User’s Manual Read Me First IM 01W01F01-11EN This document specifies the important information to use this product correctly and safely and the Use Consent Contract of Attached Software for Field Wireless Integrated Gateway. Before use the product, be sure to read this document first. Contents Introduction....................................................................................................2 Safety Precautions.................................................................................
2 Introduction n Regarding This User's Manual l This manual should be provided to the end user. Please recommend end users to keep this manual at hand and refer to it as needed. l Before use, read this manual thoroughly to comprehend its contents. l The purpose of the user’s manual is to describe details of functions provided in this product, not to warrant the product's suitability to the specific purposes of customers.
3 n ATEX Documentation l This is only applicable to the countries in European Union.
4 Safety Precautions n Safety, Protection, and Modification of the Product l Safety, Protection, and Modification of the Product l In order to protect the operator, product, and system controlled by the product, observe the safety precautions described in this user’s manual. If users handle contrary to these instructions, we can not guarantee the safety.
5 IMPORTANT Indicates important information required to understand operations or functions. NOTE Draws attention to information essential for understanding the operation and features. tip SEE ALSO Indicates additional information. Indicates a source to refer to Indicates a protective grounding terminal. Before using the product, ground the terminal. Indicates a functional grounding terminal. Before using the product, ground the terminal.
6 n The guarantee will not apply in the following cases: l Damage due to negligence or insufficient maintenance on the part of the customer. l Problems or damage resulting from handling, operation or storage that violates the intended use and specifications. l Problems that result from using or performing maintenance on the instrument in a location that does not comply with the installation location specified by Yokogawa.
7 Notes on Attached Software l Before opening the media package, read YFGW710 Software License Agreement. Once the package is opened, it is thought that the contract is agreed. l Yokogawa assumes no responsibilities for this software except as stated in the warranty. l This software is used with this product exclusively. This can be installed in the computer which connects with this product.
8 l Regulatory Compliance for Radio and Telecommunication Please confirm that a installation region fulfils a standards, require additional regulatory information and approvals, contact to Yokogawa Electric Corporation. • Radio and Telecommunications Terminal Equipment Directive (R&TTE) We, Yokogawa Electric Corporation hereby declare that this equipment, YFGW710 is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
9 l Industry Canada (IC) compliance This Class A digital apparatus complies with Canadian ICES-003. This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
10 Explosion Proof Specifications CAUTION This instrument has been tested and certified as being explosion proof. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
11 n FM Approval Caution for FM nonincendive. (Following contents refer to “DOC.NO. NFM023-A14 P.1 AND P.2.”) Note 1. Model YFGW710 Field Wireless Integrated Gateway with optional code /FN17 is applicable for use in hazardous (Classified) locations. • Applicable standard: FM3600, FM3611, FM3810, ANSI/NEMA 250 • Nonincendive for Class I, Division 2, Groups A, B, C and D. Class II, Division 2, Groups F and G. Class III, Division 1 hazardous (Classified) locations.
12 Note 3. Maintenance and Repair WARNING • The instrument modification or parts replacement by other than authorized Representative of Yokogawa Electric Corporation is prohibited and will void FM Approvals approval. • When opening the cover, the enclosure should be dry and clean to prevent from ingress water or dust. n CSA Certification Caution for CSA nonincendive/Type n. (Following contents refer to “Doc No. NCS013”) Note 1.
13 Note 3. Installation WARNING • The installation of the devices should be carried out by the engineers or other professional personnel of the related expertise. The installation should not be carried out by operators or other unprofessional personnel. • The installation should be in accordance with Canadian Electrical Code Part I or Local Electrical Code. • YFGW710 should be installed in upright position.
14 n ATEX Declaration (1) Technical Data Caution for ATEX Type n Note 1. Model YFGW710 Field Wireless Integrated Gateway with optional code /KN27 is applicable for use in hazardous area. • Applicable standard: EN60079-0: 2009, EN60079-0: 2012, EN60079-11: 2012, EN60079-15: 2010, EN60079-28: 2007 • Marking: II 3G Ex nA [ic] [op is] IIC T4 Gc (with 100BASE-FX) II 3G Ex nA [ic] IIC T4 Gc (without 100BASE-FX) • Ambient temperature: -40 to +60°C • IP code: IP66 • Power supply: 10.
15 • The thread type of the cable entries shall be confirmed according to the user’s manual. • Cable glands, adapters and/or blanking elements shall be of type “n”, type “e” or type “d” and shall be installed so as to maintain the specified degree of protection (IP code) of the equipment. • Keep the cap attached to the antenna connector (N type) until the installation of the antenna or antenna cables to protect the inside of the connector from exposure of light.
16 [Control drawing] Hazardous Area Hazardous Area Nonhazardous or Hazardous Area Zone 0/Zone 1/Zone 2 Zone 2 only Zone 2 only Electrical Equipment (e.g.) “d”, “i”, “Type n” equipment YFGW710 Field Wireless integrated gateway Antenna (*1) Radio wave (IEEE802.15.4) Surge Arrester (*1, *2) Control Equipment metal wiring or optical fiber wiring Power Supply *1: These apparatus are simple apparatus. *2: Surge Arrester may not be installed.
17 (4) Name Plate • Main name plate Field Wireless Integrated Gateway MODEL YFGW SUFFIX SUPPLY NO. STYLE VDC Made in Japan TOKYO 180-8750 JAPAN MODEL: Specified model code. STYLE: Style code. SUFFIX: Specified suffix code. SUPPLY: Specified supply voltage and wattage. NO.: Serial number and year of production *1. YOKOGAWA TOKYO 180-8750 JAPAN: The manufacturer name and the address *2.
18 IECEx Certification (1) Technical Data Model YFGW710 Field Wireless Integrated Gateway with optional code /SN27 is applicable for use in hazardous locations. • Applicable standard: IEC60079-0:2011, IEC60079-15:2010, IEC60079-11:2011 • Certificate: IECEx DEK 13.0047 • Type of Protection and Marking Code: Ex nA [ic] IIC T4 Gc • Ambient Temperature: –40 to 60°C • IP Code: IP66 • Power Supply: 10.0 V d.c. to 26.4 V d.c. (Rated voltage: 24.0 V d.c.
19 (3) Installation WARNING • The installation of the devices should be carried out by the engineers or other professional personnel of the related expertise. The installation should not be carried out by operators or other unprofessional personnel. • The installation should be in accordance with IEC 60079-14 and local electrical code. • YFGW710 should be installed in upright position. • The equipment shall be installed in accordance with the user’s manual.
20 Hazardous Location Hazardous Location Nonhazardous or Hazardous Location Zone 0/Zone 1/Zone 2 Zone 2 Zone 2 Electrical Equipment (e.g.) “d”, “i”, “Type n” equipment YFGW710 Field Wireless integrated gateway Antenna (*1) Radio wave (IEEE802.15.4) Surge Arrester (*1, *2) Control Equipment metal wiring or optical fiber Power Supply wiring *1: These apparatus are simple apparatus. *2: Surge Arrester may not be installed.
21 (5) Name Plate • Main name plate Field Wireless Integrated Gateway MODEL YFGW SUFFIX SUPPLY NO. STYLE VDC Made in Japan TOKYO 180-8750 JAPAN MODEL: Specified model code. STYLE: Style code. SUFFIX: Specified suffix code. SUPPLY: Specified supply voltage and wattage. NO.: Serial number and year of production*1. YOKOGAWA TOKYO 180-8750 JAPAN: The manufacturer name and the address*2.
22 n Ground Cable Connection The grounding terminals are located on the inside and outside of the terminal area. Connect the cable to grounding terminal in accordance with wiring procedure 1) or 2). 1) Internal grounding terminal 2) External grounding terminal If the power cable is a shielded cable, the shield should be grounded at the terminal marked as below.
23 How to Use Online Manual It is necessary to install Adobe Acrobat Reader to read the instruction manual (YFGW710 Field Wireless Integrated Gateway: IM 01W01F01-01EN). Install the following Adobe Reader by the administrator authority. • tip Adobe Reader 9.3 or later Adobe Reader can be downloaded from the Web site of Adobe Systems Incorporated. l Reading of Online Manual The online manual is stored in the attached DVD-ROM.
24 Copyright and Trademark Notices n All Rights Reserved The copyrights of the media and this manual are reserved. No part of the manual may be transferred, sold, distributed (including delivery via a commercial PC network or the like), or registered or recorded on video tapes or other media. n Trademark Acknowledgments • CENTUM, PRM, FieldMate, STARDOM and VigilantPlant are either trademarks or registered trademarks of Yokogawa.
25 About User’s Manual n Composition of User’s Manual This chapter explains the composition of User’s Manual. The following printed user’s manual is attached to YFGW710 hardware. • IM 01W01F01-11EN: Read me first The following online user’s manual is stored in the attached DVD-ROM for YFGW710.
26 YFGW710 Software License Agreement IMPORTANT - PLEASE READ CAREFULLY BEFORE INSTALLING OR USING: THIS AGREEMENT IS A LEGAL AGREEMENT BETWEEN YOU AND YOKOGAWA ELECTRIC CORPORATION AND/OR ITS SUBSIDIARIES (COLLECTIVELY, "YOKOGAWA") FOR YOU TO INSTALL OR USE YOKOGAWA YFGW710 SOFTWARE PRODUCT. BY INSTALLING OR OTHERWISE USING THE SOFTWARE PRODUCT, YOU AGREE TO BE BOUND BY THE TERMS AND CONDITIONS OF THIS AGREEMENT.
27 2.5 Upon expiration or termination of this Agreement, the Software Product and its copies shall be returned to Yokogawa and any copies retained in your computer or media shall be deleted irretrievably. If you dispose of media in which the Software Product or its copy is stored, the contents shall be irretrievably deleted. 2.6 The Software Product may contain software which Yokogawa is granted a right to sublicense by third party suppliers ("Third Party Software").
28 ject to the terms and conditions of the Supplier. 4.6 THE ABOVE WARRANTY IS GIVEN AND ACCEPTED AS A SOLE AND EXCLUSIVE LIABILITY AND IN LIEU OF ALL OTHER LIABILITY OR WARRANTIES OF ANY KIND WHATSOEVER ON THE PART OF YOKOGAWA OR SUPPLIER, EXPRESS OR IMPLIED, IN FACT OR IN LAW. ALL IMPLIED WARRANTIES AND ESPECIALLY WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NON-INFRINGEMENT ARE EXPRESSLY EXCLUDED AND DISCLAIMED.
29 (INCLUDING LIABILITY UNDER CLAUSE 6) SHALL EXCEED THE DEPRECIATED VALUE OF THE LICENSE FEE PAID TO YOKOGAWA FOR THE USE OF THE CONCERNED PART OF THE SOFTWARE PRODUCT.