Technical Guide

DNX Electrical Data
718444-YTG-E-0613
Johnson Controls Unitary Products 67
DNY Electrical Data
Model
(Tons)
Volt
Compressor
OD Fan
Motor
Supply
Blower
Motor
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA
DNY024
(2.0)
208/230-1-60 10.2 52 16 1.4 4.3 18.5 25
DNY036
(3.0)
208/230-1-60 16.6 82 26 1.4 6.8 29 35
208/230-3-60 11.1 58 17 1.4 6.8 22.1 30
DNY048
(4.0)
208/230-1-60 21.1 96 33 1.7 9.1 37.2 45
208/230-3-60 13.4 88 21 1.7 9.1 27.6 35
DNY060
(5.0)
208/230-1-60 25.6 118 40 1.8 9.1 42.9 60
208/230-3-60 17.6 135 28 1.8 9.1 32.9 40
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Model
(Tons)
Volt
Compressor
OD Fan
Motor
Supply
Blower
Motor
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA
DNX024
(2.0)
208/230-1-60 10.2 52 16 1.4 4.3 18.1 25
DNX036
(3.0)
208/230-1-60 16.6 82 26 0.9 9.1 30.7 40
208/230-3-60 11.1 58 17 0.9 9.1 23.8 30
460-3-60 4.5 29 7 0.5 4.6 10.7 15
DNX048
(4.0)
208/230-1-60 21.1 96 33 1.8 9.1 36.3 45
208/230-3-60 13.4 88 21 1.8 9.1 26.7 35
460-3-60 6.4 41 10 0.9 4.6 13.0 15
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.