Installation manual

035-19084-001-D-0504
Unitary Products Group 33
NOTE 1: HACR Type per NEC.
TABLE 11: DR ELECTRICAL DATA - STANDARD DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
15
208 21.8 184 2.1 15.4 10.0
None 0.0 ~ ~ 82.9 100
E18 13.5 1 37.5 82.9 100
E36 27.0 2 75.1 125.4 150
E54 40.6 2 112.6 172.6 175
E72 54.1 2 150.1 181.9 200
230 21.8 184 2.1 15.4 10.0
None 0.0 ~ ~ 81.9 100
E18 18.0 1 43.3 84.6 100
E36 36.0 2 86.6 138.8 150
E54 54.0 2 129.9 160.4 175
E72 72.0 2 173.2 203.7 225
460 11.0 90 1.1 7.2 5.0
None 0.0 ~ ~ 41.4 50
E18 18.0 1 21.7 42.3 50
E36 36.0 2 43.3 69.4 70
E54 54.0 2 65.0 80.2 90
E72 72.0 2 86.6 101.9 110
575 9.6 73 0.9 5.9 4.0
None 0.0 ~ ~ 35.1 40
E18 18.0 1 17.3 35.1 40
E36 36.0 2 34.6 55.7 60
E54 54.0 2 52.0 64.3 70
E72 72.0 2 69.3 81.7 90
20
208 33.6 225 3.7 20.0 10.0
None 0.0 ~ ~ 120.4 150
E18 13.5 1 37.5 120.4 150
E36 27.0 2 75.1 131.2 125
E54 40.6 2 112.6 178.4 200
E72 54.1 2 150.1 187.7 200
230 33.6 225 3.7 20.0 10.0
None 0.0 ~ ~ 120.4 150
E18 18.0 1 43.3 120.4 150
E36 36.0 2 86.6 145.8 150
E54 54.0 2 129.9 167.4 175
E72 72.0 2 173.2 210.7 225
460 17.3 114 1.9 10.0 5.0
None 0.0 ~ ~ 61.5 70
E18 18.0 1 21.7 61.5 70
E36 36.0 2 43.3 72.9 80
E54 54.0 2 65.0 83.7 90
E72 72.0 2 86.6 105.4 110
575 13.5 80 1.5 8.2 4.0
None 0.0 ~ ~ 48.6 60
E18 18.0 1 17.3 48.6 60
E36 36.0 2 34.6 58.6 60
E54 54.0 2 52.0 67.2 70
E72 72.0 2 69.3 84.5 90
25
208 47.1 245 3.7 38.6 10.0
None 0.0 ~ ~ 169.4 200
E18 13.5 1 37.5 169.4 200
E36 27.0 2 75.1 169.4 200
E54 40.6 2 112.6 201.6 225
E72 54.1 2 150.1 210.9 225
230 47.1 245 3.7 38.6 10.0
None 0.0 ~ ~ 169.4 200
E18 18.0 1 43.3 169.4 200
E36 36.0 2 86.6 169.4 200
E54 54.0 2 129.9 190.7 225
E72 72.0 2 173.2 234.0 250
460 19.6 125 1.9 19.3 5.0
None 0.0 ~ ~ 76.0 90
E18 18.0 1 21.7 76.0 90
E36 36.0 2 43.3 84.5 90
E54 54.0 2 65.0 95.3 110
E72 72.0 2 86.6 117.0 125
575 15.8 100 1.5 15.4 4.0
None 0.0 ~ ~ 61.0 70
E18 18.0 1 17.3 61.0 70
E36 36.0 2 34.6 67.6 70
E54 54.0 2 52.0 76.2 90
E72 72.0 2 69.3 93.5 100
VOLTAGE LIMITATIONS ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
MIN. MAX. 208 208 1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60 187 253 240 230 0.92
460-3-60 414 506 480 460 0.92
565-3-60 518 630 600 575 0.92
1.
Utilization Range “A” in accordance with ARI Standard 110.