance need short - term Power is low: Bit 19 maintenance need mid - term CRITICAL_LOWBAT*4 Bit 24 O/S AI3_OUT_OF_SERVICE AL.
10-1 <10. Parameter Summary> 10. Parameter Summary The setting of differential pressure (Al2 block) is invalid in this instrument. The output value of Al2 object and the output status are “0.0”(zero) and “Uncertain” respectively. Various diagnostics of the Al2 object and the static pressure is not supported in this instrument. Table 10.1 Object ID 1.
Object ID 1. UAPMO block (continued) 10-2 <10. Parameter Summary> Attribute Label ID 104 Reset Energy Left Description Initialize the remaining battery life (Energy Left) and reset it as new batteries. Perform the battery replacement. 0 = Continue (Cancel) 1 = Reset (Initialization) Default Handling value 0 (reading value W is always 0) 105 Power Supply Status Indicates the predicted battery level and the power supply method.
Object ID 1. UAPMO block (continued) 2. UDO block 3. CO block 10-3 <10. Parameter Summary> Attribute ID Label Default value Description Handling 120 Callibration problem Alert*2 The On/Off or priority for callibration problem Alert can be set. 1. On/Off setting 0 = FALSE, 255 =TRUE 2. Alert report priority: 0 to 15 1. TRUE 2. 15 W 121 Faults Sensor or actuator Alert*2 The On/Off or priority for Faults Sensor or actuator Alert can be set. 1. On/Off setting 0 = FALSE, 255 =TRUE 2.
Object ID 3. CO block (continued) 4. TRANSDUCER block 10-4 <10. Parameter Summary> Attribute ID Label Default value Description Handling 3 COMM_ CONTRACT Indicates the Contract information. The following shows the components. 1. ContractID 2. Contract_Status 3. Actual_Phase --- R 4 PUB_ITEM_MAX Maximum PUB_ITEM value --- R 5 PUB_ITEM_NUM PUB_ITEM number --- R 6 PUB_ITEM Indicates the PUB_ITEM information. The following shows the components 1. ObjectID 2. AttributeID 3.
Object ID 4. TRANSDUCER block (continued) 5. AI1 block 10-5 <10. Parameter Summary> Attribute ID Label Default value Description Handling 10 Special Cmd Special function parameter. 0 = initialize value at READ (None) 1 = Squawk status 2 = deep sleep status To start from deep sleep mode, either remove and insert the battery pack, or use the provisioning device tool or the device configuration tool via infrared communication.
Object ID 5. AI1 block (continued) 10-6 <10. Parameter Summary> Attribute ID Label Default value Description Handling 29 Transducer Value When Simulate Switch is set to Disable, this value is used as the input value for the AI object. Refer to Figure 10.1. Disable R 30 Simulate Value When Simulate Switch is set to Enable, this value is used as the input value for the AI object. The input value can be changed. --- W 51 Upper Limit Indicates the upper limit (URL) for the pressure.
Object ID 5. AI1 block (continued) 6. AI2 block 10-7 <10. Parameter Summary> Attribute ID Label Default value Description Handling 106 H/L Swap Allows performing reverse connection of the impulse line. (NORMAL, REVERSE : reverse connection) Used when the lower pressure side and higher pressure side of the impulse line were connected wrongly when installing the pressure transmitter.
Object ID 6. AI2 block (continued) 10-8 <10. Parameter Summary> Attribute ID Label Default value Description Handling 51 Upper Limit Indicates the upper limit (URL) for the pressure. --- R 52 Lower Limit Indicates the lower limit (LRL) for the pressure. --- R 53 PV Range Sets the measurement range. 1. EU at 100% : Indicates input value of the upper limit. 2. EU at 0% : Indicates input value of the lower limit. 3. Units Index : Indicates the units of the measurement range. 4.
Object ID 7. AI3 block 10-9 <10. Parameter Summary> Attribute ID Label Default value Description Handling 1 Process Value Al3 is a temperature pressure output object. Indicates the primary analog value (or corresponding process value) and status used to execute this function. Allows updating data by specifying this for the Concentrator object. 1. Value: output value of Al object 2. Status: Specify output status of Al object. 1. Value = --2.
Table 10.2 Bit 10-10 <10.
<11. General Specifications> 11. General Specifications 11.1 Standard Specifications Power Supply Specifications Battery: Use the dedicated battery pack. Rated voltage: 7.2 V Rated capacity: 19 Ah Communication protocol: ISA100.11a protocol Data rate: Output: Wireless (ISA100.11a protocol) 2.4GHz signal 250 kbps Frequency: Zero Adjustment Limits: Zero can be fully elevated or suppressed, within the lower and upper range limits of the capsule. 2400 - 2483.
Working Pressure Limits (Silicone oil): Maximum Pressure Limits Pressure Capsule EJX510B EJX530B A 200 kPa abs (29 psia) 200 kPa (29 psig) B 2 MPa abs (290 psia) 2 MPa (290 psig) C 10 MPa abs (1450 psia) 10 MPa (1450 psig) D 50 MPa abs (7200 psia) 50 MPa (7200 psig) 100(750) 10(75) 2.7(20) Applicable range Connections: Refer to “Model And Suffix Codes.” 0.13(1) 0.1(0.75) Wetted Parts Materials: Diaphragm, Process Connector Refer to “Model And Suffix Codes.” 0.013(0.1) 0.01(0.
<11. General Specifications> 11-3 11.2 Model and Suffix Codes Model Suffix Codes EJX510B ...................... EJX530B ...................... Output -L . . . . . . . . . . . . . . . . . . . . . signal Measurement A . . . . . . . . . . . . . . . . . . . span (capsule) B . . . . . . . . . . . . . . . . . . . C . . . . . . . . . . . . . . . . . . . D . . . . . . . . . . . . . . . . . . . Wetted parts material *3 S . . . . . . . . . . . . . . . . . H . . . . . . . . . . . . . . . . . Process 4 . . .
11-4 <11. General Specifications> 11.
11-5 <11. General Specifications> 11.4 Dimensions Process connections code 7 (Amplifier housing code 7) Unit: mm (approx. inch) 191 (7.52) 94*2 (3.70) 24 (0.94) 39 6 (0.24) 76 (2.99) 72 (2.83) Ø110 (4.33) Ground terminal 40 (1.57) For electrical connection code 5, 9, A, and D 202 (7.95) B 64 (1.54) (2.52) Zero adjustment 162 (6.38) A 282*5 (11.10) Integral indicator Open to atmosphere*1 Mounting bracket (Optional) 12*3 (0.47) 82*4 (3.23) 140 (5.51) 2-inch pipe (O. D.
i Revision Information Title : EJX510B and EJX530B Absolute and Gauge Pressure Transmitters Manual No. : IM 01C27F01-01EN Edition 2nd 3rd Date Aug. 2010 Apr. 2011 Page — — 4th 5th 6th Dec. 2011 Aug. 2012 Oct. 2012 7th 8th June 2013 Jan. 2014 9-7 — — 2-5 to 2-7 11-2 — — Revised Item Release of ISA100.11a protocol • Adapted to device configuration tool with infrared communication function.