Installation manual

035-16682-000-E-0303
50 Unitary Products Group
AIRFLOW (CFM)
Available External Static Pressure (IWG)
3.2 3.4 3.6 3.8 4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
6000 877 6.4 904 6.8 928 7.3 951 7.7 975 8.2
7000 885 7.3 911 7.8 935 8.3 959 8.8 984 9.2
8000 892 8.4 917 8.9 942 9.4 966 9.9 991 10.4
9000 900 9.5 925 10.1 949 10.6 974 11.2 998 11.8
10000 910 10.9 934 11.5 958 12.1 982 12.7 1006 13.3
11000 923 12.4 946 13.0 970 13.6 993 14.2 1015 14.8
12000 939 14.0 961 14.6 984 15.3 1006 16.0 1028 16.7
13000 958 15.8 980 16.5 1001 17.2 1022 17.9 1043 18.6
14000 980 17.9 1001 18.7 1021 19.4 1040 20.1 1060 20.8
15000 1004 20.2 1023 21.0 1043 21.8 1062 22.5 1081 23.3
1.
Fan performance is based on wet evaporator coils, clean 2-inch throwaway filters and system/cabinet effects at standard air den-
sity and 0 degree elevation.
2.
Refer to Tables 26, 45, and 54 for component additions and deductions to fan performance tables.
3.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
TABLE 24: FAN PERFORMANCE -30 TON
1
2
(Continued)