Technical Guide
5146416-YTG-A-0815
Johnson Controls Unitary Products 69
PERFORMANCE DATA - 5 TON
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
55 °F 65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
YCD60B21S
35 107 54.3 2.63 51.9 2.96 49.3 3.33 46.6 3.74 43.8 4.20 40.8 4.76 37.6 5.42
40 119 59.7 2.67 56.9 3.00 54.0 3.37 51.1 3.77 48.0 4.24 45.0 4.78 41.6 5.42
45 130 65.4 2.72 62.3 3.05 59.1 3.42 55.8 3.83 52.7 4.29 49.2 4.83 45.8 5.44
50 143 71.3 2.78 67.9 3.12 64.5 3.48 61.0 3.89 57.4 4.35 53.8 4.88 50.2 5.48
55 156 77.6 2.86 73.9 3.19 70.2 3.56 66.4 3.96 62.4 4.43 58.6 4.95 54.7 5.56
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YCD60B21S
INDOOR COIL MODEL NO. CF60CXA1
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM 1520 1720 1920
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
55
T.C. 50.4 55.0 55.3 57.5 60.4 53.0 55.9 56.3 58.8 59.2 55.5 56.8 57.2 60.1 57.9
S.C. 50.4 45.3 40.7 38.7 30.9 52.6 47.0 41.8 39.8 31.0 52.5 48.6 42.9 41.0 31.1
KW 3.24 3.30 3.29 3.33 3.35 3.34 3.38 3.38 3.41 3.43 3.45 3.47 3.46 3.50 3.52
65
T.C. 50.8 54.9 54.9 58.0 60.0 52.6 55.5 55.8 58.9 59.5 54.5 56.1 56.7 59.9 59.0
S.C. 50.8 46.3 40.7 38.9 30.5 52.6 48.5 42.1 40.3 31.1 54.0 50.8 43.5 41.6 31.7
KW 3.57 3.64 3.62 3.67 3.69 3.67 3.71 3.71 3.75 3.78 3.77 3.78 3.79 3.84 3.86
75
T.C. 51.1 54.8 54.4 58.4 59.5 52.3 55.1 55.2 59.1 59.8 53.4 55.4 56.1 59.8 60.1
S.C. 51.1 47.2 40.7 39.1 30.2 52.3 50.1 42.3 40.7 31.2 53.4 53.1 44.0 42.3 32.2
KW 3.90 3.97 3.95 4.01 4.03 3.99 4.03 4.04 4.09 4.12 4.08 4.10 4.12 4.18 4.20
85
T.C. 49.1 52.4 51.8 57.0 59.7 50.5 53.0 52.5 57.0 59.2 51.9 53.6 53.3 57.0 58.6
S.C. 49.1 46.4 39.4 38.9 30.3 50.5 49.3 41.1 40.4 31.1 51.9 52.2 42.8 41.8 31.9
KW 4.35 4.41 4.40 4.47 4.51 4.44 4.49 4.48 4.55 4.59 4.54 4.57 4.57 4.63 4.67
95
T.C. 47.0 49.9 49.2 55.7 60.0 48.7 50.9
49.8 55.0 58.6 50.3 51.9 50.4 54.3 57.2
S.C. 47.0 45.5 38.2 38.6 30.5 48.7 48.5
39.9 40.0 31.0 50.3 51.4 41.6 41.4 31.5
KW 4.79 4.85 4.84 4.92 4.98 4.90 4.94
4.93 5.00 5.06 5.00 5.03 5.01 5.08 5.15
105
T.C. 44.1 45.5 45.2 51.6 56.7 45.9 46.5 46.2 51.5 55.8 47.6 47.5 47.1 51.5 54.8
S.C. 44.1 43.7 36.2 36.7 29.0 45.9 45.8 38.2 38.6 29.6 47.6 47.5 40.3 40.4 30.3
KW 5.38 5.41 5.41 5.47 5.57 5.47 5.49 5.49 5.56 5.67 5.57 5.57 5.57 5.65 5.78
115
T.C. 41.2 41.1 41.3 47.4 53.5 43.0 42.1 42.5 48.1 53.0 44.9 43.0 43.7 48.7 52.4
S.C. 41.2 41.1 34.2 34.9 27.4 43.0 42.1 36.6 37.2 28.3 44.9 43.0 39.0 39.4 29.1
KW 5.96 5.97 5.97 6.02 6.17 6.05 6.04 6.05 6.12 6.29 6.15 6.12 6.12 6.22 6.40
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.