Specifications

Table Of Contents
FORM 150.72-NM1 (908)
17
JOHNSON CONTROLS
2
UNIT ON/OFF switch
The microprocessor control center is capable of
displaying the following:
Return and leaving liquid temperature
Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
Outdoor air temperature
English or Metric data
Suction pressure cutout setting
Each system suction pressure
Discharge pressure (optional)
Liquid Temperature Reset via a Johnson Controls
ISN DDC or Building Automation System (by
others) via:
- a pulse width modulated (PWM) input as stan-
dard.
- a 4-20 milliamp or 0 -10 VDC input with the
optional B.A.S. interface option.
Anti-recycle timer status for each system
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system denition
Compressor starts & operating hours
(each compressor)
Status of hot gas valves, evaporator heater
and fan operation
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load & unload timer status
Water pump status
* Intensity of Protection European Standard
** International Electrotechnical Commission
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and two
steps of demand load limiting from an external building
automation system. Unit alarm contacts are standard.
The operating program is stored in non-volatile memory
battery backed RAM to eliminate chiller failure due to
AC powered failure/battery discharge. Programmed
setpoints are retained in lithium battery-backed RTC
memory for 5 years minimum.
HIGH AMBIENT KIT
Allows units to operate when the ambient temperature
is above 115°F (46°C). Includes sun shield panels and
discharge pressure transducers.
BUILDING AUTOMATION SYSTEM
INTERFACE
The Microprocessor Board can accept a 4-20 milliamp, 0-
10VDC or contact closure input to reset the leaving chiller
liquid temperature from a Building Automation System.
Only one of the following remote communications
options can be offered on a unit at a time: BAS Interface,
Remote Control Panel or Multi-unit Sequence Control.
(Factory Mounted)
- The standard unit capabilities include remote
start-stop, remote water temperature reset via a
PWM 4-20 milliamp or 0-10VDC input signal
or up to two stages of demand (load) limiting
depending on model.
- The standard control panel can be directly con-
nected to a Johnson Controls Building Automated
System.
POWER PANEL
Each panel contains:
Compressor power terminals
Compressor motor starting contactors per
l.E.C.**
Control power terminals to accept incoming for
115-1-60 control power
Fan contactors & overload current protection
The power wiring is routed through liquid-tight conduit
to the compressors and fans.