036-21366-007-A-1205 ® DESCRIPTION TECHNICAL GUIDE AFFINITY™ SERIES York® Affinity™ Series packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. SINGLE PACKAGE GAS/ELECTRIC The gas-fired heaters have aluminized steel tubular heat exchangers and hot surface to pilot ignition. They are available in natural gas with field conversion to propane.
036-21366-007-A-1205 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 STANDARD FEATURES/BENEFITS . . . . . . . . . . . . 3 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 4 TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . . 32 MECHANICAL SPECIFICATIONS . . . . . . . . . . . . . 33 19 TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY) . . . . . . . . . . . . . . . 30 20 TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY) . . . . . . . . . .
036-21366-007-A-1205 STANDARD FEATURES/BENEFITS OPERATING EFFICIENCY - All units provide high operating efficiencies and have a minimum AFUE of 80% and SEER of 13.0. All efficiencies exceed legislated minimum levels. ON SITE FLEXIBILITY - All model sizes share a common, compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper tonnage unit on that curb after the internal load has been determined.
036-21366-007-A-1205 FAN SYSTEM - All 2-1/2, 3, 3-1/2 and 4 ton models operate over a wide range of design conditions with a constant CFM, electrically commutated (ECM) fan motor. These units easily match all types of applications and provide greater on site flexibility to match comfort requirement. These models have 2 cooling speeds and a single heating speed. The cooling speed is factory set and can be field adjusted to a second speed.
036-21366-007-A-1205 enthalpy to determine the most economical mix. Single Enthalpy sensor also required. 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly. PRESSURE SWITCH UPGRADE KIT - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing scharder ports located in the unit by furnished adapters.
036-21366-007-A-1205 DIRECT DRIVE CONDENSER FAN MOTOR BLOW-THROUGH DESIGN WITH RELIABLE ALUMINIZED STEEL TUBULAR HEAT EXC HANGERS HIGHLY EFFICIENT E NHANCE D COPPER TUBE/ALUMINUM FIN EVAPORATOR COIL HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN CONDENSER COIL LONG LASTING POWDER PAINT FINISH DECORATIVE PROTECTIVE COIL GAURD REAR AND BOTTOM RETU RN AIR AND SUPPLY AIR DUCT OPENINGS HIGH EFFICIENCY COMPRESSOR RIGIDLY MOUNTED HOT SURFACE PILOT ASSEMBLY HIGH GRADE ALUMINIZED IN-SHOT BURNERS HEAVY GA
036-21366-007-A-1205 TABLE 2: RATINGS COOLING/GAS HEATING NET COOLING CAPACITY1 MODEL DNP MBH SEER3 024N03606 024N05606 030N03606 030N03625 030N03646 030N05606 030N05625 030N05646 036N03606 036N03625 036N03646 036N03658 036N05606 036N05625 036N05646 036N05658 036N07206 036N07225 036N07246 036N07258 042N06506 042N06525 042N06546 042N06558 042N09006 042N09025 042N09046 042N09058 048N06506 048N06525 048N06546 048N06558 048N09006 048N09025 048N09046 048N09058 048N11006 048N11025 048N11046 048N11058 060N0650
036-21366-007-A-1205 TABLE 3: DNP024 COOLING CAPACITIES - 2 TON AIR ON EVAPORATOR COIL CFM 600 700 800 900 1000 600 700 800 900 1000 1. TEMPERATURE OF AIR ON CONDENSER COIL 85°F 95°F SENSIBLE CAPACITY1 NET CAP. MBH POWER INPUT KW 72 24.7 1.90 15.0 13.3 11.6 67 22.6 1.91 18.4 16.7 14.9 62 20.9 1.89 20.9 19.5 17.8 57 20.6 1.88 20.6 20.2 72 26.4 1.94 17.0 14.9 67 24.1 1.94 20.7 18.7 62 22.3 1.93 22.3 21.6 57 22.0 1.92 22.0 21.8 72 28.0 1.97 19.
036-21366-007-A-1205 TABLE 3: DNP024 COOLING CAPACITIES - 2 TON (CONT’D) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL CFM 600 700 800 900 1000 1. 125°F WB °F NET CAP. MBH POWER INPUT KW SENSIBLE CAPACITY1 ENTERING DRY BULB, °F 86 83 80 77 74 71 68 #N/A 72 18.4 2.5 13.1 11.4 9.7 8.0 6.3 #N/A 67 16.6 2.4 16.7 15.0 13.3 11.5 9.8 8.1 6.4 62 16.2 2.5 16.2 16.2 14.8 13.1 11.4 9.6 7.9 57 16.5 2.5 16.5 16.5 14.9 13.2 11.5 9.8 8.1 72 19.3 2.
036-21366-007-A-1205 TABLE 4: DNP030 COOLING CAPACITIES - 2-1/2 TON AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 57 72 67 62 57 NET CAP.MBH 33.6 31.6 30.3 30.2 34.5 32.4 31.1 31.0 TOTAL POWER INPUT kW 2.4 2.4 2.3 2.3 2.6 2.6 2.5 2.5 86 23.6 29.2 30.3 30.2 27.2 32.4 31.1 31.0 83 20.7 26.3 30.3 30.2 23.5 29.7 31.1 31.0 80 17.8 23.4 28.4 29.6 19.7 25.9 31.1 31.0 77 14.9 20.5 25.5 26.7 16.0 22.2 27.3 27.3 74 12.0 17.5 22.6 23.8 12.
036-21366-007-A-1205 TABLE 5: DNP036 COOLING CAPACITIES - 3 TON AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 72 Entering Dry Bulb °F 85 °F Sensible Capacity MBH1 NET CAP. MBH TOTAL POWER INPUT kW 86 83 80 77 74 71 68 Entering Dry Bulb °F MBH1 95 °F Sensible Capacity NET CAP. MBH TOTAL POWER INPUT kW 86 83 80 77 74 71 68 Entering Dry Bulb °F MBH1 105 °F Sensible Capacity NET CAP.
036-21366-007-A-1205 TABLE 6: DNP042 COOLING CAPACITIES - 3-1/2 TON AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 1,350 CFM NET CAP. Entering Dry Bulb °F Sensible Capacity MBH1 TOTAL POWER 85 °F Entering Dry Bulb °F MBH1 Sensible Capacity Entering Dry Bulb °F Sensible Capacity MBH1 Entering Dry Bulb °F MBH1 Sensible Capacity 57 44.5 40.9 41.2 54.0 49.6 45.6 46.0 3.3 3.8 3.7 3.6 3.7 41.2 36.8 44.4 45.6 46.0 83 29.1 36.0 40.9 41.2 32.4 40.1 45.6 46.
036-21366-007-A-1205 TABLE 7: DNP048 COOLING CAPACITIES - 4 TON AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 1,400 CFM WB °F Entering Dry Bulb °F 85 °F Sensible Capacity MBH1 NET CAP. MBH TOTAL POWER INPUT kW 1. Entering Dry Bulb °F Sensible Capacity MBH1 Entering Dry Bulb °F MBH1 Sensible Capacity Entering Dry Bulb °F Sensible Capacity MBH1 Entering Dry Bulb °F MBH1 Sensible Capacity 57 72 67 62 57 45.9 55.2 50.4 46.6 46.9 3.66 3.62 3.57 3.85 3.83 3.79 3.
036-21366-007-A-1205 TABLE 8: DNP060 COOLING CAPACITIES - 5 TON AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CONDENSER COIL 1,500 CFM WB °F Entering Dry Bulb °F 85 °F Sensible Capacity MBH1 NET CAP. MBH TOTAL POWER INPUT kW 1. Entering Dry Bulb °F Sensible Capacity MBH1 Entering Dry Bulb °F MBH1 Sensible Capacity Entering Dry Bulb °F Sensible Capacity MBH1 Entering Dry Bulb °F MBH1 Sensible Capacity 57 72 67 62 57 53.1 64.3 58.3 53.3 53.7 4.44 4.38 4.27 4.68 4.63 4.57 4.
036-21366-007-A-1205 TABLE 9: TWO TON AIR PERFORMANCE 1 EXTERNAL STAIC PRESSURE - IWG - - - - 984 443 894 422 751 390 608 358 - - - - 854 297 774 280 695 263 615 246 - - - - - - - - LOW 743 243 700 235 657 226 614 218 - - - - - - - - - - - - - - CFM WATTS 309 CFM WATTS 901 CFM 321 CFM 947 CFM 333 CFM 994 CFM HI MED CFM WATTS 1.10 CFM 1.00 WATTS .90 CFM .80 WATTS .70 WATTS .60 WATTS .50 WATTS .40 WATTS .30 WATTS .
036-21366-007-A-1205 TABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS1 EXTERNAL STATIC PRESSURE - IWG MODEL # DNP CFM .20 .30 .40 .50 .60 .70 .80 .90 1.
036-21366-007-A-1205 TABLE 11: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS1 EXTERNAL STATIC PRESSURE - IWG MODEL # DNP MODE (COOLING / HEATING) 030 COOLING (FACTORY SETTING) 030 .20 .30 .40 .50 .60 .70 .80 .90 1.
036-21366-007-A-1205 TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON RESISTANCE, IWG DESCRIPTION CFM 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 WET EVAPORATOR COIL .01 .01 .01 .02 .03 .04 .05 .06 .07 .08 .09 .09 ECONOMIZER1 .00 .00 .00 .01 .01 .01 .01 .02 .03 .04 .05 .06 FILTER FRAME KIT .01 .02 .04 .06 .08 .10 .13 .16 .17 .18 .19 .20 1.
036-21366-007-A-1205 C O N T A C T O R C O N T A C T O R F IE L D -S U P P L IE D D IS C O N N E C T G R O U N D L U G R E F E R T O E L E C T R IC A L D A T A T A B L E S T O S IZ E T H E D IS C O N N E C T S IN P H P O S U G L E A S E W E R P P L Y F IE L D -S U P P L IE D D IS C O N N E C T G R O U N D L U G T H R P H A P O W S U P R E F E R T O E L E C T R IC A L D A T A T A B L E S T O S IZ E T H E D IS C O N N E C T E E S E E R P L Y FIGURE 4 - POWER WIRING FIELD DIAGRAM TABLE 14: ELECTRI
036-21366-007-A-1205 V E N T AI R O U T L E T H O O D B L O W E R S E R V I C E A C C E S S C O M PA R T M E N T G AS S U P PL Y 1 - 1 / 4 " D I A . P A N E L H O L E ( 1 / 2 " N P T I C O N N E C T I O N ) C O N D E N S E R C O I L U N I T C O N D E N S A T E C O N N E C T I O N 3 / 4 " N P T I ( T R A P R E C O M M E N D E D ) A 2 - 3/ 8 H I G H V O L T A G E C O N N . 1 - 3 / 8 " D I A . K N O C K O U T H I G H V O L T A G E C O N N . 7 / 8 " D I A .
036-21366-007-A-1205 HIGH VOLTAGE CONN. 1-3/32" DIA. KNOCKOUT 8-7/8 11-7/8 19-1/4 FRONT GAS SUPPLY 1-5/8" DIA. KNOCKOUT (1/2" NPTI CONNECTION) LOW VOLTAGE CONN. 7/8 " DIA.
036-21366-007-A-1205 F IE L D S U P P L IE D D IS C O N N E C T S W IT C H L O C A T E D T O R E A R O F U N IT T O P O W E R C O N T R O L W IR IN G T O IN D O O R T H E R M O S T A T S U P P Y R E T U R N A IR D U C T S U P P L Y A IR D U C T T O G A S S U P P L Y L IN E M A N U A L G A S S H U T -O F F V A L V E FIGURE 8 - TYPICAL SLAB ON GROUND INSTALLATION M A N U A L G A S S H U T -O F F V A L V E S U D IS C S M O O T O F IE L D P P L IE D O N N E C T W IT C H U N T E D N U N IT P O W E
036-21366-007-A-1205 R O O F C U R B IN S T A L L A T IO N R E A R D U C T R O O F C U R B IN S T A L L A T IO N B O T T O M D U C T S L A B O N G R O U N D IN S T A L L A T IO N FIGURE 10 - TYPICAL DUCT APPLICATIONS TABLE 17: UNIT WEIGHTS AND CENTER OF GRAVITY UNIT SIZE SHIPPING WEIGHT (lbs.) CORNER WEIGHTS (location, lbs.) OPERATING WEIGHT (lbs.) “A” ECONOMIZER (lbs.) “B” “C” 024, 030, 036 400 395 100 96 98 101 “D” 042, 048, 060 475 470 133 130 102 104 40 ROOF CURB (lbs.
036-21366-007-A-1205 R E C O M M E N D E D D U C T S IZ E 1 7 -1 /2 " X 1 6 -3 /4 " 4 2 -2 /3 4 0 -3 /4 1 7 -5 /8 3 -1 /2 1 7 -1 /4 4 5 -1 /8 4 3 -1 /4 O P E N IN G F O R R E T U R N A IR D U C T 2 2 1 O P E N IN G F O R S U P P L Y A IR D U C T R E C O M M E N D E D D U C T S IZ E 1 7 -1 /8 " X 2 1 -1 /2 " 1 4 FIGURE 12 - ROOF CURB DIMENSIONS1 1 " 3 /4 " X 1 " W ID E G A S K E T IN G F O R C U R B F R A M E A N D A L L D U C T S U P P O R T S U R F A C E S U N IT B A S E U N IT B A S E R A IL
036-21366-007-A-1205 FIGURE 14 - TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60 POWER SUPPLY) Unitary Products Group 25
FAN RC1/RC2 BRN 205/R 206/R LS C 101/BK 102/Y R COMPR S 103/BR LP HP FS 211/PR 208/PR 213/R 204/O RS PS 205/R 213/R ALS 805/BL 801/BL 806/BR G C B A TB2 200/R 230 107/PR A M1 B A M2 B B 801/BL 7 2 209/BK 1 804/BK 805/BL 803/BK 802/BK 803/BK 804/BK S2 210/BL 207/Y 3 2 211/PR 4 GAS VALVE 2 5 3 6 CN1 EAC 4 1 204/O N N OUTDOOR FAN MOTOR 2 W1/ WHT DRAFT MOTOR PRP BLU CLEAR BLU 3 4 5 9 11 HEAT /BLK 10 13 R/RED 12 14 6 Y1/ YEL HS
036-21366-007-A-1205 FIGURE 16 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-1-60 POWER SUPPLY) Unitary Products Group 27
PRP 105/BL BRN 110/BK 100/BK 107/PR 108/PR 224/R 805/BL 801/BL 806/BR 205/R 206/R RS LS 121/BK 126/Y L3 L1 L2 COMPR 123/BL 211/PR 208/PR 213/R 204/O PS 205/R 213/R ALS 2 LP HP FS B 801/BL 7 2 1 804/BK 805/BL 803/BK 802/BK 803/BK 804/BK T1 208 2 1 2 5 3 6 CN1 EAC 4 1 204/O N N OUTDOOR FAN MOTOR BLK BRN PRP BLU BLU 2 W1/ WHT DRAFT MOTOR PRP 3 BLU 9 HEAT /BLK 10 11 4 R/RED 12 HSP 212/R 201/BR C1/BRN 214/BR 221/BR 220/O 5 13 14 6 CO
036-21366-007-A-1205 FIGURE 18 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-3-60 POWER SUPPLY) Unitary Products Group 29
036-21366-007-A-1205 FIGURE 19 - TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY) 30 Unitary Products Group
036-21366-007-A-1205 FIGURE 20 - TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY) Unitary Products Group 31
036-21366-007-A-1205 TYPICAL WIRING DIAGRAM NOTES 1. All field wiring to be accomplished following city, local and/or national codes in effect at time of installation of this unit. 2. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation if any of the wire as supplied with this unit must be removed it must be replaced with type 105°C, 600V wire or equivalent clearly renumbered for identification.
036-21366-007-A-1205 MECHANICAL SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK’s DNP is a unit that gives you the flexibility and choices you need in today’s market. These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation.
036-21366-007-A-1205 UNIT OPERATING CHARACTERISTICS ELECTRICAL REQUIREMENTS Unit shall be capable of starting and running at 125º F outdoor temperature, exceeding maximum load criteria ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 45º F outdoor temperature. Accessory low ambient kit shall be available for operation to 0º F.
036-21366-007-A-1205 Unitary Products Group 35
Subject to change without notice. Printed in U.S.A. Copyright © 2005 by Unitary Products Group. All rights reserved.