Technical Guide

718444-YTG-E-0613
62 Johnson Controls Unitary Products
DNZ/DNQ/DNY/DNX Additional Static Resistance
Size
(Tons)
CFM Wet Indoor Coil Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter/Frame Kit Electric Heat
DNZ/DNQ/DNY/DNX
024
(2.0)
500 0.01 0.00 0.01 -
600 0.01 0.00 0.02 -
700 0.01 0.00 0.04 -
800 0.02 0.01 0.06 -
900 0.03 0.01 0.08 -
1000 0.04 0.01 0.10 -
1100 0.05 0.01 0.13 -
1200 0.06 0.02 0.16 -
DNZ/DNQ
030
(2.5)
700 0.01 0.00 0.04 -
800 0.02 0.01 0.06 -
900 0.03 0.01 0.08 -
1000 0.04 0.01 0.10 -
1100 0.05 0.01 0.13 -
1200 0.06 0.02 0.16 -
1300 0.07 0.03 0.17 -
DNZ/DNQ/DNY/DNX
036
(3.0)
700 0.01 0.00 0.04 -
800 0.02 0.01 0.06 -
900 0.03 0.01 0.08 -
1000 0.04 0.01 0.10 -
1100 0.05 0.01 0.13 -
1200 0.06 0.02 0.16 -
1300 0.07 0.03 0.17 -
1400 0.08 0.04 0.18 -
DNZ/DNQ
042
(3.5)
1100 0.02 0.02 0.04 -
1200 0.03 0.02 0.04 -
1300 0.04 0.02 0.05 -
1400 0.05 0.03 0.05 -
1500 0.06 0.04 0.06 -
1600 0.07 0.04 0.07 -
1700 0.07 0.04 0.08 -
1800 0.08 0.04 0.09 -
1900 0.09 0.05 0.10 -
2000 0.09 0.05 0.11 -
DNZ/DNQ
048
(4.0)
1100 0.02 0.02 0.04 -
1200 0.03 0.02 0.04 -
1300 0.04 0.02 0.05 -
1400 0.05 0.03 0.05 -
1500 0.06 0.04 0.06 -
1600 0.07 0.04 0.07 -
1700 0.07 0.04 0.08 -
1800 0.08 0.04 0.09 -
1900 0.09 0.05 0.10 -
2000 0.09 0.05 0.11 -
DNZ/DNQ/DNY
060
(5.0)
1100 0.02 0.02 0.04 -
1200 0.03 0.02 0.04 -
1300 0.04 0.02 0.05 -
1400 0.05 0.03 0.05 -
1500 0.06 0.04 0.06 -
1600 0.07 0.04 0.07 -
1700 0.07 0.04 0.08 -
1800 0.08 0.04 0.09 -
1900 0.09 0.05 0.10 -
2000 0.09 0.05 0.11 -