Technical Data
OPERATIONAL LIMITATIONS (ENGLISH)
VOLTAGE LIMITATIONS
The following voltage limitations are absolute and operation beyond these limitations may cause serious damage
to the compressor.


TABLE 2 – VOLTAGE LIMITATIONS
UNIT POWER MIN. MAX.
200-3-60 180 220
230-3-60 207 253
380-3-60 355 415
460-3-60 414 506
575-3-60 517 633
SECTION 5 – TECHNICAL DATA
TABLE 1 – TEMPERATURES AND FLOWS
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls Ofce for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Johnson Controls Ofce for application guidelines. 3. The evaporator
is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
3. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (for YLAA0014 0080 models
only).
4. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
Nominal Evaporator Water Flow
Unit Designation
Temperature (°F) Water Flow (gpm) Air On Condenser (°F)
MIN MAX MIN MAX MIN MAX
YLAA0070SE
40 55 60 285 0 125
YLAA0080SE
40 55 100 355 0 125
YLAA0090SE
40 55 140 625 0 125
YLAA0100SE
40 55 100 385 0 125
YLAA0115SE
40 55 100 385 0 125
YLAA0120SE
40 55 150 625 0 125
YLAA0135SE
40 55 120 625 0 125
YLAA0150SE
40 55 120 625 0 125
YLAA0155SE
40 55 150 625 0 125
YLAA0170SE
40 55 120 625 0 125
High Efciency
YLAA0091HE
40 55 100 385 0 125
YLAA0101HE
40 55 100 385 0 125
YLAA0125HE
40 55 100 385 0 125
YLAA0141HE
40 55 150 625 0 125
YLAA0156HE
40 55 120 625 0 125
YLAA0175HE
40 55 180 650 0 125