FIG. 6 – PROCESS AND INSTRUMENTATION DIAGRAM
PROCESS AND INSTRUMENTATION DIAGRAM
Low pressure liquid refrigerant enters the cooler and is
evaporated and superheated by the heat energy
absorbed from the chilled liquid passing through the
cooler shell. Low pressure vapour enters the
compressor where pressure and superheat are
increased. The high pressure vapour is fed to the air
cooled condenser coil and fans where the heat is
removed. The fully condensed and subcooled liquid
passes through the expansion valve where pressure is
reduced and further coo
ling takes place before
r
eturning to the cooler.
PS
ZCPR-1
ZCPR-2
ZCPR-3
DV
HPL
HPC
P
DV
LPC
P
Condenser
Fans Fans
-YLLSV
S
Chilled
Liquid
T
DV
CHT
LTC
Evaporator
Chilled
Liquid
See P.R.V.
Options
Compressors
Control Functions:
DV - Display Value
CHT - Chilled Liquid Temperature
HPC - High Pressure Cutout
LPC - Low Pressure Cutout
HPL - High Pressure Load Limiting
LTC - Low Temperature Cutout
Components:
Pressure Relief Valve
Service (Ball) Valve
Expansion Valve
Solenoid Valve
Sight Glass
Sensor Pressure
or Temperature
Service (Stop) Access Valv
e
Pressure Switch
Filter Drier
(Removable Core)
S
PS
T
Ambient Air Sensor
DV
HTC
LTC
585 PSIG
650 PSIG
450 PSIG
LD13139