Installation manual

035-16682-000-E-0303
34 Unitary Products Group
460-3-60
40 40
10
7.5 11 92 110
10 14 95 110
15 21 104 110
15
7.5 11 100 110
10 14 104 110
15 21 113 125
20
7.5 11 108 125
10 14 111 125
15 21 120 125
25
7.5 11 116 125
10 14 120 150
15 21 129 150
80 80
10
7.5 11 127 150
10 14 131 150
15 21 140 150
15
7.5 11 136 150
10 14 140 150
15 21 149 150
20
7.5 11 144 150
10 14 147 150
15 21 156 175
25
7.5 11 152 175
10 14 156 175
15 21 165 175
108 108
10
7.5 11 161 175
10 14 165 175
15 21 174 175
15
7.5 11 170 175
10 14 174 175
15 21 182 200
20
7.5 11 177 200
10 14 181 200
15 21 190 200
25
7.5 11 186 200
10 14 190 200
15 21 199 225
TABLE 21: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 30 TON (Continued)
VOLTAGE
ELECTRIC HEAT
SUPPLY
AIR MOTOR
EXHAUST FAN
BASIC UNIT WITH EXHAUST FAN
AND ELECTRIC HEAT
NOMINAL
KW
APPLIED KW HP HP FLA MCA
MAX. OVERCURRENT
PROTECTION