Technical information
-/- Configuration of sensors
Description Range Units Value
Sensor B3 calibration. Coil pressure circuit 1 -9,9/9,9 bar 0
Sensor B4 calibration. Coil pressure circuit 2 -9,9/9,9 bar 0
Sensor B5 calibration. Inlet water temp. to exchanger. -9,9/9,9 K 0
Sensor B6 calibration. Outlet water temp. to exchanger. -9,9/9,9 K 0
Sensor B7 calibration. Outdoor temperature -9,9/9,9 K 0
Sensor B8 calibration. Dynamic set point -9,9/9,9 % 0
Enabling sensor B1 YES / NO - NO
Enabling sensor B2 YES / NO - NO
Enabling sensor B3. Coil pressure circuit 1 YES / NO - YES
Enabling sensor B4. Coil pressure circuit 2 YES / NO - YES
Enabling sensor B5. Inlet water temp. to exchanger. YES / NO - YES
Enabling sensor B6. Outlet water temp. to exchanger. YES / NO - YES
Enabling sensor B7 YES / NO - NO
Enabling sensor B8 YES / NO - NO
Enabling sensor B9. YES / NO - NO
Enabling sensor B10. YES / NO - NO
Sensor B3 configuration. Minimum value -30/150 bar 0
Sensor B3 configuration. Maximum value -30/151 bar 45
Sensor B4 configuration. Minimum value -30/152 bar 0
Sensor B4 configuration. Maximum value -30/153 bar 45
-A- Antifreeze
Description Range Units Value
Antifreeze alarm set point -99,9/99,9 °C 3
Antifreeze alarm set point differential 99,9 °K 5
Lower antifreeze alarm set point limit -99,9/99,9 °C 3
Upper antifreeze alarm set point limit -99,9/99,9 °C 5
Antifreeze alarm reset
MANUAL
AUTOMATIC
- MANUAL
Antifreeze alarm delay (If automatic reset has been selected) 0/540 Minutes 0
Antifreeze heater trigger set point -99,9/99,9 °C 3
Antifreeze heater trigger set point differential -99,9/99,9 °K 2
Auxiliary heater trigger set point (winter cycle) -99,9/99,9 °C 25
Auxiliary heater trigger set point differential (winter cycle) -99,9/99,9 °K 5
Auxiliary heater trigger delay 0/60 Minutes 15
Automatic enabling of the frost protection system with the unit OFF
DISABLED
HEATER AND PUMP
HEATER AND UNIT HEATER
- HEATER
1 Technical Information
1.13 Operating instructions