Heating and Air Conditioning INSTALLATION MANUAL AFFINITY OUTDOOR SPLIT GEOTHERMAL HEAT PUMPS DUAL CAPACITY MODELS: YAST026 - 072 (2 THRU 6 NOMINAL TONS) Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york-geothermal.com Additional rating information can found at www.ahridirectory.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Table of Contents Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7 Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Model Nomenclature 1-3 4 4-6 8 9 10 11 12 13 14 15 16 17 YAS T 038 A A 1 3 A C B 0 A * Model YAS – Affinity Outdoor Split Vintage * - Factory Use Only Stage T – Dual Capacity Controls A – AuroraTM Base Control Unit Capacity 026, 038, 049, 064, 072 Future Options 0 – Standard Discharge Configuration A – None Flow Center A – None B – Flow Center Air Configuration A – None Water Coax Option C – Copper N – CuproN
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL General Installation Information Safety Considerations Duct System All blower coil units/air coils must be installed as specified by the manufacturer’s installation instructions; however, the following recommendations should considered to minimize noise and service problems. WARNING: Before performing service or maintenance operations on a system, turn off main power switches to both units.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL General Installation Information cont. When utilizing the existing air coil or line set, only flushing compounds that vaporize should be used; which means they are packaged in a pressurized disposable cylinder. It is preferable to use a flushing agent that removes oil, water, and acid, plus, is biodegradeable and non-toxic. The flushing agent should be safe to use with both HCFC and HFC refrigerants.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL General Installation Information cont. In add-on Outdoor Split applications, the coil should be located in the supply side of the furnace to avoid condensation damage to the furnace heat exchanger. A high temperature limit should be installed upstream of the coil to de-energize the compressor whenever the furnace is operating. Without this switch, the Outdoor Split will trip out on high pressure.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Water Quality In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Water Piping Residential split units are supplied standard with GeoLink swivel connections with P.T. ports. Flow Center Installation Flow centers FC1-GL or FC2-GL, as needed, may be internally mounted on the outdoor split, Two stub tubes with barbs are pre connected to the coax.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Electrical Connections General Accessory Relay Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Electrical Connections cont. Figure 14: Pump Wiring 208-230/60/1 Pump Power Wiring See Figure 14 for electrical connections from control box to pumps. FC1/FC2 style flow centers with fixed speed pumps connect to PB1 in the control box.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Electronic Thermostat Installation cont.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Electrical Data Rated Voltage Voltage Min/Max MCC RLA LRA LRA* Ext Loop FLA Total Unit FLA Min Circ Amp Max Fuse/ HACR 026 208-230/60/1 187/253 18.2 11.6 58.3 21.0 5.4 17.0 19.9 30 038 208-230/60/1 187/253 23.8 15.2 83.0 30.0 5.4 20.6 24.4 40 049 208-230/60/1 187/253 33.0 21.1 104.0 37.0 5.4 26.5 31.8 50 064 208-230/60/1 187/253 42.3 27.1 152.9 54.0 5.4 32.5 39.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Dimensional Data Cabinet Dimensions and Refrigerant Piping Connections B A C E D F G H L J K Model 026 thru 072 in [cm] A B C D E F G H I J K L M 36.0 [91.4] 23.9 [60.7] 26.7 [67.8] 9.3 [23.7] 7.1 [18.0] 9.0 [22.8] 5.6 [14.2] 8.2 [20.9] 10.7 [27.2] 18.9 [48.0] 8.7 [22.1] 14.8 [37.6] 7.0 [17.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Model Nomenclature - Air Handler 1-3 4-6 7 8-9 10 11 12 YAH 036 * 00 0 1 R Air Coil R – Refrigerant H - Hydronic Model YAH – Affinity Series Air Handler Unit Capacity Refrigeration (DX) Models with Nominal CFM 022 MBTUH 800 026 MBTUH 925 030 MBTUH 980 036 MBTUH 1225 042 MBTUH 1425 048 MBTUH 1625 060 MBTUH 1760 Hydronic Models with Nominal CFM 026 MBTUH 925 036 MBTUH 1225 048 MBTUH 1625 060 MBTUH 1760 Motor 1 – ECM 208-230/60/1
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Physical Data - Air Handler Air Handler Model Number (Refrigerant) 2 YAH022 YAH026 YAH030 2 Air Coil Total Face Area - ft [m ] YAH042 YAH048 YAH060 5.83 [0.54] Tube Outside Diameter - in [mm] Evaporator Coil YAH036 3/8 [9.52] Number of Rows 2 3 Fins Per Inch 12 Suction Line Connection - in [mm] Sweat 5/8 [15.87] 7/8 [22.22] Liquid Line Connection - in [mm] Sweat 3/8 [9.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora™ Control System Aurora ‘Base’ Control The Aurora ‘Base’ Control (ABC) System is a complete residential and commercial comfort system that brings all aspects of the HVAC system into one cohesive module network. The ABC features microprocessor control and HP, LP, condensate and freeze detection, over/ under voltage faults, along with communicating thermostat capability for complete fault detection text at the thermostat.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora Control System cont. Aurora ‘Base’ Control Reset Configuration Mode The control is placed in reset configuration mode by holding the push button switch SW1 for 50 to 60 seconds. This will reset all configuration settings and the EEPROM back to the factory default settings. LED3 (green) will turn off when entering reset configuration mode. Once LED3 (green) turns off, release SW1 and the control will reset.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Safety Features Over/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the range of 18 VAC to 30 VAC. If the over/under voltage shutdown lasts for 15 minutes, the lockout and alarm relay will be energized. Over/under voltage shutdown is self-resetting in that if the voltage comes back within range of 18 VAC to 30 VAC for at least 0.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Blower (G) - The blower will start immediately upon receiving a thermostat G command. If there are no other commands from the thermostat the ECM will run on “G” speed until the G command is removed. Regardless of blower input (G) from the thermostat, the blower will remain on for 30 seconds at the end of each heating, cooling, and emergency heat cycle.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Reference Calculations Heating Calculations: LWT = EWT - Cooling Calculations: HE GPM x 500 LAT = EAT + LWT = EWT + HC CFM x 1.08 HR GPM x 500 LAT (DB) = EAT (DB) - SC CFM x 1.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics Dual Capacity Split - 208-230/60/1 Flow Center Ext Pump 1/2 hp Total 208-230/60/1 Pump Pump G PB1 Yellow(8) 11 Gray(9) 2 Compressor 1 2 Blue Note 1 S C R Cap Green(17) Violet(6) Ground Lug G Red Tan(16) Black 5A Violet(7) Circuit Breaker Unit Power Supply Black(2) T2 208-230/60/1 5A G Circuit Breaker T1 CC L2 Black L1 Crankcase Heater Black(1) Black Black(3) 2 RP 4 5 FP Red(11) Red(12)
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics cont. Dual Capacity Split - 208-230/60/1 cont.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics cont.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics cont. Dual Capacity Split with GeoStart - 208-230/60/1 cont.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Refrigeration If an air handler manufactured by others is used then refrigerant should be added to the Affinity Split factory pre-charge. Refrigerant should be added for liquid line length. This should result in a slightly under-charged system exhibiting low subcooling and high superheat. As charge is added, the subcooling should rise and the superheat should fall.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Refrigeration cont. Determining Subcooling 1. 2. 3. 4. Measure the temperature of the liquid line on the small refrigerant line (liquid line) just outside the split cabinet. This location will be adequate for measurement in both modes unless a significant temperature drop in the liquid line is anticipated. Measure the liquid line pressure by attaching refrigerant gauges to the schrader connection on the liquid line service valve.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Pressure/Temperature Conversion Chart for R-410A PRESSURE (PSIG) 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150 152 154 156 158 160 162 164 166 168 170 172 174 176 178 TEMP °F 8.5 9.9 11.2 12.5 13.8 15.1 16.3 17.5 18.7 19.8 21.0 22.1 23.2 24.3 25.4 26.5 27.5 28.6 29.6 30.6 31.6 32.6 33.5 34.5 35.4 36.4 37.3 38.2 39.1 40.0 40.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Unit Startup 11. First stage heating will energize after a time delay. 12. Check the temperature of both the supply and discharge water (see the Unit Operating Parameters tables). 13. Check for an air temperature rise of 12°F to 35°F across the air coil, depending on the fan speed and entering water temperature. 14. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Operating Parameters First Stage Operation Entering Water Temp °F 50 70 90 Entering Water Temp °F 30 50 70 Water Flow GPM/Ton 1.5 YAST026 thru YAST064 Suction Discharge Pressure Pressure PSIG PSIG 130-150 193-230 Cooling -- No Desuperheater YAST072 Suction Discharge Pressure Pressure PSIG PSIG 130-150 200-245 YAST026 thru YAST072 Superheat Subcooling Water Temp Rise °F Air Temp Drop °F DB 18-24 8-16 7-14 15-21 3.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Pressure Drop Compressor Resistance Dual Capacity Compressor Resistance Chart (Ohms) Model 026 full load 026 part load 038 full load 038 part load 049 full load 049 part load 064 full load 064 part load 072 full load 072 part load GPM 4 6 8 10 3 5 7 9 5 7 9 11 4 6 8 10 6 9 12 15 5 8 11 14 8 12 16 20 6 10 14 18 12 15 18 21 10 13 16 19 30°F 1.4 2.8 4.7 7.0 0.8 2.0 3.6 5.8 1.2 2.2 3.4 4.9 0.9 1.7 2.8 4.2 1.2 2.4 3.9 5.7 0.9 2.0 3.4 5.0 1.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Refrigerant Circuit Guideline Symptom Under Charged System (Possible Leak) Over Charged System Low Air Flow Heating Low Air Flow Cooling Low Water Flow Heating Low Water Flow Cooling High Air Flow Heating High Air Flow Cooling High Water Flow Heating High Water Flow Cooling Low Indoor Air Temperature Heating Low Indoor Air Temperature Cooling High Indoor Air Temperature Heating High Indoor Air Temperature Cooling Restricted TXV (Check Service
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Troubleshooting Aurora Control System Refrigerant Systems NOTE: Refer to the Aurora Base Control Application and Troubleshooting Guide and the Instruction Guide: Aurora Interface and Diagnostics (AID) Tool for additional information. To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Startup and Troubleshooting Heating Cycle Analysis Measure suction temperature here at TXV bulb in heating modes. Measure suction temperature here at TXV bulb in cooling modes.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Troubleshooting cont. Single Speed/Dual Capacity Startup/Troubleshooting Form 1. Job Information Model # Job Name: Serial # Install Date: 2. Flow Rate in gpm Loop: Open / Closed Hot Water Generator: Y / N SOURCE COAX HEATING LOAD COAX (Water-to-Water) COOLING HEATING COOLING WATER IN Pressure: a. psi a. psi a. psi a. psi WATER OUT Pressure: b. psi b. psi b. psi b. psi Pressure Drop: a - b c. psi c. psi c.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Preventive Maintenance Water Coil Maintenance Other Maintenance 1. Filters 2. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight. Keep the system under pressure at all times.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Service Parts List Dual Capacity Split Units Compressor Part Description 026 038 049 064 072 Compressor 34P640-01 34P641-01 34P642-01 34P643-01 34P644-01 Run Capacitor 16P002D19 16P002D20 16P002D18 Sound Jacket Power Harness 11P781-01 Crankcase Heater 19P535-09 19P535-07 Refrigeration Components Solenoid Harness Electrical Components Sensors & Safeties 19P535-08 11P782-02 Accumulator 36P509-02 Coax 62I594-01 36P5
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Revision Guide Pages: All Description: First Published 38 Date: By: 03 Sept 2013 DS
Product: Type: Size: Affinity Outdoor Split Series Geothermal Heat Pumps 2-6 Ton Dual Capacity Document Type: Part Number: Release Date: Installation Manual IM2504SK6 09/13 ©2013 The manufacturer has a policy of continual product research and development and reserves the right to change design and specifications without notice. York and Affinity are registered trademarks of Johnson Controls, Inc., and are used with permission.