Installation manual
035-16682-000-E-0303
Unitary Products Group 81
TABLE 47: HOT WATER COIL (1 ROW 25 & 30 TON)
1
1.
Based on 60°F entering air temperature, 2.00” maximum
pressure drop across the hot water coil.
GPM CFM
Capacity (MBH) at Entering Water
Temperature
140 °F 160 °F 180 °F 200 °F
10
6000 91.4 115.3 139.3 163.6
8000 102 128.8 155.8 182.9
10000 110.4 139.5 168.8 198.4
12000 117.3 148.4 179.6 211.2
15000 125.9 159.2 192.9 226.9
20
6000 103 129.4 156 182.7
8000 116.8 147 177.2 207.7
10000 128.2 161.3 194.7 228.2
12000 137.8 173.6 209.5 245.6
15000 150 189 228.2 267.8
30
6000 107.6 135 162.5 190.1
8000 122.8 154.3 185.8 217.5
10000 135.5 170.3 205.1 240.2
12000 146.4 184 221.8 259.7
15000 160.3 201.6 243 284.8
40
6000 110.1 138 166 194.1
8000 126.1 158.2 190.5 222.8
10000 139.6 175.2 210.9 246.8
12000 151.2 189.8 228.5 267.5
15000 166.1 208.6 251.3 294.1
TABLE 48: HOT WATER COIL (1 ROW, 40 TON)
1
1.
Based on 60°F entering air temperature, 2.00” maximum
pressure drop across the hot water coil.
GPM CFM
Capacity (MBH) at Entering Water
Temperature
140 °F 160 °F 180 °F 200 °F
10
8000 102 128.8 155.8 182.9
11000 114 144.1 174.4 205.1
14000 123.2 155.9 188.8 222.1
17000 130.6 165.4 200.4 235.8
20000 136.8 173.3 210.1 247.3
20
8000 116.8 147 177.2 207.7
11000 133.2 167.7 202.3 237.2
14000 146.2 184.2 222.4 260.8
17000 157 197.9 239 280.5
20000 166.2 209.6 253.2 297.3
30
8000 122.8 154.3 185.8 217.5
11000 141.2 177.4 213.8 250.3
14000 155.9 196.1 236.4 276.9
17000 168.3 211.8 255.4 299.3
20000 179.1 225.3 271.8 318.6
40
8000 126.1 158.2 190.5 222.8
11000 145.6 182.7 220 257.5
14000 161.4 202.6 244.1 285.8
17000 174.7 219.5 264.5 309.7
20000 186.3 234.2 282.3 330.6