Technical information

Wiring diagrams YLCA / YLHA 100, 120 and 150 (µC3) 400.3.50
A The components in the box are not supplied by the manufacturer
B The components in the box are standard accessories supplied by the manufacturer
(*) On units with hydro kit only
(*)FC
If the unit has power and the digital input D1 is open, check that the sequence of phases
L1, L2, L3 is correct
Model
Q2
[A]
Cross-
section B
mm
2
F1 [A] F2 [A] F3 [A] F4 [A]
F5 [A]
REG
F6 [A]
REG
F7 [A]
REG
F8 [A]
REG
100 100 5 x 35 25 25 25 25 5,4 5,4 8 8
120 125 5 x 50 25 25 25 25 6 6 8 8
150 160 5 x 50 32 32 32 32 6,8 6,8 10 10