Technical information

-H- Unit configuration
Description Range Units Value
Unit type 0 ‑ 7 -
2 (COOLER)
3 (HEAT PUMP)
Number of compressors/circuits - 4 / 2
Compressor rotation
LIFO
FIFO
PERSONALISED
TIME
- FIFO
No. of evaporators 1 ‑ 2 - 1
Driver number (EVD400) 0-1-2-4 - 0
Cycle inversion valve logic NO / NC - NC
No. of pumps 1 ‑ 2 -
1 (SINGLE PUMP)
2 (TWO-PUMP ACCESSORY)
Pump rotation
START-UP
TIME
- TIME
Pump operation
ON WITH COMP. ON
ALWAYS OFF
ALWAYS ON
SAFETY ON/ OFF
ALWAYS ON
No. of hours for pump rotation 0 ‑ 9999 Hours 12
ON/OFF digital input activation YES / NO - NO
WINTER/SUMMER digital input activation YES / NO - NO
ON/OFF activation with Monitor YES / NO - NO
WINTER/SUMMER activation with Monitor YES / NO - NO
WINTER/SUMMER operation inversion delay Seconds 10
Monitoring protocol
CAREL
GSM MODEM
ANALOGUE MODEM
RS 232
LONWORKS
MODBUS
- CAREL
Selection of communication speed
1200
2400
4800
9600
19200
Bauds 19200
Monitoring ID number 0 ‑ 200 - 1
Selection of language at start-up YES / NO - YES
Restore default values (Warning!) YES / NO - NO
Technical Information 1
Operating instructions 1.13
111