115°F 125°F
875
77
39.1 3.8 18.9 13.9 10.9 - - - 36.1 4.1 20.4 11.9 9.9 - - -
72
34.3 3.7 24.2 20.1 15.9 11.8 - - 31.0 3.9 23.1 18.9 14.6 10.4 - -
67
29.6 3.6 29.6 26.3 20.9 16.8 12.6 - 25.8 3.8 25.8 25.8 19.3 15.1 10.9 -
62
31.0 3.5 31.0 31.0 24.8 20.6 16.4 12.3 29.5 3.8 29.5 29.5 22.9 18.6 14.4 10.1
1050
57
40.7 3.8 24.7 17.2 12.4 - - - 37.5 4.1 26.4 16.6 11.4 - - -
77
35.8 3.7 27.7 22.9 18.1 13.2 - - 32.1 3.9 26.6 21.7 16.8 11.8 - -
72
30.8 3.6 30.8 28.6 23.8 18.9 14.1 - 26.8 3.8 26.8 26.8 22.2 17.3 12.3 -
67
32.3 3.5 32.3 32.3 28.1 23.3 18.5 13.6 30.7 3.8 30.7 30.7 26.2 21.3 16.4 11.4
62
29.5 3.6 29.5 29.5 25.4 20.6 15.7 10.9 26.9 3.8 26.9 26.9 22.5 17.6 12.7 7.8
1225
57
42.4 3.8 30.5 20.6 13.9 - - - 38.8 4.1 32.5 21.3 12.8 - - -
77
37.2 3.7 31.2 25.7 20.2 14.7 - - 33.3 4.0 30.1 24.5 18.9 13.3 - -
72
32.0 3.6 32.0 30.9 26.6 21.1 15.6 - 27.7 3.8 27.7 27.7 25.0 19.4 13.8 -
67
33.6 3.6 33.6 33.6 31.5 26.0 20.5 15.0 31.8 3.8 31.8 31.8 29.6 24.0 18.3 12.7
62
30.7 3.6 30.7 30.7 28.4 22.9 17.4 11.9 27.8 3.8 27.8 27.8 25.4 19.8 14.2 8.6
1400
57
44.0 3.8 36.2 23.9 15.3 - - - 40.2 4.1 38.5 26.0 14.3 - - -
72
38.6 3.7 34.7 28.6 22.4 16.2 - - 34.4 4.0 33.6 27.3 21.1 14.8 - -
67
33.2 3.6 33.2 33.2 29.4 23.3 17.1 - 28.7 3.8 28.7 28.7 27.8 21.6 15.3 -
62
34.8 3.6 34.8 34.8 34.8 28.7 22.5 16.3 32.9 3.8 32.9 32.9 32.9 26.6 20.3 14.1
57
31.9 3.6 31.9 31.9 31.5 25.3 19.1 13.0 28.8 3.8 28.8 28.8 28.3 22.1 15.8 9.5
1515
72
38.9 3.7 36.6 30.0 23.4 16.8 - - 34.7 4.0 34.7 28.7 22.0 15.2 - -
67
33.5 3.6 33.5 33.5 30.7 24.1 17.5 - 29.0 3.9 29.0 29.0 29.0 22.3 15.5 -
62
35.1 3.6 35.1 35.1 35.1 28.5 21.9 15.3 33.2 3.8 33.2 33.2 33.2 26.4 19.7 12.9
57
32.1 3.6 32.1 32.1 31.9 25.3 18.7 12.1 29.1 3.8 29.1 29.1 28.8 22.1 15.3 8.5
1630
72
39.2 3.7 38.5 31.4 24.4 17.3 - - 35.0 4.0 35.0 30.1 22.9 15.6 - -
67
33.8 3.6 33.8 33.8 32.0 25.0 17.9 - 29.2 3.9 29.2 29.2 29.2 23.0 15.8 -
62
35.4 3.6 35.4 35.4 35.4 28.3 21.3 14.2 33.5 3.9 33.5 33.5 33.5 26.2 19.0 11.8
57
32.4 3.6 32.4 32.4 32.4 25.3 18.3 11.2 29.3 3.9 29.3 29.3 29.3 22.1 14.8 7.6
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DNZ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65