User’s Manual Daqstation DX1000/DX1000N/ DX2000 and DAQSTANDARD Functional Changes Resulting from the Updating (Applies to DX1000/DX1000N/DX2000 with hardware style 2 or later and firmware release 2 or later as well as DAQSTANDARD version 7.
Contents Overview of the Functional Changes..........................................................................................................................4 Checking the Style Number and Release Number on the Name Plate......................................................................4 Operations on the DX1000/DX1000N/DX2000..............................................................................................................
Thank you for purchasing the Daqstation DX1000/DX1000N/DX2000 (DX). This manual covers functions that has been changed in hardware style 2 and firmware release 2 or later. It also covers functions that have been changed on DAQSTANDARD version 7.21 or later. Change the contents of the following manuals with the contents of this manual.
Overview of the Functional Changes Below is an overview of the main functional changes. • Improvement to the Operability on the Historical Trend Display When changing to the all data display, the DX loads as much of the continuous data as the display memory can hold and shows the data. • Alarm Output Relay Action When the Alarm ACK Operation Is Executed You can select the mode in which the alarm output relay is turned OFF when alarm ACK is executed and remains OFF until the next alarm occurs.
Operations on the DX1000/DX1000N/DX2000 Below are the operational changes as a result of the functional changes. This section mainly uses the DX1000 display in the explanations. Improvement to the Operability on the Historical Trend Display Loading Operation of Continuous Data to the Display Memory All Data Display When all data display is enabled, as much of the past measured data that are continuous to the measured data shown on the screen at that point as the display memory can hold are loaded.
Operations on the DX1000/DX1000N/DX2000 Improvement to the Display Group Setup Operation The channel settings of a display group can be copied to another group. Setup Screen Press MENU (switch to the setting mode) and select Group set, Trip line Procedure 1. Select the copy source channel settings. 2. Press the Copy soft key. 3. Select the copy destination channel settings. 4. Press the Paste soft key. The channel settings are copied. Section 5.
Operations on the DX1000/DX1000N/DX2000 Setup Items • Bar graph > Base position Set the base position of the bar graphs to Normal, Center, Lower, or Upper. The bar graphs for the different settings are shown below.
Operations on the DX1000/DX1000N/DX2000 When the Display Direction of the Bar Graph Is Horizontal The span lower limit (or scale lower limit) becomes the left edge of the bar graph, and the span upper limit (or scale upper limit) becomes the right edge of the bar graph.
Operations on the DX1000/DX1000N/DX2000 Alarm Output Relay Action When the Alarm ACK Operation Is Executed You can select the relay output status that is enabled after the alarm ACK operation from the following two settings. • Normal: The relay output is deactivated when the alarm ACK operation is executed. If the condition for activating the alarm output relay is met in the next scan interval, the relay output is activated. This operation is valid only when the alarm output relay is set to Hold.
Operations on the DX1000/DX1000N/DX2000 Resetting the Computed Value during Computation (/M1 and /PM1 Options) You can reset the computed value not only when the computation is stopped but also when the computation is in progress. Section 9.4, “Starting/Stopping Computation, Resetting Computation, and Releasing Computation Data Dropout Display” in the user’s manual Changes to How the Data Files Are Named The table below shows the file name that is assigned when the measured data is saved to the CF card.
Operations on the DX1000/DX1000N/DX2000 Sorting the Files by the Update Date/Time The files can be sorted in order by the update date/time in the screens below. This function allows you to easily locate the files you need. • File list/delete • Load display data • Load event data • Load settings (setting mode) • Load settings (basic setting mode) Procedure The procedure is explained using the “File list/delete” screen of the CF card as an example. 1.
Operations on the DX1000/DX1000N/DX2000 Storage Method for Constantly Retaining the Most Recent Data Files in the CF Card (Media FIFO) When saving the data files automatically, you can save the data so that the most recent data files are constantly retained in the CF card. This method allow you to use the DX continuously without having to replace the CF card.
Operations on the DX1000/DX1000N/DX2000 Status Display of the CF Card • If an error occurs on the CF card, the CF card icon in the status display section changes to an error display. An error occurred while accessing the CF card. (White) Detected an error when the CF card was inserted or performed a key operation to eject the CF card when an error was occurring (Light blue) while the CF card was being accessed.
Operations on the DX1000/DX1000N/DX2000 Progress Display When Saving All Data of the Internal Memory If you carry out All Save* on the memory summary screen, a pop-up window appears showing the progress of the save operation. * Function for saving all data in the internal memory to a CF card or USB flash memory. Note • • • The pop-up window appears only when the memory summary display is showing.
Operations on the DX1000/DX1000N/DX2000 Function for Automatically Assigning MW100s to the Modbus Client (DX2000 Only) If the DX2000 is a Modbus client, MW100s, Modbus servers on the network, can be automatically assigned to the DX2000. This function can be used only on DX2000s with the external input channel function (/MC1 option). Setup Preparation Set the MW100s so that measurements can be started (IP address, system construction, range setting, and the like of the MW100s to be automatically assigned).
Operations on the DX1000/DX1000N/DX2000 Setup Items The MW100 channels are assigned to the external input channels of the DX as follows: • Channel Number The channels of the MW100 selected first are assigned consecutively from external input channel 201. The channels of the MW100 selected next are assigned to the available external input channels from the smallest number. You cannot select the external input channels to be assigned. DX external input channels DX MW100 meas.
Operations on the DX1000/DX1000N/DX2000 Note About the MW100 • MW100s that support auto setting are those with firmware version R2.22 or later. • MW100 modules that can be automatically set are the following input modules. 4-CH, High-Speed Universal Input Module 10-CH, Medium-Speed Universal Input Module 6-CH, Medium-Speed Four-Wire RTD Resistance Input Module 10-CH, High-speed Input Module • If there are no channels to be assigned or the Modbus server setting is OFF, auto setting fails with an error.
Operations on the DX1000/DX1000N/DX2000 Changing of the Default Setting of the Web Server Function The default setting of the Web server function has been changed to Use. You can use the Web server function by setting the monitor page or operator page to On. Section 1.5, “Monitoring the DX on a PC Browser” in the communication interface user’s manual A List of Added Messages The following error messages have been added. Code 129 131 132 Message IP address is not set.
Communication Commands Communication commands are described in chapter 3, “Commands” in the DX1000/ DX1000N/DX2000 Communication Interface User’s Manual (IM 04L41B01-17E).
Communication Commands Alarm Output Relay Action When the Alarm ACK Operation Is Executed WO Set alarm and DO settings Set the Output Relay Syntax WO p1,p2,p3,p4,p5 p1 DO type (RLY) p2 Relay number NONE No AND setting I01 Specify only I01 I01-Ixx Specify I01 to Ixx xx={02 to 36} p3 Energize/De-energize the relay DE_ENERGIZE ENERGIZE p4 Hold/Not hold the relay NONHOLD HOLD p5 Relay action on ACK NORMAL RESET Exa
DAQSTANDARD for DXAdvanced The functions below have been added or changed since DAQSTANDARD revision 7.21. Hardware Configurator Setup Menu Corresponding to the DX Functions of Firmware Version 2.0x • Specifying the Base Position of the Bar Graph Applies to the operations on the [Measure channel], [Math channel], or [Ext channel] tab screen. Bar Display Position Set the base position of the bar graphs to [Normal], [Center], [Lower], or [Upper].
DAQSTANDARD for DXAdvanced Dialog Box for Setting the Display Type for Each View Group Select [View group] on the [General Setting] tab screen. Double-click the view group number to display a dialog box for setting each group. View group number Enter the view group name Select the type of views to be displayed or drag and drop the view icons Select the group to be displayed Selectable view types Section 3.
DAQSTANDARD for DXAdvanced Viewer Linking the Previous and Subsequent Files Collectively You can collectively link previous and subsequent files to the working file. Up to now, the previous or subsequent file could be linked sepaparately. Carry out the following procedure with the file opened. • Operation on the Toolbar Click here All linkable files are linked and displayed. The .ldx extension is appended to the original file name.