Installation manual

035-16682-000-E-0303
Unitary Products Group 53
AIRFLOW (CFM)
Available External Static Pressure (IWG)
3.2 3.4 3.6 3.8 4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
8000 774 8.3 797 8.8 817 9.4 837 9.9 857 10.5
9000 784 9.3 806 9.8 826 10.4 846 11.0 866 11.6
10000 794 10.3 815 11.0 836 11.6 856 12.3 876 12.9
11000 804 11.6 824 12.2 845 12.9 865 13.6 886 14.2
12000 814 12.9 835 13.6 855 14.3 876 15.0 896 15.7
13000 825 14.4 846 15.1 866 15.8 886 16.6 906 17.3
14000 837 16.0 858 16.8 878 17.5 898 18.3 917 19.1
15000 851 17.8 871 18.6 891 19.4 910 20.2 928 21.0
16000 866 19.7 886 20.5 905 21.4 923 22.2 941 23.1
17000 882 21.9 901 22.7 919 23.6 937 24.5 - -
18000 900 24.2 --------
1.
Fan performance is based on wet evaporator coils, clean 2-inch throwaway filters and system/cabinet effects at standard air den-
sity and 0 degree elevation.
2.
Refer to Tables 26, 46 and 55 for component additions and deductions to fan performance tables.
3.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
TABLE 25: FAN PERFORMANCE - 40 TON
1
2
(Continued)