Technical information

-P- Alarms
Description Range Units Value
High-pressure alarm set point (transducer B3; B4) 0 / 99,9 bar 41
High-pressure alarm differential (transducer B3; B4) 0 / 99,9 bar 10
Summer low-pressure alarm 0 / 99,9 bar 3
Winter low-pressure alarm 0 / 99,9 bar 2
Defrost low-pressure alarm 0 / 99,9 bar 1
Low-pressure differential 0 / 99,9 bar 1
Low-pressure alarm delay on cold cycle start-up 0 ‑ 999 Seconds 60
Low-pressure alarm delay on heat cycle and defrost 0 ‑ 999 Seconds 0
Water flow control (flow switch) alarm delay on start-up 0 ‑ 999 Seconds 20
Water flow control (flow switch) alarm delay on operating 0 ‑ 9999 Seconds 5
Number of automatic reset alarm stoppages 0 ‑ 4 1
Maximum period for automatic reset alarms 0 ‑ 99 Minutes 60
Alarm selection with automatic reset: compressor thermal breaker
AUTOMATIC
/ MANUAL
AUTOMATIC
Alarm selection with automatic reset: fan thermal breaker
AUTOMATIC
/ MANUAL
AUTOMATIC
Alarm selection with automatic reset: low-pressure switch
AUTOMATIC
/ MANUAL
AUTOMATIC
Alarm selection with automatic reset: high-pressure switch
AUTOMATIC
/ MANUAL
AUTOMATIC
-r- Control
When this submenu is activated, the dynamic set point temperature appears (if this function is enabled).
Press Down to access the configuration menu.
Description Range Units Value
Set point in COOL °C 12
Set point in HEAT °C 40
Temperature control adjustment range °K 3
COOL set point lower limit °C 6
COOL set point upper limit °C 20
HEAT set point lower limit °C 25
HEAT set point upper limit °C 45
Temperature setting type INPUT / OUTPUT - INPUT
Setting type with input sensor PROPORTIONAL / P+I PROPORTIONAL
Integration time in each adjustment P+I 0 / 9999 Seconds 600
Max. increase time of call (output adjustment) 0 / 9999 Seconds 20
Min. increase time of call (output adjustment) 0 / 9999 Seconds 20
Max. decrease time of call (output adjustment) 0 / 9999 Seconds 10
Min. decrease time of call (output adjustment) 0 / 9999 Seconds 10
Temp. differential in which increase and decrease times vary
(output adjustment)
-99,9 / 99,9 °C 2
Forced stoppage in COOL cycle (output adjustment) -99,9 / 99,9 °C 5
Forced stoppage in HEAT cycle (output adjustment) -99,9 / 99,9 °C 47
Technical Information 1
Operating instructions 1.13
113