Specifications
Table Of Contents
- Form 150.72-NM1 (908)
- GENERAL SAFETY GUIDELINES
- CHANGEABILITY OF THIS DOCUMENT
- TABLE OF CONTENTS
- LIST OF FIGURES
- LIST OF TABLES
- SECTION 1 – GENERAL CHILLER INFORMATION & SAFETY
- SECTION 2 – PRODUCT DESCRIPTION
- INTRODUCTION
- GENERAL SYSTEM DESCRIPTION
- HIGH AMBIENT KIT
- BUILDING AUTOMATION SYSTEM INTERFACE
- MILLENIUM CONTROL CENTER
- POWER PANEL
- ACCESSORIES AND OPTIONS
- UNIT COMPONENTS
- CONTROL / POWER PANEL COMPONENTS
- PRODUCT IDENTIFICATION NUMBER (PIN)
- BASIC UNIT NOMENCLATURE
- REFRIGERANT FLOW DIAGRAM
- PROCESS AND INSTRUMENTATION DIAGRAM
- SECTION 3 – HANDLING AND STORAGE
- SECTION 4 – INSTALLATION
- INSTALLATION CHECKLIST
- HANDLING
- INSPECTION
- LOCATION AND CLEARANCES
- SPRING ISOLATORS (OPTIONAL)
- COMPRESSOR MOUNTING
- REMOTE COOLER OPTION
- CHILLED LIQUID PIPING
- PIPEWORK ARRANGEMENT
- DUCT WORK CONNECTION
- WIRING
- COMPRESSOR HEATERS
- RELIEF VALVES
- HIGH PRESSURE CUTOUT
- SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
- USER CONTROL WIRING INPUTS
- USER CONTROL WIRING OUTPUTS
- SECTION 5 – TECHNICAL DATA
- OPERATIONAL LIMITATIONS (ENGLISH)
- HEAT EXCHANGER FLOW, GPM
- PHYSICAL DATA (ENGLISH)
- ELECTRICAL DATA
- ELECTRICAL NOTES
- ELECTRICAL DATA W/O PUMPS
- ELECTRICAL DATA W/ PUMPS
- ELECTRICAL NOTES AND LEGEND
- WIRING DIAGRAMS
- DIMENSIONS (ENGLISH)
- TECHNICAL DATA – CLEARANCES
- WEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONS
- ISOLATOR INFORMATION FOR UNITS SHIPPED ON OR AFTER JUNE 15, 2008
- ISOLATOR INFORMATION FOR UNITS SHIPPED BEFORE JUNE 15, 2008
- SLRS Seismic Isolator Specifications
- SLRS Seismic Isolator Installation and Adjustment
- One Inch Deflection Spring Isolator Cross-reference
- Installation of 1” Deflection Mounts
- Neoprene Isolator Cross-reference
- Two Inch Deflection, Seismic Spring IsolatorCross-reference - SLRS
- SLRS Seismic Isolator Installation and Adjustment
- SECTION 6 – COMMISSIONING
- SECTION 7 – UNIT CONTROLS
- SECTION 8 – UNIT OPERATION
- CAPACITY CONTROL
- SUCTION PRESSURE LIMIT CONTROLS
- DISCHARGE PRESSURE LIMIT CONTROLS
- LEAVING CHILLED LIQUID CONTROL
- LEAVING CHILLED LIQUID CONTROLOVERRIDE TO REDUCE CYCLING
- LEAVING CHILLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- RETURN CHILLED LIQUID CONTROL
- RETURN CHILLLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- ANTI-RECYCLE TIMER
- ANTI-COINCIDENCE TIMER
- EVAPORATOR PUMP CONTROL & YORK HYDRO KIT PUMP CONTROL
- EVAPORATOR HEATER CONTROL
- PUMPDOWN CONTROL
- STANDARD CONDENSER FAN CONTROL
- LOAD LIMITING
- COMPRESSOR RUN STATUS
- ALARM STATUS
- REMOTE BAS/EMS TEMPERATURE RESET USINGA VOLTAGE OR CURRENT SIGNAL
- SECTION 9 – SERVICE AND TROUBLESHOOTING
- SECTION 10 – MAINTENANCE
JOHNSON CONTROLS
138
FORM 150.72-NM1 (908)
Unit Controls
Option 12 – Power Fail Restart:
Chiller auto restarts after a power failure.
After a power failure, the UNIT switch must be
toggled before restart at the unit is allowed.
NORMALLY MANUAL RESTART should NOT BE
SELECTED.
Option 13 – Soft Start Enable/Disable:
SOFT START “DISABLED” MUST be selected on all
chillers.
This message may not be viewable on non-European
chillers.
Option 14 – Unit Type:
The UNIT TYPE message cannot be modied under
the unit keys.
-
-
-
If unit type needs to be changed to make the unit
a liquid chiller, remove power and then remove
the jumper between J11-7 and J11-12 on the I/O
Board. Reapply power to the micropanel and the
microprocessor will store the change.
Option 15 – Refrigerant Type:
Refrigerant type R-410A must be selected under Service
Mode. Refrigerant type is displayed under the Options
Key, but is only programmable in Service Mode.
Do not select this option on R-410A chillers.
Option 10 – Manual Override Mode:
This option allows overriding of the daily schedule
that is programmed. MANUAL OVERRIDE MODE
– DISABLED indicates that override mode has no
effect.
or
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to
start when shut down on the daily schedule. It will
automatically be disabled after 30 minutes.
Option 11 – Current Feedback Options
Installed:
This mode should be selected when the panel is not
equipped with current sensing capability.
or
This mode should be selected when an optional
2ACE Module is installed to allow combined current
monitoring of all systems by sensing current on the
incoming line.
or
This mode should be selected when an optional
2ACE module is installed to allow individual current
monitoring of each system. SYS 1 input is to J7 of the
I/O. SYS 2 input is to J8 of the I/O.
C U R R E N T F E E D B A C K
N O N E
C U R R E N T F E E D B A C K
O N E P E R U N I T
C U R R E N T F E E D B A C K
O N E P E R S Y S T E M
M A N U A L O V E R R I D E M O D E
D I S A B L E D
M A N U A L O V E R R I D E M O D E
E N A B L E D
F A N C O N T R O L
A M B I E N T & D S C H P R E S S
U N I T T Y P E
L I Q U I D C H I L L E R
R E F R I G E R A N T T Y P E
R – 4 1 0 A
S O F T S T A R T
D I S A B L E D
P O W E R F A I L R E S T A R T
A U T O M A T I C
P O W E R F A I L R E S T A R T
M A N U A L