Installation & Owner’s Manual MINISPLIT HIGH WALL MODELS RMHC 18-30 AIR CONDITIONER The units comply with one or more of the following marks - see unit for details. J287-EN.indd 1 EN 035M80159-000 07.03.
CONTENTS Safety Precautions ................................................... 3 Part Names ................................................................ 4 Manual Operation ..................................................... 5 How the Air Conditioner Works............................... 5 Optimal Operation .................................................... 6 Preparation Before Installation ............................... 6 Installation Procedure ..............................................
REQUIRED TOOLS Screw driver Hexagonal wrench Torque wrench Spanner Reamer Hole core drill Tape measure Thermometer 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. EXTENDED PARTS Manifold Guage Gas leak detector Vacuum pump Pipe clamp Pipe Cutter Flare Tool Set Electrical Circuit tester 1. Refrigerant Pipe Models 18 21 27 Liquid size (inch) Gas size (inch) 30 1/4 1/4 1/4 1/4 3/8 3/8 and 1/2 3/8 3/8 and 1/2 2. Pipe Insulation Material (Polyethylene foam 9 mm thick) 3. Vinyl tape 4.
PART NAMES INDOOR UNIT ■ INDOOR & OUTDOOR UNIT 1 2 3 4 5 6 7 8 Front panel Air inlet Air filter 9 Air outlet 0 Horizontal air flow grille Vertical air flow louver = Display panel ~ Remote controller signal receiver Remote controller Manual control button Connecting pipe, drain hose Air inlet (side and rear) Air outlet ■ DISPLAY PANEL 1 AUTO indicator 2 OUTDOOR UNIT 3 4 5 This indicator illuminates when the air conditioner is in AUTO operation.
MANUAL OPERATION Manual operation can be used temporarily in case you can not find the remote controller or its batteries are exhausted. 1 Open and lift the front panel up to an angle at which it remains fixed with a clicking sound. 2 Press the button until the AUTO indicator is lit, the unit will work in forced AUTO mode. 3 Close the panel firmly to its original position. Panel CAUTIONS • • • • Once you push the manual button, the operation mode is shifted in an order as: AUTO, COOL, OFF.
OPTIMAL OPERATION To achieve optimal performance, please note the following: • Adjust the air flow direction correctly so that it is not directed on people. • Adjust the temperature to achieve the highest comfort level. Do not adjust the unit to excessive temperature levels. • Close doors and windows on COOL or HEAT modes, or performance may be reduced. • Use TIMER ON button on the remote controller to select a time you want to start your air conditioner.
OUTDOOR UNIT PICTURES Model 18-21 Model 27-30 345 820 830 655 625 330 320 895 350 920 370 355 90 680 583 PARTS INSTALLATION Model 18-21 Number Model 18-21 Name of part Q’ty 1 Installation plate 2x1 2 Self-tapping screw ST3.9x25 2x8 3 Plastic Expansion Pipe 2x8 4 Connection Liquid side Pipe Ass. Gas side 5 Remote controller 2x1 6 Mounting screw ST2.9x10 2x2 7 Remote controller holder 2x1 8 Seal 2x1 9 Drain elbow 1x1 ø 6.35 ø 9.53 / ø 12.
Model 27-30 Model 27-30 2 INDOOR UNIT Mounting screw A ST3.9x25-C-H 3 Clip anchor Number 1 2 3 4 5 6 7 8 9 10 4.3cm 1 Installtion plate >12c m B Unit >17 cm Air filter 5 Mounting screw B ST2.9x10-C-H 6 Remote controller holder 4 2 Mounting screw A ST3.9x25-C-H 3 Clip anchor Remote controller 4.3cm 1 >12c m or Installtion plate more A2 Unit >17 Air filter Mounting screw B ST2.9x10-C-H 6 4 2 Remote controller holder ST3.9x25-C-H 3 Clip anchor 4.
INSTALLATION PROCEDURE INDOOR UNIT ■ Fixing • • Place the installation guide pattern on the designated installation place and mark the hole position. Drill a hole and mount installation plate. • Make 6 mm 4-6 holes, in the wall at the four corners of mounting plate (bracket) then insert appropriate mounting devices. • Install the mounting plate using 4-6 pieces of mounting screw securely at four corners and tighten the screw completely. Do not over tighten the screws and deform the back plate.
■ Drain hose • Drain hose is flexible and can be routed to suit various piping arrangements. The drain line must include elbow trap (U bend). Connect a plastic condensate pipe with an internal diameter of 12 mm. For right connection Drain hose Drain cap Verification of condensate water drainage: Note: Do not put the drain hose end into water. • Fill the drain pan with water and observe evacuation. The drain hose can be connected to the left or the right side.
OUTDOOR UNIT ■ Fixing and Piping • • • • • • • Piping must be performed by qualified personnel according to good refrigeration systems practices. Piping materials and insulation materials must be of refrigerant quality. Select the pipe diameters according to the size of unit and cut the pipe to design length by using pipe cutter. Install the flare nuts and flare the end of the pipes. Check that no foreign bodies are inside the piping. Align the central of the connecting pipes and tighten the flare nut.
COLD AREA RECOMMENDATION - Outdoor heat pump unit : install the unit at least 10 cm above ground level to facilitate drainage of defrost water and prevent accumulation of ice. In effect, defrost water can cause accumulation of ice under the unit during subfreezing outdoor temperatures. - In areas with heavy snowfall, it is best to install the unit on wall supports.
■ Electrical Connections All electrical wiring and connections must comply with local codes and standards. Power supply cord and interconnection cord used must not be lighter than Polychloroprene sheeted cord (245 IEC 57 or H05RN-F). Disconnecting device must have a contact separation of at least 3 mm.
■ Electrical Work Model Power Source Power Switch and Fuse rating Wiring size 18 220-240V ~ 50Hz 4.6x2A 3x2.5mm2 21 220-240V ~ 50Hz 5+6A 3x2.5mm2 27 220-240V ~ 50Hz 4.6x3A 3x2.5mm2 30 220-240V ~ 50Hz 8.2+5.8A 3x2.5mm2 NOTE The supply voltage must be consistent with the rate voltage of the air conditioner. ■ Defrosting operation (Available for heating only). 1. Condition to start defrosting: Units will switch to defrosting mode when either of the following conditions is met.
MAINTENANCE WARNING Household Drain Cleaner It is necessary to stop the air conditioner and disconnect the power supply before cleaning. No ■ Cleaning the indoor unit and remote controller CAUTION Thinner • Use a dry cloth to wipe the indoor unit and remote controller. • A cloth dampened with cold water may be used on the indoor unit if it is very dirty. • The front panel of the indoor unit can be removed and cleaned with water. Then wipe it with a dry cloth.
OPERATION TIPS The following events may occur during normal operation. 1. Protection of the air conditioner. Compressor protection • The compressor cannot restart for 3 minutes after it stops. Anti-cold air (Cooling and heating models only) • The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following three situations and the set temperature has not been reached. A) When heating has just starting. B) Defrosting. C) Low temperature heating.
TROUBLE SHOOTING GUIDE Problem Probable cause Remedy A. The air conditioner does not run. 1. Power Failure. 2. Fuse blown or circuit breaker open. 3. Voltage is too low. 4. Faulty contactor or relay. 5. Electrical connections loose. 6. Thermostat adjustment too low (in heating mode) or too high (in cooling mode) 7. Faulty Capacitor 1. Wait for Power resume. 2. Replace the fuse or reset the breaker. 3. Find the cause and fix it. 4. Replace the faulty component. 5. Retighten the connection. 6.
TECHNICAL SPECIFICATION Technical Specifications : Multi Everest RMHC R410A - 50Hz Indoor Unit Models Outdoor Unit RMKC 18 21 18 21 V/Ph/Hz Power Supply 27 30 27 30 RMJC 220-240/1/50 Ph 1 1 1 1 Power Consumption CL kW 1800 2100 2900 2900 Power Consumption HP 2800 kW 1900 2150 2800 Running Current CL A 8.1 9.4 13 13 Running Current HP A 8.
DECLARATION OF CONFORMITY DECLARATION OF CONFORMITY Type of Equipment Brand Name Type Designation Air Conditioners YORK HAEA-HADA07/09/12FS, HAEB-HADB07/09/12FS, HAEC-HADC07/09/12FS, HAKA-HAJA07/09/12FS, HAKB-HAJB07/09/12FS, HAKC-HAJC07/09/12FS, HEEB-HEDB07/09/12/18/24/30FS, HEKB-HEJB07/09/12/18/21/24/30FS, HLEA-HLDA07/09/12/18/24FS, HLCA-HLHA24/28/FS, HMEA09MC/MD/ME, HMDA18MC, HMDA21MD, HMDA27ME, HMKB09MC/MD/ME/MF, HMKB12MD/MF, HMJB18MC, HMJB21MD, HMJB27ME, HMJB30MF, HRKB09AB/AG/AH, HRKB12AG, HRJB18AB, HR