Installation manual
30
Refrigeration cont.
Line Set Sizes
AFFINITY INDOOR SPLIT SERIES INSTALLATION MANUAL
NOTES:  * The "Charge Amount with YAH Air Handler" column is based on the charge amount for a YAH Air Handler+Compressor Section/Split.
Additional charge will have to be added accordingly for line set length.
After Charge is added adjustments can be made to get appropriate subcooling and superheat.
Additional charge for R-410A is 0.50 oz. per ft. for 3/8 in. and 1.0 oz. per ft. for 1/2 in. tube.
Unit
Size
Air 
Handler
20 feet 40 feet 60 feet
Factory
Charge (oz.)
*Charge Amount 
with YAH Air 
Handler (oz.)
Suction Liquid Suction Liquid Suction Liquid
022 YAH022 5/8” OD 3/8” OD 5/8” OD 3/8” OD 3/4” OD 3/8” OD 56 78
030 YAH030 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 3/8” OD 56 78
036 YAH036 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 86
042 YAH042 3/4” OD 3/8” OD 3/4” OD 3/8” OD 7/8” OD 1/2” OD 74 99
048 YAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 115
060 YAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 112
070 YAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 108 132
026 YAH026 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 52 74
038 YAH036 3/4” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 86
049 YAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 115
064 YAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 112
072 YAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 104 132
4/6/10
Determining Subcooling
1.  Measure the temperature of the liquid line on the small 
refrigerant line (liquid line) just outside the split cabinet. This 
location will be adequate for measurement in both modes unless 
a significant temperature drop in the liquid line is anticipated. 
2.  Measure the liquid line pressure by attaching refrigerant 
gauges to the Schrader connection on the liquid line
service valve.
3.  Convert the pressure obtained in Step 2 to the saturation 
temperature by using the R-410A Pressure/Temperature 
Conversion Chart.
4.  Subtract the temperature in Step 1 from the temperature in 
Step 3. The difference will be the subcooling value for that 
unit. Refer to the Operating Parameters tables for subcooling 
ranges at specific enter water conditions.