Aurora Control System
NOTE: Refer to the Aurora Base Control Application and 
Troubleshooting Guide and the Instruction Guide: Aurora Interface and 
Diagnostics (AID) Tool for additional information. 
To check the unit control board for proper operation:
1.  Disconnect thermostat wires at the control board.
2.  Jumper the desired test input (Y1, Y2, W, O or G) to the R 
  terminal to simulate a thermostat signal.
3.  If control functions properly:
•  Check for thermostat and field control wiring (use 
  the diagnostic inputs mode).
4.  If control responds improperly:
•  Ensure that component being controlled is functioning 
(compressor, blower, reversing valve, etc.).
•  Ensure that wiring from control to the component
is correct.
•  Refer to the Aurora Base Control Application and 
Troubleshooting Guide and the Instruction Guide: Aurora 
Interface and Diagnostics (AID) Tool for additional information.
Troubleshooting
Refrigerant Systems 
To maintain sealed circuit integrity, do not install service gauges 
unless unit operation appears abnormal. Compare the change in 
temperature on the air side as well as the water side to the Unit 
Operating Parameters tables. If the unit’s performance is not 
within the ranges listed, and the airflow and water flow are known 
to be correct, gauges should then be installed and superheat and 
subcooling numbers calculated. If superheat and subcooling are 
outside recommended ranges, an adjustment to the refrigerant 
charge may be necessary.
NOTE: 
Refrigerant tests must be made with hot water generator 
turned “OFF”. 
Verify that air and water flow rates are at proper levels 
before servicing the refrigerant circuit.