Installation manual

035-16682-000-E-0303
Unitary Products Group 47
AIRFLOW CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.2 3.4 3.6 3.8 4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
4000 864 4.90 890 5.26 913 5.64 935 6.01 957 6.39
5000 878 5.69 904 6.10 927 6.51 950 6.92 973 7.33
6000 885 6.47 911 6.91 935 7.36 959 7.82 983 8.29
7000 889 7.25 914 7.74 939 8.24 964 8.75 988 9.25
8000 892 8.13 918 8.66 942 9.18 967 9.71 992 10.26
9000 897 9.09 921 9.63 946 10.18 970 10.78 995 11.37
10000 903 10.15 927 10.76 951 11.36 975 11.97 999 12.57
11000 913 11.50 936 12.10 959 12.70 983 13.30 1005 13.90
12000 926 12.96 948 13.54 970 14.12 992 14.70 1013 15.33
13000 942 14.55 963 15.12 984 15.79 1005 16.45 1025 17.11
1.
Fan performance is based on wet evaporator coils, clean 2-inch throwaway filters and system/cabinet effects at standard air den-
sity and 0 degree elevation.
2.
Refer to Tables 26, 45, and 54 for component additions and deductions to fan performance tables.
3.
BHP does not include drive losses. Multiply BHP by 1.05 for drive losses.
TABLE 23: FAN PERFORMANCE - 25 TON
1
2
(Continued)