TABLE 23: DR300 BLOWER PERFORMANCE - HIGH STATIC DRIVE
25 Ton Blower Performance (Horizontal Discharge) (High Static Option)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP
0.4 11600 1200 12.5 16.0 11175 1164 11.5 14.7 10620 1127 10.4 13.3 10500 1092 9.2 11.7 9875 1058 8.2 10.5 9100 1020 7.4 9.4
0.6 11060 1201 11.8 15.1 10600 1166 10.8 13.8 10100 1131 9.7 12.4 9980 1095 8.6 11.0 9320 1060 7.6 9.7 8920 1022 6.9 8.8
0.8 10500 1203 11.1 14.2 10100 1169 10.2 13.0 9520 1132 9.1 11.6 9360 1097 8 10.2 8600 1061 6.9 8.8 8230 1024 6.3 8.0
1 9930 1205 10.4 13.3 9430 1171 9.5 12.1 8870 1134 8.4 10.7 8800 1099 7.4 9.4 8240 1063 6.4 8.2 7500 1025 5.7 7.3
1.2 9800 1207 9.9 12.6 9270 1173 8.9 11.4 8590 1136 7.9 10.1 8120 1101 6.8 8.7 7240 1065 5.7 7.3 6990 1027 5.2 6.6
1.4 9200 1210 9.2 11.7 8480 1174 7.9 10.1 8070 1039 7.1 9.1 7340 1103 6.1 7.8 6820 1066 5.3 6.8 6100 1029 4.8 6.1
1.6 8400 1213 8.4 10.7 7750 1177 7.2 9.2 7560 1140 6.5 8.3 7220 1103 5.9 7.5 5380 1069 4.2 5.4
1.8 7830 1215 7.7 9.8 7600 1178 7 8.9 6600 1142 5.6 7.1 5810 1106 4.7 6.0
2 7300 1216 7 8.9 6300 1180 6.1 7.8 5450 1145 4.9 6.3
2.2 6400 1218 6.2 7.9 5230 1184 5.1 6.5
2.4 5400 1221 5.4 6.9
1 Turn 2 Turns 3 Turns 4 Turns 5 Turns 6 Turns
Chart shading corresponds to minimum horsepower requirements as defined below.
15 HP motor 10 HP motor 7.5 HP motor