Specifications
Table Of Contents
- Form 150.72-NM1 (908)
- GENERAL SAFETY GUIDELINES
- CHANGEABILITY OF THIS DOCUMENT
- TABLE OF CONTENTS
- LIST OF FIGURES
- LIST OF TABLES
- SECTION 1 – GENERAL CHILLER INFORMATION & SAFETY
- SECTION 2 – PRODUCT DESCRIPTION
- INTRODUCTION
- GENERAL SYSTEM DESCRIPTION
- HIGH AMBIENT KIT
- BUILDING AUTOMATION SYSTEM INTERFACE
- MILLENIUM CONTROL CENTER
- POWER PANEL
- ACCESSORIES AND OPTIONS
- UNIT COMPONENTS
- CONTROL / POWER PANEL COMPONENTS
- PRODUCT IDENTIFICATION NUMBER (PIN)
- BASIC UNIT NOMENCLATURE
- REFRIGERANT FLOW DIAGRAM
- PROCESS AND INSTRUMENTATION DIAGRAM
- SECTION 3 – HANDLING AND STORAGE
- SECTION 4 – INSTALLATION
- INSTALLATION CHECKLIST
- HANDLING
- INSPECTION
- LOCATION AND CLEARANCES
- SPRING ISOLATORS (OPTIONAL)
- COMPRESSOR MOUNTING
- REMOTE COOLER OPTION
- CHILLED LIQUID PIPING
- PIPEWORK ARRANGEMENT
- DUCT WORK CONNECTION
- WIRING
- COMPRESSOR HEATERS
- RELIEF VALVES
- HIGH PRESSURE CUTOUT
- SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
- USER CONTROL WIRING INPUTS
- USER CONTROL WIRING OUTPUTS
- SECTION 5 – TECHNICAL DATA
- OPERATIONAL LIMITATIONS (ENGLISH)
- HEAT EXCHANGER FLOW, GPM
- PHYSICAL DATA (ENGLISH)
- ELECTRICAL DATA
- ELECTRICAL NOTES
- ELECTRICAL DATA W/O PUMPS
- ELECTRICAL DATA W/ PUMPS
- ELECTRICAL NOTES AND LEGEND
- WIRING DIAGRAMS
- DIMENSIONS (ENGLISH)
- TECHNICAL DATA – CLEARANCES
- WEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONS
- ISOLATOR INFORMATION FOR UNITS SHIPPED ON OR AFTER JUNE 15, 2008
- ISOLATOR INFORMATION FOR UNITS SHIPPED BEFORE JUNE 15, 2008
- SLRS Seismic Isolator Specifications
- SLRS Seismic Isolator Installation and Adjustment
- One Inch Deflection Spring Isolator Cross-reference
- Installation of 1” Deflection Mounts
- Neoprene Isolator Cross-reference
- Two Inch Deflection, Seismic Spring IsolatorCross-reference - SLRS
- SLRS Seismic Isolator Installation and Adjustment
- SECTION 6 – COMMISSIONING
- SECTION 7 – UNIT CONTROLS
- SECTION 8 – UNIT OPERATION
- CAPACITY CONTROL
- SUCTION PRESSURE LIMIT CONTROLS
- DISCHARGE PRESSURE LIMIT CONTROLS
- LEAVING CHILLED LIQUID CONTROL
- LEAVING CHILLED LIQUID CONTROLOVERRIDE TO REDUCE CYCLING
- LEAVING CHILLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- RETURN CHILLED LIQUID CONTROL
- RETURN CHILLLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING
- ANTI-RECYCLE TIMER
- ANTI-COINCIDENCE TIMER
- EVAPORATOR PUMP CONTROL & YORK HYDRO KIT PUMP CONTROL
- EVAPORATOR HEATER CONTROL
- PUMPDOWN CONTROL
- STANDARD CONDENSER FAN CONTROL
- LOAD LIMITING
- COMPRESSOR RUN STATUS
- ALARM STATUS
- REMOTE BAS/EMS TEMPERATURE RESET USINGA VOLTAGE OR CURRENT SIGNAL
- SECTION 9 – SERVICE AND TROUBLESHOOTING
- SECTION 10 – MAINTENANCE
FORM 150.72-NM1 (908)
59
JOHNSON CONTROLS
55
CHILLER
MODEL
VOLT
PUMP
MODEL
PUMP
FLA
MINIMUM
CIRCUIT
AMPS
MIN N/F DISC SW
MIN DUAL
ELEM FUSE
& MIN CB
MAX DUAL
ELEM FUSE
& MAX CB
SYSTEM # 1 SYSTEM # 2
RATING SIZE LUG
COMPR 1 COMPR 2 COMPR 3 COND FANS COMPR 1 COMPR 2 COMPR 3 COND FANS
RLA LRA RLA LRA RLA LRA
QTY FLA LRA
RLA LRA RLA LRA RLA LRA
QTY FLA LRA
YLAA0101
HE
208
B, F
21.4 481 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.6 30.9 109.6 599 109.6 599 4 7.6 30.9
230 20.4 479 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.4 37.0 109.6 599 109.6 599 4 7.4 37.0
380 12.0 303 400 S5-400 S5: (2) 3/0 - 250kcmil 350 350 36.0 239 36.0 239 36.0 239 2 4.5 22.3 69.2 358 69.2 358 4 4.5 22.3
460 10.2 238 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 26.9 187 26.9 187 26.9 187 2 4.0 19.0 54.5 310 54.5 310 4 4.0 19.0
575 8.2 208 250 S4-250 S4: 6AWG - 350kcmil 225 250 23.7 148 23.7 148 23.7 148 2 2.9 14.6 49.4 239 49.4 239 4 2.9 14.6
YLAA0101
HE
208
D, O
41.7 501 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.6 30.9 109.6 599 109.6 599 4 7.6 30.9
230 36.3 495 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.4 37.0 109.6 599 109.6 599 4 7.4 37.0
380 22.0 313 400 S5-400 S5: (2) 3/0 - 250kcmil 350 350 36.0 239 36.0 239 36.0 239 2 4.5 22.3 69.2 358 69.2 358 4 4.5 22.3
460 18.2 246 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 26.9 187 26.9 187 26.9 187 2 4.0 19.0 54.5 310 54.5 310 4 4.0 19.0
575 14.5 214 250 S4-250 S4: 6AWG - 350kcmil 250 250 23.7 148 23.7 148 23.7 148 2 2.9 14.6 49.4 239 49.4 239 4 2.9 14.6
YLAA0101
HE
208
E, P
54.7 514 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.6 30.9 109.6 599 109.6 599 4 7.6 30.9
230 49.5 508 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.4 37.0 109.6 599 109.6 599 4 7.4 37.0
380 29.1 320 400 S5-400 S5: (2) 3/0 - 250kcmil 350 350 36.0 239 36.0 239 36.0 239 2 4.5 22.3 69.2 358 69.2 358 4 4.5 22.3
460 24.8 252 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 26.9 187 26.9 187 26.9 187 2 4.0 19.0 54.5 310 54.5 310 4 4.0 19.0
575 19.8 219 250 S4-250 S4: 6AWG - 350kcmil 250
250 23.7 148 23.7 148 23.7 148 2 2.9 14.6 49.4 239 49.4 239 4 2.9 14.6
YLAA0101
HE
208
K
15.4 475 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.6 30.9 109.6 599 109.6 599 4 7.6 30.9
230 13.9 472 600 S6-600 S6: (2) 250kcmil - 500kcmil 500 500 55.8 425 55.8 425 55.8 425 2 7.4 37.0 109.6 599 109.6 599 4 7.4 37.0
380 8.1 299 400 S5-400 S5: (2) 3/0 - 250kcmil 350 350 36.0 239 36.0 239 36.0 239 2 4.5 22.3 69.2 358 69.2 358 4 4.5 22.3
460 7.0 234 400 S5-400 S5: (2) 3/0 - 250kcmil 250 250 26.9 187 26.9 187 26.9 187 2 4.0 19.0 54.5 310 54.5 310 4 4.0 19.0
575 5.6 205 250 S4-250 S4: 6A
WG - 350kcmil 225 250 23.7 148 23.7 148 23.7 148 2 2.9 14.6 49.4 239 49.4 239 4 2.9 14.6
YLAA0101
HE
208
L
27.1 487 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.6 30.9 109.6 599 109.6 599 4 7.6 30.9
230 24.5 483 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 55.8 425 55.8 425 55.8 425 2 7.4 37.0 109.6 599 109.6 599 4 7.4 37.0
380 14.8 306 400 S5-400 S5: (2) 3/0 - 250kcmil 350 350 36.0 239 36.0 239 36.0 239 2 4.5 22.3 69.2 358 69.2 358 4 4.5 22.3
460 12.3 240 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 26.9 187 26.9 187 26.9 187 2 4.0 19.0 54.5 310 54.5 310 4 4.0 19.0
575 9.8 209 250 S4-250 S4: 6AWG - 350kcmil 225 250 23.7 148 23.7 148 23.7 148 2 2.9 14.6 49.4 239 49.4 239 4 2.9 14.6
YLAA0115
YLAA0120
SE
208
F
21.4 533 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 109.6 599 109.6 599 3 7.6 30.9 109.6 599 109.6 599 3 7.6 30.9
230 20.4 531 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 109.6 599 109.6 599 3 7.4 37.0 109.6 599 109.6 599 3 7.4 37.0
380 12.0 333 400 S5-400 S5: (2) 3/0 - 250kcmil 400 400 69.2 358 69.2 358 3 4.5 22.3 69.2 358 69.2 358 3 4.5 22.3
460 10.2 266 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 54.5 310 54.5 310 3 4.0 19.0 54.5 310 54.5 310 3 4.0 19.0
575 8.2 236 400 S5-400 S5: (2) 3/0 - 250kcmil 250 250 49.4 239 49.4 239 3 2.9 14.6 49.4 239 49.4 239 3 2.9 14.6
YLAA0115
YLAA0120
SE
208
C
32.2 544 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 109.6 599 109.6 599 3 7.6 30.9 109.6 599 109.6 599
3 7.6 30.9
230 28.4 539 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 109.6 599 109.6 599 3 7.4 37.0 109.6 599 109.6 599 3 7.4 37.0
380 15.4 337 400 S5-400 S5: (2) 3/0 - 250kcmil 400 400 69.2 358 69.2 358 3 4.5 22.3 69.2 358 69.2 358 3 4.5 22.3
460 14.2 270 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 54.5 310 54.5 310 3 4.0 19.0 54.5 310 54.5 310 3 4.0 19.0
575 11.4 239 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 49.4 239 49.4 239 3 2.9 14.6 49.4 239 49.4 239 3 2.9 14.6
YLAA0115
YLAA0120
SE
208
D, M, N
41.7 553 800 S6-800 S6: (3) 2/0 - 4000kcmil 600 600 109.6 599 109.6 599 3 7.6 30.9 109.6 599 109.6 599 3 7.6 30.9
230 36.3 547 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 109.6 599 109.6 599 3 7.4 37.0 109.6 599 109.6 599 3 7.4 37.0
380 22.0 343 400 S5-400 S5: (2) 3/0 - 250kcmil 400 400 69.2 358 69.2 358 3 4.5 22.3 69.2 358 69.2 358 3 4.5 22.3
460 18.2 274 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 54.5 310 54.5 310 3 4.0 19.0 54.5 310 54.5 310 3 4.0 19.0
575 14.5 242 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 49.4 239 49.4 239 3 2.9 14.6 49.4 239 49.4 239 3 2.9 14.6
YLAA0115
YLAA0120
SE
208
E, P
54.7 566 800 S6-800 S6: (3) 2/0 - 4000kcmil 600 600 109.6 599 109.6 599 3 7.6 30.9 109.6 599 109.6 599 3 7.6 30.9
230 49.5 560 800 S6-800 S6: (3) 2/0 - 4000kcmil 600 600 109.6 599 109.6 599 3 7.4 37.0 109.6 599 109.6 599 3 7.4 37.0
380 29.1 350 400 S5-400 S5: (2) 3/0 - 250kcmil 400 400 69.2 358 69.2 358 3 4.5 22.3 69.2 358 69.2 358 3 4.5 22.3
460 24.8 280 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 54.5 310 54.5 310 3 4.0 19.0 54.5 310 54.5 310 3 4.0 19.0
575 19.8 247 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 49.4 239 49.4 239 3 2.9 14.6 49.4 239 49.4 239 3 2.9 14.6
YLAA0115
YLAA0120
SE
208
K
15.4 527 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 109.6 599 109.6 599 3 7.6 30.9 109.6 599 109.6 599 3 7.6 30.9
230 13.9 524 600 S6-600 S6: (2) 250kcmil - 500kcmil 600 600 109.6 599 109.6 599 3 7.4 37.0 109.6 599 109.6 599 3 7.4 37.0
380 8.1 329 400 S5-400 S5: (2) 3/0 - 250kcmil 350 350 69.2 358 69.2 358 3 4.5 22.3 69.2 358 69.2 358 3 4.5 22.3
460 7.0 263 400 S5-400 S5: (2) 3/0 - 250kcmil 300 300 54.5 310 54.5
310 3 4.0 19.0 54.5 310 54.5 310 3 4.0 19.0