Installation manual
27
Unit
Size
Air 
Handler
20 feet 40 feet 60 feet
Factory
Charge (oz.)
*Charge 
Amount with 
YAH Air
Handler (oz.)
Suction Liquid Suction Liquid Suction Liquid
026 YAH026 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 52 74
038 YAH036 3/4” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 86
049 YAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 115
064 YAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 112
072 YAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 104 132
4/16/10
NOTES:  * The “Charge Amount with YAH Air Handler” column is based on the charge amount for an YAH Air Handler +   
  Compressor Section Split.
  Additional charge will have to be added accordingly for line set length.
  After charge is added, adjustments can be made to get appropriate subcooling and superheat.
  Additional charge for R-410A is 0.50 oz. per ft. for 3/8 in. and 1.0 oz. per ft. for 1/2 in. tube.
Refrigeration cont.
Line Set Sizes
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL
Determining Subcooling
1.  Measure the temperature of the liquid line on the small 
refrigerant line (liquid line) just outside the split cabinet. 
This location will be adequate for measurement in both 
modes unless a significant temperature drop in the liquid 
line is anticipated. 
2.  Measure the liquid line pressure by attaching refrigerant gauges 
to the schrader connection on the liquid line service valve.
3.  Convert the pressure obtained in Step 2 to the saturation 
temperature by using the Pressure Temperature Conversion 
Chart for R-410A.
4.  Subtract the temperature in Step 1 from the temperature in 
Step 3. The difference will be the subcooling value for that 
unit. Refer to the Operating Parameters tables for subcooling 
ranges at specific enter water conditions.










