User’s Manual EJX910A and EJX930A Multivariable Transmitter HART Communication Type IM 01C25R02-01E IM 01C25R02-01E 6th Edition
i EJX910A and EJX930A Multivariable Transmitter HART Communication Type IM 01C25R02-01E 6th Edition Contents 1. 2. 3. Introduction................................................................................................ 1-1 Regarding This Manual..................................................................................... 1-1 1.1 Safe Use of This Product ................................................................................. 1-2 1.2 Warranty...............................
ii 3.3.7 Trim Analog Output........................................................................... 3-22 3.3.8 External Switch Mode....................................................................... 3-22 3.3.9 CPU Failure Burnout Direction and Hardware Write Protect........... 3-23 3.3.10 Software Write Protection................................................................. 3-23 3.3.11 Alarm.................................................................................................
iii Appendix 1. Safety Instrumented Systems Installation.............................A1-1 A1.1 Scope and Purpose........................................................................................ A1-1 A1.2 Using the EJX for an SIS Application........................................................... A1-1 A1.3 Appendix 2. A1.2.1 Safety Accuracy................................................................................A1-1 A1.2.2 Diagnostic Response Time..................................
1. 1-1 <1. Introduction> Introduction Thank you for purchasing the DPharp EJX multivariable transmitter. EJX multivariable transmitters are precisely calibrated at the factory before shipment. To ensure both safety and efficiency, please read this manual carefully before operating the instrument.
1.1 Safe Use of This Product For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated.
1.3 <1. Introduction> 1-3 ATEX Documentation This is only applicable to the countries in European Union.
2. 2.1 2-1 <2. Connection> Connection Integral Indicator Display When Powering On NOTE For models with the integral indicator code “D”, the display shows all segments in the LCD and then changes to the displays shown below sequentially. All segments display Model name (3 sec.) LCD display can be set to all segments display only. • Procedure to call up the display [Root Menu] (Refer to subsection DD (HART 5/7) 3.1.
(1) Confirmation by the name plate The HART protocol revision is shown by the last number of the serial number. Refer to Figure 2.1. STYLE MODEL SUFFIX SUPPLY OUTPUT MWP mA DC V DC CAL RNG NOTE HART 7 communication is supported by FieldMate R2.02 or later. NOTE NO. Made in Japan TOKYO 180-8750 JAPAN : Refer to USER'S MANUAL. XXX - - - XX 5 : HART 5 7 : HART 7 F0201.ai Figure 2.1 2-2 <2.
(1) Confirming the device revision of the transmitter ● Confirmation by using integral indicator (When the integral indicator code is “D”) Refer to the section 2.1 ● Confirmation by using HART configuration tool Follow the procedure below. 1) Connect the configuration tool to the transmitter. 2) Select the “Root Menu” (Refer to subsection 3.1.1) Call up the “Review” display. 3) The device revision is displayed on the “Fld dev rev” column.
2.6 <2. Connection> 2-4 Power Supply Voltage and Load Resistance When configuring the loop, make sure that the external load resistance is within the range in the figure below. (Note) With an intrinsically safe transmitter, external load resistance includes safety barrier resistance. 600 External load resistance R (Ω) R= E–10.5 0.0244 Communication applicable range 250 0 10.5 16.6 25.2 Power supply voltage E (V DC) Figure 2.3 42 F0203.
3. 3.1 <3. Parameter Setting> 3-1 Parameter Setting Menu Tree The menu tree is different in DD(HART 5/HART 7)/DTM(HART 7) and DTM(HART 5). See the menu tree corresponding to the configuration tool. 3.1.
A • Process variables 3-2 <3.
<3.
• Diag Mode • Diag Applicable • Diag Variables • Diag Description • Ref fDP Status • Ref fDP • Ref fSPl Status • Ref fSPl • Ref fSPh Status • Ref fSPh • Ref BlkF Status • Ref BlkF • Ref DP Avg Status • Ref DP Avg • Fluct Variables • fDP Status • fDP • fSPl Status • fSPl • fSPh Status • fSPh B1 • Diag Error • Diag Option • ILBD Parameters • Configuration • Diag Output • Set Diag Mode • Diag Period • Diag Lim • Lim fDPmax • Lim fDPmin • Lim fSPlmax • Lim fSPlmin • Lim fSPhmax • Lim fSPhmin • Lim B
<3. Parameter Setting> C • Basic setup HART 7 3-5 : HART 7 only • Tag • Long tag HART 7 • Units • Pres Unit • SP Unit • ET Unit • Flow Unit • Total Flow Unit • Keypad input • PV is • Change PV Assgn • PV Unit • PV LRV • PV URV • PV Damp • Device infomation • Date • Descriptor • Message • Write Protect • Model • Others • Low cut • Low cut mode • H/L Swap F0301-05.
D • Detailed setup 3-6 <3.
<3.
HART 5 E • Detailed setup • Review 3-8 <3.
<3. Parameter Setting> 3-9 3.1.
<3.
3-11 <3. Parameter Setting> T • Configuration • Pressure Sensor • Static Pressure Sensor • External Temperature Sensor • ET USL • ET LSL • ET Min Span • ET Unit • ET URV • ET LRV • ET Damp • ET Fixed • Fixed ET Val • SP USL • SP LSL • SP Min span • SP Unit • SP URV • SP LRV • SP Damp • SP H/L Select • A/G Select • Atm. Pres Value • Auto Atm.
<3.
3.2 Basic Setup *1: The characters bounded by the thick line in the following table can be used. *2: All characters in the following table can be used. IMPORTANT After setting and sending data with the HART configuration tool, wait 30 seconds before turning off the transmitter. If it is turned off too soon, the settings will not be stored in the transmitter. 3.2.1 Tag and Device Information If there are specified when ordering, the desired Tag No. and device information are set and shipped.
<3.
NOTE The calibration range can be set as PV LRV > PV URV under the following conditions, reversing the 4 to 20 mA output signal. PV LSL -10% of USL ≤ PV LRV ≤ PV USL +10% of USL PV LSL -10% of USL ≤ PV URV ≤ PV USL +10% of USL |PV URV - PV LRV| ≥ PV Min. Span If PV is flow, PV LRV and PV URV must be the following conditions. 0 ≤ PV LRV 0 ≤ PV URV PV LRV < PV URV The flow range is set to LRV=0 and URV=100 when the Flow calc mode is changed to Basic mode or Full Auto mode.
<3. Parameter Setting> 3-16 3.2.6 Differential Pressure Signal Low Cut Mode Setup 3.2.7 Impulse Line Connection Orientation Setup Low cut mode can be used to stabilize the differential pressure output signal near the zero point. The Low cut is applied to the differential pressure used to flow calculation. The low cut point can be set from 0 to 20% of output. (Hysteresis for the cut point: ±10% of the cut point ) This function reverses the impulse line orientation.
3.3 3-17 <3. Parameter Setting> Detailed Setup • Procedure to call up the display 3.3.1 Analog Output Signal Adjustable Range Output signal adjustable range at normal operating condition are set as shown below at the factory when the instrument is shipped, and output signal are limited by these value. Standard Option code /C1 Option code /C2 and /C3 Lower limit Upper limit 3.8 mA 21.6 mA 3.8 mA 20.5 mA Output signal range can be changed between 3.8mA and 21.
<3. Parameter Setting> Available displays Description and related parameters % of PV range (PV %) F Flow rate (Flow) F Indicates input value depending on the set PV range (PV LRV and PV URV). PV % Indicates values of calculated flow with the indication limits –99999 to 99999. Flow Input differential pressure (Pres) P SP 26.0 kg/h Indicates values of input differential pressure with the indication limits –99999 to 99999. PRES Input static pressure (SP) 92.4 % 45.
• Procedure to call up the display DD (HART 5/7) DTM (HART 7) → Set Engr Unit → Engr LRV → Engr URV → Engr exp → Engr point [Root Menu] → Detailed setup → Display condition → Engr disp range Select the engineering unit Lower range value Upper range value Exponents for user scale display Decimal point position for user scale display Select the engineering unit from the list.
<3. Parameter Setting> 3.3.6 Sensor Trim Typical Unit Conversion Factor Use “kg” in case of mass flow Use “m3” in case of volume flow Use “Nm3” in case of normal or standard volume flow Set Base Unit kg m3 Nm3 User Unit g kg t lb STon LTon oz gal L Impgal m3 bbl bushel yd3 ft3 in3 bbl hl Nm3 NL SCF Convert val 1.0000E+03 1.0000E+00 1.0000E-03 2.2046E+00 1.1023E-03 9.8421E-04 3.5274E+01 2.6417E+02 1.0000E+03 2.1997E+02 1.0000E+00 6.2898E+00 2.8378E+01 1.3080E+00 3.5315E+01 6.1024E+04 6.2898E+00 1.
(1) Auto Sensor Trim Applying reference pressure of 0% and 100% of the measurement range to the transmitter, adjust the lower and upper points automatically.
• Procedure to call up the display for differential pressure DD (HART 5/7) DTM (HART 7) DTM (HART 5) [Root Menu] → Diag/Service → Calibration → Pres Sensor trim → Clear P trim → Execute Calibration → Clear Pressure Sensor trim → Execute Adjustment using a volt meter. (4mA → 1V, 20mA → 5V) 1) Select “Change”. 2) Enter the value read on the voltmeter when the output signal is 4mA.
3-23 <3. Parameter Setting> 3.3.9 CPU Failure Burnout Direction and Hardware Write Protect There are two slide switches on the CPU assembly board. One sets the burnout direction at CPU failure, and the other sets a write protection function which disables parameter changes through the use of a handheld terminal or some other communication method.
<3. Parameter Setting> 3-24 (1) Alarm Setting • Procedure to call up the display Select the process variable at Process Alert which the alarm is set, then set the alert mode for that value. DD (HART 5/7) [Root Menu] → Detailed setup → DTM (HART 7) Output condition → Process Alerts → DO config → DO Signal type DTM (HART 5) Configuration → Process Alerts → DO Signal type Status Output On When Al. Output is “ON” when Detect alert is detected Off When Al.
• Procedure to call up the display [Root Menu] → Detailed setup → Output condition → Process Alerts → DO config → DO Select DTM (HART 5) Configuration → Process Alerts → DO Select Display Item Contents (Select a output variable from the list below) Off – Pres Differential pressure SP Static pressure Temp External temperature Pres/SP Differential pressure and static pressure Pres/Temp Differential pressure and external temperature SP/Temp Static pressure and external temperature Pres/SP/Temp Differential
<3. Parameter Setting> 3.3.13 Test Output, Simulation, and Squawk Example of Pulse Output The number of pulses (PPS) NOTE T = 1sec (*1) Example of scaled pulse Pulse Rate =10kg (*2) Example of freqency output Configuration: Freq at 100% =10000Hz Flow Rate: URL =100% 10000(PPS) F0307.
<3. Parameter Setting> • Procedure to call up the display • Procedure to call up the display DTM (HART 5) DD (HART 5/7) DTM (HART 7) DTM (HART 5) → Simulation Mode Display Item Manual Test Auto Test Diag and Service → Service → Loop test → Contents Set the current value or % value at Test output value, then click the Start button. Set the interval and rate of change of current output at Auto Test Setting, then click the Start button.
• Procedure of device variable simulation NOTE The output process value while simulation can be monitored by LCD and through communication as follows. Process value DP SP ET Flow Rate Total Flow Output value Simulation value according to simulation mode Simulation value according to simulation mode Simulation value according to simulation mode Flow calculation value using the DP, SP, ET simulation value Flow Rate accumulation value Following function is reflected to flow calculation while simulation.
(5) Squawk (Effective only when setting to HART 7) This feature can be used to identify the communicating transmitter by remotely causing LCD to display the particular pattern as shown in the Figure 3.3. “SQUAWK” continues for approximately 15 seconds, then is released automatically. Enter the larger number to “Change number of squawks to make” in order to prolong the duration of squawk indication. • Procedure to call up the Squawk display [Root Menu] → Diag/Service → Test → Squawk P SP T 3.3.
3-30 <3. Parameter Setting> Table 3.2 Basic Flow Calc Set-up Steps Step Parameter Contents 1 Flow Calc Mode Select Basic Mode 2 Fluid Type Select liquid or gas 3 Flow Calc Fixed Input Kfactor 4 Ref SP 5 6 Ref Temp Temp K1 Remarks Kfactor calculated by Table 3.3 Flow Equation and Kfactor Calculation This factor is used for gas. When fluid type is liquid, set 0 to Ref SP(Spb).
Flow unit category Table 3.5 Table 3.7 Mass Flow Unit Unit grams per second grams per minute grams per hour Kilograms per second kilograms per minute kilograms per hour kilograms per day metric tons per minute metric tons per hour metric tons per day pounds per second pounds per minute pounds per hour pounds per day short tons per minute short tons per hour short tons per day long tons per hour long tons per day Table 3.6 3-31 <3.
3.3.15 Burst Mode 3.3.15.1 In the case of using HART 5 When the Burst mode is enabled, the transmitter continuously sends the stored data. The data is sent approximately three times per second as a digital signal when the transmitter is set in burst mode. When data is being sent in burst mode, other operations can be performed with the HART configuration tool. (1) Selection of the transmission data. Call up the Burst option parameter and select the data which is transferred.
Table 3.8 <3.
3-34 <3. Parameter Setting> (2) Burst mode setting procedure • Procedure to call up the display DD (HART 7) DTM (HART 7) [Root Menu] → Detailed setup → Output condition →HART output → Burst Condition → Burst Message 1,2 or 3 → Burst Command a. Burst Command Burst Command Send to EJX Cmd9, Cmd33 Burst Command? Cmd1, Cmd2, Cmd3, Cmd48 Burst Variable Code b. Burst Variable Code Send to EJX Update Period Max Update Period c. Update period and Max Update Period by “Set Burst Period” Send to EJX d.
a. <3. Parameter Setting> Burst Command Select the transmission data at Burst Command parameter.
e. <3. Parameter Setting> Burst Mode When the Burst mode is set to “Wired HART Enabled”, the transmitter starts to send the data. • Procedure to call up the display DD (HART 7) DTM (HART 7) [Root Menu] → Detailed setup → Output condition →HART output → Burst condition → Burst Message 1,2 or 3 → Burst mode → Wired HART Enabled 3.3.15.2.2 Event Notification When a setting change and a change of the Selfdiagnostics occur, device detect it as an event and can transmit an alarm signal continuously.
b) Acknowledge Event Notification Execute Acknowledge Event Notification method. 1) Set to Enter Event Number is in confirmed Event Number a)5. 2) OK. 3) Set “Trans 1: Send Acknowledge” to Select Transaction. 4) OK. 5) Confirm Event Status is 0x00.
3.3.16.2 In the case of using HART 7 “Multidropping” transmitters refer to the connection of several transmitters to a single communication transmission line. Up to 63 transmitters can be connected when set in the multidrop mode. To activate multidrop communication, the transmitter address must be changed to a number from 1 to 63. This change deactivates the 4 to 20 mA analog output, sending it to 4 mA. The alarm current is also disabled.
<3. Parameter Setting> 3-39 4) Applying the new protocol revision a. Close the configuration tool After completion of Chg universal rev method, close the HART configuration tool. NOTE When using a FieldMate, close the main display of FieldMate. b. Restart the transmitter Turn off the power to the transmitter, and turn it on. IMPORTANT New protocol revision is applied only after having performed restart of the transmitter.
4. 4.1 <4. Diagnostics> 4-1 Diagnostics Self-Diagnostics (2) Using DTM(HART 5) 4.1.1 Identify Problems by Using the HART Configuration Tool The HART configuration tool can be used to run self-diagnostics on a transmitter and check for incorrect data settings. (1) Using DD(HART 5/HART 7) and DTM(HART 7) The Device Status commands are used for selfdiagnostics.
4.1.2 Checking with Integral Indicator NOTE If an error is detected by running self-diagnostics, an error number is displayed on the integral indicator. If there is more than one error, the error number changes at three-second intervals. See table 4.3.1 regarding the alarm codes. F0401.ai Figure 4.1 4-2 <4. Diagnostics> Integral Indicator 4.1.3 Status information available for HART 7 Status added to HART 7 is explained below.
4.2 NOTE Time Stamp is reset when powering on. (5) Configuration Change Counter The Configuration Change Counter is incremented once for every user action that changes the device’s configuration or calibration. This value is never reset or written and maintained even if power is removed from the device. • Procedure to call up the display using DD (HART 7) and DTM (HART 7) DD (HART 7) DTM (HART 7) → Cfg chng count 4-3 <4.
<4. Diagnostics> 4-4 IMPORTANT • The pressure fluctuation amplitude in fluids must be sufficiently large for blockages to be detected. • If the pressure fluctuation amplitude is too low for a reference value to be obtained, blockages detection operation cannot be performed with an alarm that the reference value is invalid. • The pressure fluctuation amplitude may decrease due to other causes unrelated with a blockage according to process condition.
4-5 <4. Diagnostics> Functional block diagram The figure below shows the functional block diagram of ILBD.
4.2.2.1 Blockage Detection Limit parameter When the parameter based on pressure fluctuation exceeds the preset value, EJX diagnoses an impulse line as blockage and gives an alarm. The threshold values are set to Limit parameter shown in below table.
H/L Blocking Detection EJX differential pressure transmitter enables to detect both-, a high-, or low-pressure-side blockage. The blockage degree characterized by a comparison of high-pressure side and lowpressure-side fluctuation values, BlkF, is used to detect it. The value changes within a range of –1 to +1. As BlkF approaches +1, the high-pressureside blockage progresses. On the other hand, if it approaches –1, the low-pressure-side blockage progresses.
4-8 <4. Diagnostics> 4.2.2.2 Combination of Reference Result and Blockage Detection Diag Applicable An EJX multivariable transmitter can detect four modes of impulse line blockage: both-sides, highpressure side, low-pressure side, and/or single-side and abnormal fluctuation when all the reference values are properly measured. However, the detectable alarm mode combination is limited when some of the reference values are invalid. Available Blockage Detection are shown in the below figure.
4.2.2.3 Operation Parameters Diag Mode Diag Mode gives the directive for the ILBD operation. There are following three modes. • Procedure to call up the display DD (HART 5/7) [Root Menu] → Diag/Service → Diag DTM (HART 7) Parameters → ILBD Parameters → Configuration → Set Diag Mode → DTM (HART 5) Diag and Service → Advanced Diag Configurations → Impulse Line Blockage Detection → Diag Mode → Diag Mode Mode Stop Function The blockage detection operation is stopped.
<4. Diagnostics> 4-10 Diag Supp Count (Number of times: 3) An alarm is generated. A B B B Upper Threshold (Ex.Lim fDPmax) Diag Period Time Diag Period A Lower Threshold (Ex.Lim fDPmin) A A B An alarm is generated. Diag Supp Count (Number of times: 3) Time F0406.ai Figure 4.4 Relationship of Diag Supp Count and Alarm The number of detection to give an alarm is set for each blockage detection function. The default value at the shipment is set to three times.
4-11 <4. Diagnostics> 4.2.2.4 Operating Procedure If an alarm is often generated or the process condition changed in the ILBD operation, do tuning to change the alarm setting, or to reset the reference values. The basic flow of the ILBD operation is as follows. 1) Initial setting 2) Condition check 3) Start up 4) Perform the ILBD algorithm. Fill out the information to the checklist, at the process shown in below figure. (Refer to the Appendix 1.
<4. Diagnostics> 4.2.2.5 Alarm and Alert Setting The abnormal results as the blockage detection and high/low flange temperature (heat trace monitoring) are given through an analog alert or the LCD display of alarm status. Before performing the ILBD operation, it is necessary to set the alarm and alert according to the following procedure.
When the level range that can be measured by the transmitter with 100 kPa span is –80 to 80 kPa, the limits are set as follows. • Lim DPAvgmax: 0.80 • Lim DPAvgmax: –0.80 1.000 ILBD over range 0.
• Procedure to call up the display DD (HART 5/7) [Root Menu] → Diag/Service → Diag DTM (HART 7) Parameters → Diag Output → Diag Fixed Out Val → DTM (HART 5) Diag and Service → Advanced Diag Configurations → Diag Output → Diag Out Option → Status Output for Advanced diagnostic The output of the abnormal results are applicable for a transistor output (open collector) of an on/off signal according to the status of high and low alarm limits, which are values set to Limit parameters as shown in subsection
fDP is not enough. No blockage can be detected if fDP is not larger than the specified value. Only fDP is enough. “A Blocking” or “B Blocking” can be detected if fSPl and fSPh are not larger than specified values. fDP and fSPl are enough. “H Side Blocking” and “Large Fluct H” can not be detected if fSPh is not larger than specified value. fDP and fSPh are enough. “L Side Blocking” and “Large Fluct L” can not be detected if fSPl is not larger than specified value.
Invalid Ref F, SPH, SPL, or DP When the enough reference fluctuation value is not obtained, an alarm of invalid reference value for each parameter is generated and also the ILBD operation is not carried out. Confirm the alarm of Invalid Ref F, SPH, SPL, or DP is not displayed in Diag Error. If an alarm of Invalid Ref F, SPH, SPL, or DP is generated, consider the process condition or obtain the reference fluctuation values again.
4.2.2.10 Tuning (1) For DD (HART 5/HART 7) and DTM (HART 7) When the pressure fluctuation amplitude in fluids is not sufficiently large or an alarm is often generated according to the process condition, tune up by changing the threshold for the blockage detection (Limit parameters) or the sampling period (Diag Period) to enhance the accuracy of the blockage detection The ILBD operation must be stopped to tune up. Set “Stop” to Diag Mode.
Combination of threshold for sensitivity parameter High Medium Low Lim fDPmax 1.50 3.00 3.00 Lim fDPmin 0.40 0.30 0.20 Lim fSPlmax 5.00 5.00 5.00 Lim fSPlmin 0.50 0.50 0.30 Lim fSPhmax 5.00 5.00 5.00 Lim fSPhmin 0.50 0.50 0.30 Lim BlkFmax 0.60 0.60 0.80 Lim BlkFmin -0.60 -0.60 -0.80 Sampling Period If fluctuating around the threshold value, an alarm maybe often generated.
<4. Diagnostics> 4-19 4.2.2.12 ILBD Parameter List # Parameter name Default value Explanation 1 Diag Error 0x0000 The results detected by ILBD or Heat trace monitoring are stored into this parameter. Also the condition abnormality in the diagnostic process is stored as an error. 2 Diag Option 0x08FC The masking in this parameter enable to display each error message and the status to the output signal or LCD. The error assigned to each bit is corresponding to that of Diag Error.
# 28 29 30 31 32 33 34 35 Parameter name Default value Ref fSPl Ref fSPl Status Ref fSPh Ref fSPh Status Ref BlkF Ref BlkF Status Ref DPAvg Ref DPAvg Status 36 Lim fDPmax Refer to Table 4.3 37 Lim fDPmin 38 Lim fSPlmax 39 Lim fSPlmin 40 Lim fSPhmax 41 Lim fSPhmin 42 Lim BlkFmax 43 Lim BlkFmin 44 Lim DPAvgmax 45 Lim DPAvgmin 46 Ref Lim fDPmin 7.0E-10 47 Ref Lim fSPmin 1.0E-10 48 Ref Lim BlkFmax 0.
4-21 <4. Diagnostics> 4.2.3 Heat Trace Monitoring 4.2.3.1 Flg Temp Coef Setting The EJX multivariable transmitter with Heat trace monitoring function calculates the flange temperature by using the two temperature sensors built in the EJX multivariable transmitter. The value calculated according to the following procedure is set to Flg temp Coef. An analog alert is generated if the temperature reached to the preset level.
4-22 <4.
Alarms and Countermeasures Integral indicator AL. 01 CAP.ERR Alarm Message Summary HART configuration tool display Cause P sensor error *1 Pressure Sensor Error *2 Sensor problem.
HART configuration tool display AL. 30 PRS.RNG P over range *1 Pressure Over Range *2 AL. 31 SP. RNG SP over range *1 Static Pressure Over Range *2 AL. 32 F. RNG F over range *1 Flow Over Range *2 AL. 33 ET. RNG ET over range *1 External Temp Over Range *2 P high alarm *1 Pressure High Alarm *2 AL. 36 P.LO P low alarm *1 Pressure Low Alarm *2 AL. 37 SP high alarm *1 SP.HI Static Pressure High Alarm *2 AL. 38 SP low alarm *1 Static Pressure Low SP.LO Alarm *2 AL. 41 F.
Cause 4-20mA Output operation during error SP SPAN trim err *1 Static Pressure SPAN Trim Error *2 SP ZERO trim err *1 Static Pressure ZERO Trim Error *2 Illegal ET LRV *1 Illegal External Temp LRV *2 Illegal ET URV *1 Illegal External Temp URV *2 Illegal ET SPAN *1 Illegal External Temp SPAN *2 ET SPAN trim err *1 External Temp SPAN Trim Error *2 ET ZERO trim err *1 External Temp ZERO Trim Error *2 F set outside Range *1 Flow set Outside Range *2 Specified value is outside Continues to operate and of
Cause 4-20mA Output operation during error AL.89 B BLK B Blocking *1, *2 B Blocking (both-side blockage) is detected. AL.89 H BLK H Side Blocking *1 High Side Blocking *2 High-pressure-side blockage is detected. AL.89 L BLK L Side Blocking *1 Low Side Blocking *2 Low-pressure-side blockage is detected. AL.89 H LRG Large Fluct H *1 Large Fluctuation of High Side *2 Large Fluct L *1 Large Fluctuation of Low Side *2 A Blocking *1, *2 Pressure fluctuation amplitude of highpressure side is large.
Table 4.6 4-27 <4. Diagnostics> HART Configuration Tool Error Messages Error message Invalid selection Passed Parameter Too Large Passed Parameter Too Small Too Few Data Bytes Received In Write Protect Mode Lower Range Value too High Lower Range Value too Low Upper Range Value too High Upper Range Value too Low Span too Small Applied Process too High Applied Process too Low New Lower Range Value Pushed Upper Range Value Over Sensor Limit Excess Correction Attempted Small Char.
Table 4.10 Relationship between Alarm and Status available for HART 7 HART Integral configuration Indicator tool display Device Status Extended Device Status Value and Status (Data Quality and Limit Status) Flow Differential Pressure (DP) Static Pressure (SP) External Temperature Total Flow (ET) AL.01 P sensor Device Maintenance Value: Hold value CAP.
HART Integral configuration Indicator tool display AL.30 P over PRS.RNG range Device Status Value and Status (Data Quality and Limit Status) Extended Device Status Flow Differential Pressure (DP) Static Pressure (SP) External Temperature Total Flow (ET) In the case Device Value: Measured value of PV: Variable Alert Status: Good and Not Limited Loop (0x02) Current Saturated (0x04) AL.31 SP. RNG SP over range AL.32 F. RNG F over range AL.33 ET. RNG ET over range AL.35 P. HI AL.36 P. LO AL.
HART Integral configuration Indicator tool display AL.55 SP. ADJ SP SPAN trim err Device Status --- SP ZERO trim err AL.56 ET.
4-31 <4. Diagnostics> HART Integral configuration Indicator tool display AL.87 FLG. HI FT high alarm AL.87 FLG. LO FT low alarm AL.88 INVR.DP AL.88 INVR.SL AL.88 INVR.SH AL.88 INVR.F AL.89 ILBD.OV AL.89 B BLK Invalid Ref DP Invalid Ref SPL Invalid Ref SPH Invalid Ref F ILBD over range B Blocking AL.89 H BLK H Side Blocking AL.89 L BLK L Side Blocking AL.89 H LRG Large Fluct H AL.89 L LRG Large Fluct L AL.89 A BLK A Blocking AL.
HART Integral configuration Indicator tool display AL.91 F. SIM F Simulate Mode AL.91 P. SIM P Simulate Mode AL.91 SP.SIM SP Simulate Mode AL.91 ET.SIM ET Simulate Mode AL.91 TF.SIM TF Simulate Mode AL.91 PCT. SIM AL.91 AO.SIM 4-32 <4.
5. Function Analog output Analog output trim Burst mode <5. Parameter Summary> 5-1 Parameter Summary Label AO alm typ AO lower limit AO upper limit Auto recover Clear D/A trim D/A trim Scaled D/A trim Channel flags Burst mode Item Analog output alarm type Lower limit of analog output Upper limit of analog output Auto-recover from hardware error Reset analog output trim Analog output trim with ammeter Analog output trim with voltmeter Analog channel flags Burst mode *2 Contents High or Low 3.
Function Device information <5. Parameter Summary> Label Country Item Country code Contents US, JP, DE, FR, ES, RU, CN 5-2 Default value Handling *1 JP W HART 7 Dev id Distributor Drain vent matl Extra No. Ext SW Fill fluid Final asmbly num Fld dev rev Gasket matl Isoltr matl Mftr Date Model 1/MS Code 1 Model 2/MS Code 2 Model 3/MS Code 3 Num of RS Process Conn matl Process Conn size Process Conn type PT100 Serial No. RS fill fluid RS Isoltr matl RS type Serial No. Sofftware rev Style No.
Function Diag Lim <5.
Function Display setup <5.
Function Event Notification <5.
Function Event Notification <5.
Function Master test Message Model Number of requested preambles <5.
Function Process variables <5.
Function Process variables <5. Parameter Summary> Label QV is Item Contents Current QV 5-9 Default value Handling *1 R HART 7 QV Data Quality*3 HART 7 QV Limit Status Device variable process data quality Device variable process data quality of QV R Device variable limit status Device variable limit status of QV R % of range value (PV value in %) -2.50 to 110.
Function Self test Sensor trim Label Self test Clear ET trim Clear P snsr trim Simulation/ Flow Simulation Clear SP snsr trim ET trim Pres trim SP trim Trim Date Trim Desc Trim Loc Trim Who (Flow) Simulation Mode (Flow) Sim Pres Basic Flow Calc (Flow) Sim Pres Unit (Flow) Sim SP (Flow) Sim SP Unit (Flow) Sim Temp (Flow) Sim Temp Unit Flow Calc Fixed Flow Calc mode Fluid Type Ref SP Ref Temp Temp K1 SP setup 5-10 <5. Parameter Summary> A/G Select Atm.
Function Status <5.
A1-1 Appendix 1. Safety Instrumented Systems Installation WARNING The contents of this appendix are cited from exida.com safety manual on the EJX series pressure transmitters specifically observed for the safety transmitter purpose. When using the EJX for Safety Instrumented Systems (SIS) application, the instructions and procedures in this section must be strictly followed in order to preserve the transmitter for that safety level. A1.
Table A1.2 A1-2 Proof Testing Testing method Functional test: 1. Follow all Management of Change procedures to bypass logic solvers if necessary. Tools required • Handheld terminal Expected outcome Remarks Proof Test Coverage The output needs to be =52% monitored to assure that the transmitter communicates the correct signal. • Handheld terminal • Calibrated pressure source Proof Test Coverage =99% 2.
A1-3 A1.3 Definitions and Abbreviations A1.3.
A2-1 Appendix 2. ILBD Check List Fill out the below checklist according to the operation flow of the ILBD in order to keep the important information for the blockage detection. Checklist (1/5) No. 1 Items 4-20 mA Analog Signal Setting • Select the output mode when an alarm is generaed.
A2-2 Checklist (2/5) No. 8 Items Alarm status • Check the alarm status shown in Diag Error. • Check that the alarm status of “ILBD over range” is not shown in Diag Error. 9 ILBD parameters • Record the values of parameters for ILBD operation. • Check the status of parameters for ILBD operation. *: Record the value after checked that the status of each parameter is “GOOD”.
A2-3 Checklist (3/5) Go to the following step according to the result of "Invalid Ref xx" shown in the Diag Error of 8th check item. Invalid Ref SPH Diag Error Invalid Ref SPL Invalid Ref DP → → Check item 10-a 10-b : The alarm is generated. : The alarm is not generated. No.
A2-4 Checklist (4/5) No. Items 10-a-2 L Side Blocking • Close the low-pressure side valve completely. • Record the values of fDP, fSPl, fSPh, BlkF, and DPAvg after the certain time, (Diag Period X Diag Supp Count), passed. *: Record the value after checked that the status is “GOOD”. • Record the status of Checkbox in Diag Option. • Check that the alarms status of “A Blocking” and “L Side Blocking” are set.
A2-5 Checklist (5/5) No. 10-b Items Simulation of Blockage detection operation • Close completely the valve for the side where the alarm of Invalid Reference Value is not generated. For the case that the high-pressure side value is closed; Parameters Result Example fDP* 7.48562E-09 fSPh* 7.14085E-09 fDP* 7.48562E-09 fSPI* 7.23277E-09 • Record the values of fDP, fSPl, fSPh, BlkF, and DPAvg after the certain time, (Diag Period X Diag Supp Count), passed.
i Revision Information Title : EJX910A and EJX930A Multivariable Transmitter HART Communication Type Manual No. : IM 01C25R02-01E Edition Date Page 1st Mar. 2005 — New publication 2nd Mar. 2009 — Add model EJX930A. 3rd Aug. 2009 3-25 and 3-26 3-30 4th Apr. 2010 July 2011 Mar. 2012 Revise the description. Add the detail of the status output hysteresis. A-1 2-3 3-6 3-13 2.4 3.1.1 3.2.1 4-2 to 4-18 4-19 5-1 5th 3.5.10 3.5.13 Revise the description for device revision 2. 1.
Blank Page