Installation manual

035-19084-001-D-0504
Unitary Products Group 35
NOTE 1: HACR Type per NEC.
TABLE 13: DR ELECTRICAL DATA - LOW SPEED DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
25
208 47.1 245 3.7 20.0 10.0
None 0.0 ~ ~ 150.8 175
E18 13.5 1 37.5 150.8 175
E36 27.0 2 75.1 150.8 175
E54 40.6 2 112.6 178.4 200
E72 54.1 2 150.1 187.7 200
230 47.1 245 3.7 20.0 10.0
None 0.0 ~ ~ 150.8 175
E18 18.0 1 43.3 150.8 175
E36 36.0 2 86.6 150.8 175
E54 54.0 2 129.9 167.4 175
E72 72.0 2 173.2 210.7 225
460 19.6 125 1.9 10.0 5.0
None 0.0 ~ ~ 66.7 80
E18 18.0 1 21.7 66.7 80
E36 36.0 2 43.3 72.9 80
E54 54.0 2 65.0 83.7 90
E72 72.0 2 86.6 105.4 110
575 15.8 100 1.5 8.2 4.0
None 0.0 ~ ~ 53.8 60
E18 18.0 1 17.3 53.8 60
E36 36.0 2 34.6 58.6 60
E54 54.0 2 52.0 67.2 70
E72 72.0 2 69.3 84.5 90
VOLTAGE LIMITATIONS ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
MIN. MAX. 208 208 1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60 187 253 240 230 0.92
460-3-60 414 506 480 460 0.92
565-3-60 518 630 600 575 0.92
1.
Utilization Range “A” in accordance with ARI Standard 110.