TABLE 16: DR180 BLOWER PERFORMANCE - HIGH STATIC DRIVE (COOLING ONLY)
15 Ton High Static Drive Blower Performance (Horizontal Discharge)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP
0.2 8109 1124 6.31 8.00 7890 1085 5.70 7.22 7566 1046 5.20 6.59 7196 1006 4.47 5.66 6850 966 3.96 5.01 6436 925 3.43 4.3
0.4 7821 1125 6.03 7.64 7585 1086 5.34 6.77 7229 1046 4.89 6.20 6857 1006 4.20 5.32 6487 967 3.70 4.68 6070 926 3.20 4.0
0.6 7513 1127 5.71 7.24 7267 1088 5.12 6.49 6879 1047 4.56 5.77 6500 1008 3.93 4.99 6113 968 3.44 4.36 5666 927 2.95 3.7
0.8 7190 1128 5.39 6.83 6865 1089 4.78 6.06 6518 1048 4.26 5.40 6124 1009 3.66 4.64 5696 969 3.16 4.01 5257 928 2.70 3.4
1 6825 1130 5.06 6.42 6506 1090 4.48 5.67 6135 1048 3.96 5.01 5712 1010 3.38 4.28 5239 970 2.87 3.64 4731 929 2.41 3.0
1.2 6455 1131 4.72 5.98 6122 1092 4.16 5.27 5752 1050 3.66 4.64 5250 1011 3.06 3.88 4729 970 2.57 3.25 4243 930 2.15 2.7
1.4 6062 1133 4.39 5.56 5700 1094 3.82 4.84 5260 1051 3.31 4.19 4763 1013 2.76 3.49 4184 971 2.26 2.87
1.6 5650 1135 4.04 5.12 5243 1095 3.48 4.41 4637 1052 2.90 3.67 4272 1014 2.47 3.13
1.8 5213 1136 3.69 4.68 4770 1097 3.15 3.99 4416 1053 2.75 3.49
2 4750 1138 3.36 4.26
1 Turn 2 Turns 3 Turns 4 Turns 5 Turns 6 Turns
Chart shading corresponds to minimum motor horsepower requirements as defined below.
7.5 HP motor 5 HP motor