FORM 150.72-NM1 (908)
85
JOHNSON CONTROLS
55
DIMENSIONS – YLAA0135 - 0155 (ENGLISH)
Water connection sizes are shown
in Physical Data (Table 4).
F
W
P
D
C1 C2
R2
R1
H
L
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall 6'; control panel to end wall – 4'0''; top
– no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
YLAA Models L (length) W (width) H (height) F P D C1 C2 R4 R3 R2 R1
YLAA0135SE
187.5 88.25 94.2 88.5 42.75 16.25 19.6 83 NA 58 66 39
YLAA0141HE
187.5 88.25 94.2 88.5 42.75 17.25 22.13 102 NA 58 66 39
YLAA0150SE
187.5 88.25 94.2 88.5 42.75 16.25 19.6 83 NA 58 66 39
YLAA0155SE
187.5 88.25 94.2 88.5 42.75 17.25 22 102 NA 58 66 39