Technical Guide

718444-YTG-F-0214
30 Johnson Controls Unitary Products
115°F 125°F
600
77
23.2 2.2 13.2 10.0 7.5 - - - 21.3 2.4 14.3 9.5 7.0 - - -
72
20.5 2.2 15.5 13.0 10.5 8.0 - - 18.3 2.3 14.8 12.3 9.8 7.3 - -
67
17.8 2.1 17.8 16.1 13.6 11.1 8.6 - 15.3 2.3 15.3 15.0 12.5 10.1 7.6 -
62
17.3 2.1 17.3 17.3 15.3 12.8 10.3 7.8 15.5 2.2 15.5 15.5 13.6 11.1 8.6 6.1
57
17.4 2.1 17.4 17.4 15.3 12.8 10.3 7.8 15.7 2.2 15.7 15.7 13.7 11.2 8.7 6.2
700
77
23.6 2.2 15.8 11.1 8.1 - - - 21.4 2.4 16.8 11.4 7.6 - - -
72
20.9 2.2 16.9 14.2 11.4 8.6 - - 18.4 2.3 16.0 13.3 10.6 7.8 - -
67
18.1 2.1 18.1 17.2 14.7 11.9 9.1 - 15.3 2.3 15.3 15.3 13.5 10.8 8.0 -
62
17.5 2.1 17.5 17.5 16.5 13.8 11.0 8.2 15.5 2.3 15.5 15.5 14.7 11.9 9.2 6.4
57
17.7 2.1 17.7 17.7 16.6 13.8 11.1 8.3 15.7 2.2 15.7 15.7 14.8 12.0 9.3 6.5
800
77
24.0 2.2 18.4 12.2 8.7 - - - 21.5 2.4 19.3 13.3 8.1 - - -
72
21.2 2.2 18.4 15.3 12.3 9.2 - - 18.4 2.3 17.3 14.3 11.3 8.3 - -
67
18.4 2.1 18.4 18.4 15.8 12.8 9.7 - 15.3 2.3 15.3 15.3 14.5 11.5 8.5 -
62
17.8 2.1 17.8 17.8 17.8 14.8 11.7 8.6 15.6 2.3 15.6 15.6 15.6 12.7 9.7 6.7
57
18.0 2.1 18.0 18.0 17.9 14.8 11.8 8.7 15.8 2.3 15.8 15.8 15.8 12.8 9.8 6.8
900
72
21.3 2.2 19.2 16.0 12.7 9.4 - - 18.7 2.3 18.1 14.9 11.7 8.5 - -
67
18.5 2.2 18.5 18.5 16.4 13.1 9.9 - 15.6 2.3 15.6 15.6 15.0 11.8 8.6 -
62
17.9 2.1 17.9 17.9 17.9 14.7 11.4 8.2 15.8 2.3 15.8 15.8 15.8 12.7 9.5 6.3
57
18.1 2.1 18.1 18.1 18.1 14.8 11.5 8.3 16.1 2.3 16.1 16.1 16.1 12.9 9.7 6.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DNQ024 (2.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65