Technical information
Correcting factors for other glycol concentrations
% in weight
Ethylene glycol Propylene glycol
Capacity Absorbed power Capacity Absorbed power
10 1,061 1,025 1,097 1,033
20 1,036 1,015 1,067 1,023
30 1,015 1,005 1,026 1,008
35 1 1 1 1
40 0,985 0,995 0,974 0,992
50 0,954 0'985 0,923 0,977
If it is necessary to select different glycol percentages, correct the capacity and absorbed power capaciā
ties of tables 2 and 4 (35% ethylene glycol), multiplying them by the coefficients indicated in the table.
Altitude factors
Altitude Capacity factor compressor absorbed power factor
0 1 1
600 0,987 1,01
1200 0,973 1,02
1800 0,958 1,029
2400 0,943 1,038
1 Technical Information
1.6 Technical data
18