Specifications
Table Of Contents
- Form 150.72-NM1 (908)
- GENERAL SAFETY GUIDELINES
- CHANGEABILITY OF THIS DOCUMENT
- TABLE OF CONTENTS
- LIST OF FIGURES
- LIST OF TABLES
- SECTION 1 – GENERAL CHILLER INFORMATION & SAFETY
- SECTION 2 – PRODUCT DESCRIPTION
- INTRODUCTION
- GENERAL SYSTEM DESCRIPTION
- HIGH AMBIENT KIT
- BUILDING AUTOMATION SYSTEM INTERFACE
- MILLENIUM CONTROL CENTER
- POWER PANEL
- ACCESSORIES AND OPTIONS
- UNIT COMPONENTS
- CONTROL / POWER PANEL COMPONENTS
- PRODUCT IDENTIFICATION NUMBER (PIN)
- BASIC UNIT NOMENCLATURE
- REFRIGERANT FLOW DIAGRAM
- PROCESS AND INSTRUMENTATION DIAGRAM
- SECTION 3 – HANDLING AND STORAGE
- SECTION 4 – INSTALLATION
- INSTALLATION CHECKLIST
- HANDLING
- INSPECTION
- LOCATION AND CLEARANCES
- SPRING ISOLATORS (OPTIONAL)
- COMPRESSOR MOUNTING
- REMOTE COOLER OPTION
- CHILLED LIQUID PIPING
- PIPEWORK ARRANGEMENT
- DUCT WORK CONNECTION
- WIRING
- COMPRESSOR HEATERS
- RELIEF VALVES
- HIGH PRESSURE CUTOUT
- SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
- USER CONTROL WIRING INPUTS
- USER CONTROL WIRING OUTPUTS
- SECTION 5 – TECHNICAL DATA
- OPERATIONAL LIMITATIONS (ENGLISH)
- HEAT EXCHANGER FLOW, GPM
- PHYSICAL DATA (ENGLISH)
- ELECTRICAL DATA
- ELECTRICAL NOTES
- ELECTRICAL DATA W/O PUMPS
- ELECTRICAL DATA W/ PUMPS
- ELECTRICAL NOTES AND LEGEND
- WIRING DIAGRAMS
- DIMENSIONS (ENGLISH)
- TECHNICAL DATA – CLEARANCES
- WEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONS
- ISOLATOR INFORMATION FOR UNITS SHIPPED ON OR AFTER JUNE 15, 2008
- ISOLATOR INFORMATION FOR UNITS SHIPPED BEFORE JUNE 15, 2008
- SLRS Seismic Isolator Specifications
- SLRS Seismic Isolator Installation and Adjustment
- One Inch Deflection Spring Isolator Cross-reference
- Installation of 1” Deflection Mounts
- Neoprene Isolator Cross-reference
- Two Inch Deflection, Seismic Spring IsolatorCross-reference - SLRS
- SLRS Seismic Isolator Installation and Adjustment
- SECTION 6 – COMMISSIONING
- SECTION 7 – UNIT CONTROLS
- SECTION 8 – UNIT OPERATION
- CAPACITY CONTROL
- SUCTION PRESSURE LIMIT CONTROLS
- DISCHARGE PRESSURE LIMIT CONTROLS
- LEAVING CHILLED LIQUID CONTROL
- LEAVING CHILLED LIQUID CONTROLOVERRIDE TO REDUCE CYCLING
- LEAVING CHILLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- RETURN CHILLED LIQUID CONTROL
- RETURN CHILLLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- ANTI-RECYCLE TIMER
- ANTI-COINCIDENCE TIMER
- EVAPORATOR PUMP CONTROL & YORK HYDRO KIT PUMP CONTROL
- EVAPORATOR HEATER CONTROL
- PUMPDOWN CONTROL
- STANDARD CONDENSER FAN CONTROL
- LOAD LIMITING
- COMPRESSOR RUN STATUS
- ALARM STATUS
- REMOTE BAS/EMS TEMPERATURE RESET USINGA VOLTAGE OR CURRENT SIGNAL
- SECTION 9 – SERVICE AND TROUBLESHOOTING
- SECTION 10 – MAINTENANCE
FORM 150.72-NM1 (908)
155
JOHNSON CONTROLS
8
LOAD LIMITING
Load Limiting is a feature that prevents the unit from
loading beyond the desired value. 2 and 4 compressor
units can be load limited to 50%. This would allow only
1 compressor per system to run. 3 and 6 compressor units
can be load limited to 33% or 66%. The 66% limit would
allow up to 2 compressors per system to run, and the
33% limit would allow only 1 compressor per system
to run. Five-compressor units may be load limited to
40% (1 compressor per system runs) or 80% (up to 2
compressors per system) are permitted to run. No other
values of limiting are available.
There are two ways to load limit the unit. The rst is
through remote communication via an ISN. Load limit
stages are sent through YORK Talk on pages 9 and 10
of feature 54. Page 9 is stage 1 load limit and page 10
is stage 2 load limit.
A second stage of load limiting the unit is accomplished
by closing contacts connected to the Load Limit
(XTBC1 – terminals 13-21) and PWM inputs (XTBC1
– terminals 13-20). Stage 1 of load limiting involves
closing the Load Limit input. Stage 2 of load limiting
involves closing both the Load Limit and PWM inputs.
The rst stage of limiting is either 80%, 66% or 50%,
depending on the number of compressors on the unit.
The second stage of limiting is either 40% or 33% and
is only available on 3, 5 & 6 compressor units. Table
19 shows the load limiting permitted for the various
numbers of compressors.
-
COMPRESSOR RUN STATUS
Compressor run status is indicated by closure of contacts
at XTBC2 – terminals 25 to 26 for system 1 and XTBC2
– terminals 27 to 28 for system 2.
ALARM STATUS
System or unit shutdown is indicated by normally-open
alarm contacts opening whenever the unit shuts down on
a unit fault, locks out on a system fault, or experiences
a loss of power to the chiller electronics . System 1
alarm contacts are located at XTBC2 – terminals 29
to 30. System 2 alarm contacts are located at XTBC2
– terminals 31 to 32. The alarm contacts will close when
conditions allow the unit to operate, or the fault is reset
during a loss of power, the contacts will remain open
until power is reapplied and no fault conditions exist.
COMPRESSORS
IN UNIT
STAGE 1 STAGE 2
2 50% -
3 66% 33%
4 50% -
5 80% 40%
6 66% 33%
TABLE 19 – COMPRESSOR OPERATION –
LOAD LIMITING