Specifications
Table Of Contents
- Form 150.72-NM1 (908)
- GENERAL SAFETY GUIDELINES
- CHANGEABILITY OF THIS DOCUMENT
- TABLE OF CONTENTS
- LIST OF FIGURES
- LIST OF TABLES
- SECTION 1 – GENERAL CHILLER INFORMATION & SAFETY
- SECTION 2 – PRODUCT DESCRIPTION
- INTRODUCTION
- GENERAL SYSTEM DESCRIPTION
- HIGH AMBIENT KIT
- BUILDING AUTOMATION SYSTEM INTERFACE
- MILLENIUM CONTROL CENTER
- POWER PANEL
- ACCESSORIES AND OPTIONS
- UNIT COMPONENTS
- CONTROL / POWER PANEL COMPONENTS
- PRODUCT IDENTIFICATION NUMBER (PIN)
- BASIC UNIT NOMENCLATURE
- REFRIGERANT FLOW DIAGRAM
- PROCESS AND INSTRUMENTATION DIAGRAM
- SECTION 3 – HANDLING AND STORAGE
- SECTION 4 – INSTALLATION
- INSTALLATION CHECKLIST
- HANDLING
- INSPECTION
- LOCATION AND CLEARANCES
- SPRING ISOLATORS (OPTIONAL)
- COMPRESSOR MOUNTING
- REMOTE COOLER OPTION
- CHILLED LIQUID PIPING
- PIPEWORK ARRANGEMENT
- DUCT WORK CONNECTION
- WIRING
- COMPRESSOR HEATERS
- RELIEF VALVES
- HIGH PRESSURE CUTOUT
- SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
- USER CONTROL WIRING INPUTS
- USER CONTROL WIRING OUTPUTS
- SECTION 5 – TECHNICAL DATA
- OPERATIONAL LIMITATIONS (ENGLISH)
- HEAT EXCHANGER FLOW, GPM
- PHYSICAL DATA (ENGLISH)
- ELECTRICAL DATA
- ELECTRICAL NOTES
- ELECTRICAL DATA W/O PUMPS
- ELECTRICAL DATA W/ PUMPS
- ELECTRICAL NOTES AND LEGEND
- WIRING DIAGRAMS
- DIMENSIONS (ENGLISH)
- TECHNICAL DATA – CLEARANCES
- WEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONS
- ISOLATOR INFORMATION FOR UNITS SHIPPED ON OR AFTER JUNE 15, 2008
- ISOLATOR INFORMATION FOR UNITS SHIPPED BEFORE JUNE 15, 2008
- SLRS Seismic Isolator Specifications
- SLRS Seismic Isolator Installation and Adjustment
- One Inch Deflection Spring Isolator Cross-reference
- Installation of 1” Deflection Mounts
- Neoprene Isolator Cross-reference
- Two Inch Deflection, Seismic Spring IsolatorCross-reference - SLRS
- SLRS Seismic Isolator Installation and Adjustment
- SECTION 6 – COMMISSIONING
- SECTION 7 – UNIT CONTROLS
- SECTION 8 – UNIT OPERATION
- CAPACITY CONTROL
- SUCTION PRESSURE LIMIT CONTROLS
- DISCHARGE PRESSURE LIMIT CONTROLS
- LEAVING CHILLED LIQUID CONTROL
- LEAVING CHILLED LIQUID CONTROLOVERRIDE TO REDUCE CYCLING
- LEAVING CHILLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- RETURN CHILLED LIQUID CONTROL
- RETURN CHILLLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- ANTI-RECYCLE TIMER
- ANTI-COINCIDENCE TIMER
- EVAPORATOR PUMP CONTROL & YORK HYDRO KIT PUMP CONTROL
- EVAPORATOR HEATER CONTROL
- PUMPDOWN CONTROL
- STANDARD CONDENSER FAN CONTROL
- LOAD LIMITING
- COMPRESSOR RUN STATUS
- ALARM STATUS
- REMOTE BAS/EMS TEMPERATURE RESET USINGA VOLTAGE OR CURRENT SIGNAL
- SECTION 9 – SERVICE AND TROUBLESHOOTING
- SECTION 10 – MAINTENANCE
FORM 150.72-NM1 (908)
35
JOHNSON CONTROLS
4
Ground Level Locations
It is important that the units be installed on a substantial
base that will not settle. A one piece concrete slab
with footers extended below the frost line is highly
recommended. Additionally, the slab should not be
tied to the main building foundations as noise and
vibration may be transmitted. Mounting holes (5/8”
dia.) are provided in the steel channel for bolting the
unit to its foundation (see DIMENSIONS).
For ground level installations, precautions should be
taken to protect the unit from tampering by or injury to
unauthorized persons. Screws and/or latches on access
panels will prevent casual tampering. However, further
safety precautions such as a fenced-in enclosure or
locking devices on the panels may be advisable.
Rooftop Locations
Choose a spot with adequate structural strength to
safely support the entire weight of the unit and service
personnel. Care must be taken not to damage the roof.
Consult the building contractor or architect if the roof
is bonded. Roof installations should have wooden
beams (treated to reduce deterioration), cork, rubber,
or vibration isolators under the base to minimize
vibration.
Noise Sensitive Locations
Efforts should be made to assure that the chiller is not
located next to occupied spaces or noise sensitive areas
where chiller noise level would be a problem. Chiller
noise is a result of compressor and fan operation.
Considerations should be made utilizing noise levels
published in the YORK Engineering Guide for
the specific chiller model. Sound blankets for the
compressors and low sound fans are available.
SPRING ISOLATORS (OPTIONAL)
When ordered, four (4) isolators will be furnished.
Identify the isolator, locate at the proper mounting point,
and adjust per instructions.
COMPRESSOR MOUNTING
The compressors are mounted on four (4) rubber
isolators. The mounting bolts should not be loosened
or adjusted at installation of the chiller.
REMOTE COOLER OPTION
Not available at this time.
CHILLED LIQUID PIPING
General – When the unit(s) has been located in its
nal position, the unit water piping may be connected.
Normal installation precautions should be observed in
order to receive maximum operating efciencies. Piping
should be kept free of all foreign matter. All chilled water
evaporator piping must comply in all respects with local
plumbing codes and ordinances.
Since elbows, tees and valves decrease pump capacity,
all piping should be kept as straight and as simple as
possible. All piping must be supported independent
of the chiller.
-
-
Hand stop valves should be installed in all lines to
facilitate servicing.
Piping to the inlet and outlet connections of the chiller
should include high-pressure rubber hose or piping
loops to ensure against transmission of water pump
vibration. The necessary components must be obtained
in the eld.