Technical Guide

718444-YTG-E-0613
38 Johnson Controls Unitary Products
115°F 125°F
1400
77 47.2 4.2 32.9 23.5 17.4 - - - 44.1 4.6 33.6 23.0 16.4 - - -
72 44.5 4.2 37.4 31.3 25.2 19.1 - - 41.7 4.6 36.4 30.3 24.1 17.9 - -
67 41.8 4.2 41.8 39.0 32.9 26.8 20.7 - 39.3 4.6 39.3 38.0 31.8 25.6 19.5 -
62 41.5 4.2 41.5 40.8 35.9 29.8 23.7 17.6 39.5 4.6 39.5 38.5 32.8 26.6 20.5 14.3
57 42.0 4.2 42.0 41.4 36.4 30.3 24.2 18.1 41.6 4.6 41.6 40.6 34.8 28.6 22.5 16.3
1500
77 46.6 4.2 36.4 24.4 17.9 - - - 43.4 4.6 37.7 24.3 16.9 - - -
72 43.9 4.2 38.8 32.3 25.8 19.2 - - 41.0 4.6 38.2 31.5 24.8 18.2 - -
67 41.2 4.2 41.2 40.2 33.7 27.1 20.6 - 38.6 4.6 38.6 38.6 32.8 26.1 19.4 -
62 41.0 4.1 41.0 41.0 36.8 30.2 23.7 17.2 38.8 4.6 38.8 38.8 33.8 27.2 20.5 13.8
57 41.5 4.1 41.5 41.5 37.3 30.8 24.2 17.7 41.0 4.6 41.0 41.0 35.9 29.2 22.5 15.9
1650
72 42.6 4.2 40.0 33.7 26.7 19.6 - - 39.3 4.6 38.7 32.7 25.6 18.4 - -
67 39.9 4.2 39.9 39.4 34.9 27.8 20.8 - 37.0 4.6 37.0 37.0 33.7 26.6 19.4 -
62 39.7 4.2 39.7 39.7 37.6 30.5 23.5 16.4 37.3 4.6 37.3 37.3 34.8 27.6 20.4 13.3
57 40.2 4.1 40.2 40.2 38.1 31.1 24.0 17.0 39.3 4.6 39.3 39.3 36.8 29.6 22.5 15.3
1800
72 41.2 4.2 41.2 35.2 27.6 20.1 - - 37.6 4.6 37.6 34.0 26.3 18.6 - -
67 38.7 4.2 38.7 38.7 36.1 28.5 21.0 - 35.4 4.6 35.4 35.4 34.7 27.1 19.4 -
62 38.4 4.2 38.4 38.4 38.4 30.9 23.3 15.7 35.7 4.6 35.7 35.7 35.7 28.0 20.4 12.7
57 38.9 4.2 38.9 38.9 38.9 31.4 23.8 16.2 37.7 4.6 37.7 37.7 37.7 30.1 22.4 14.7
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DNQ048 (4.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65