Installation manual

035-16682-000-E-0303
28 Unitary Products Group
TABLE 18: ELECTRICAL DATA BASIC UNIT WITH POWER EXHAUST - 30 TON
VOLTAGE
SUPPLY AIR MOTOR EXHAUST FAN MOTOR BASIC UNIT WITH EXHAUST FAN
HP HP FLA MCA
MAX. OVERCURRENT
PROTECTION DEVICE
208-3-60
10
7.5 24.2 192 225
10 30.8 199 225
15 46.2 216 250
15
7.5 24.2 209 250
10 30.8 216 250
15 46.2 231 250
20
7.5 24.2 226 250
10 30.8 233 250
15 46.2 248 300
25
7.5 24.2 245 300
10 30.8 252 300
15 46.2 267 300
230-3-60
10
7.5 22.0 186 200
10 28.0 192 225
15 42.0 207 225
15
7.5 22.0 201 225
10 28.0 207 225
15 42.0 221 250
20
7.5 22.0 216 250
10 28.0 222 250
15 42.0 236 250
25
7.5 22.0 233 300
10 28.0 239 300
15 42.0 253 300
460-3-60
10
7.5 11.0 92 110
10 14.0 95 110
15 21.0 102 110
15
7.5 11.0 99 110
10 14.0 102 110
15 21.0 109 125
20
7.5 11.0 107 125
10 14.0 110 125
15 21.0 117 125
25
7.5 11.0 115 125
10 14.0 118 150
15 21.0 125 150
575-3-60
10
7.5 9.0 75 90
10 11.0 77 90
15 17.0 84 100
15
7.5 9.0 82 90
10 11.0 84 100
15 17.0 90 100
20
7.5 9.0 88 100
10 11.0 90 110
15 17.0 96 110
25
7.5 9.0 94 110
10 11.0 96 110
15 17.0 102 125