Installation manual

035-16682-000-E-0303
Unitary Products Group 9
RIGGING AND HANDLING
This unit is not designed to be handled with a fork-truck
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the holes pro-
vided in lifting lugs. Spreaders MUST be used across the top
of the unit. Refer to Figure 1.
Rig with six cables and spread with four 95-inch spread-
ers across width and two spreaders of length equal to A
+ B.
Refer to Tables 4 and 5 for unit weight.
Center of gravity includes economizer, exhaust or return
air fan and inlet guide vanes (Refer to Table 6).
TABLE 4: UNIT WEIGHTS
COMPONENT 25 TON 30 TON 40 TON
Basic Unit
1
1.
Weight includes the 10HP motor and economizer.
4,300 4,600 5,100
Gas Heat
233 MBH 90 90 90
466 MBH 180 180 180
699 MBH 270 270 270
Electric Heat
40KW 757575
80KW 909090
108KW 100 100 100
Hot Water Heat
Hot Water Coil 1
Row
71 71 lbs. 71 lbs
Hot Water Coil 2
Row
90 90 lbs. 90 lbs.
Steam Heat
Steam Coil 1 Row 87 lbs. 87 lbs. 87 lbs.
Blower Motor (Std./Hi-eff)
7.5hp 0/10 - -
10hp 10/20 0/10 0/10
15hp 60/100 50/90 50/90
20hp 105/110 95/100 85/110
25hp - 165/200 165/200
Inlet Guide Vanes
w/ Actuator
175 175 205
VFD
2
2.
Weight for 20-25HP drive.
24 lbs. 24 lbs. 24 lbs.
VFD w/Bypass
2
28 lbs. 28 lbs. 28 lbs.
Exhaust
Barometric 40 75 75
Powered 180 325 325
Exhaust Motor (Std./Hi-eff)
5hp 75/90 - -
7.5hp 100/110 100/110 100/110
10hp 110/120 110/120 110/120
15hp - 160/200 160/200
Low Ambient Head Pressure Control
208/203V,460V &
380-3-50Hz
10 10 10
575V &
380-3-60 Hz
40 40 40
Filters
6" Rigid 80 80 80
Refrigeration
Hi Capacity Coil N/A 45 25
Coated Cond. Coil 32 30 40
Hot Gas Bypass 20 20 20
Disconnect
Convenience
Outlet
40/40 40/40 40/40
Accessories
Partial Curb 385 385 385
Full Curb 545 545 545
FIGURE 2 - CENTER OF GRAVITY
1
1.
Refer to Tables 5 and 6 for A, B, C, D and X and Y data
respectively
All panels must be secured in place when the unit
is lifted.
The condenser coils should be protected from
damage by the rigging cables with plywood or
other suitable material.
An adhesive backed cover is provided over the
outside of the combustion air inlet opening on gas
fired units to prevent moisture from entering the
unit which could cause damage to electrical com-
ponents. Allow this closure label to remain in place
until the combustion air hood is to be installed
(Refer to Figures 7, 8, & 9).