the unit into the reheat mode. While in the reheat
mode, the unit operates both stages of compression
and the one reheat coil.
When the room thermostat calls for first stage cooling
while there is still a call for dehumidification, no opera-
tional change is made. The unit continues to operate
both stages of compression with system #1 in the
reheat mode.
When the room thermostat calls for second stage cool-
ing, the RCB senses a signal through “Y1” & “Y2” and
de-energizes the HGR, which de-energizes SOL 3 and
SOL 2, and energizes SOL 1.
Indoor blower operation is initiated upon a call for first
stage cooling, second stage cooling or dehumidifica-
tion.
Anytime there is a call for 2 stages of cooling, the unit
will not operate in the reheat mode, even if there is still
a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is
any call for heating.
All safety devices function as previously described.